1. Catalogs
  2. HD FIRE PROTECT PVT. LTD.
  3. UPRIGHT, PENDENT AND RECESSED PENDENT SPRINKLER
video corpo

UPRIGHT, PENDENT AND RECESSED PENDENT SPRINKLER

UPRIGHT, PENDENT AND RECESSED  PENDENT SPRINKLER

UPRIGHT, PENDENT AND RECESSED PENDENT SPRINKLER

Product catalog summary
Technical Specifications
The document outlines the specifications for Upright, Pendent, and Recessed Pendent Sprinklers, available in both Standard and Quick Response types. Key specifications include:
  • Temperature Response: Standard (5mm glass bulb) and Quick (3mm glass bulb).
  • Coverage: Standard Coverage with a K-Factor of 5.6 US (80 metric).
  • Nominal Thread Size: ½” BSPT (NPT Optional).
  • Pressure Ratings: Max Working Pressure of 175 PSI (12 Bar), Factory Hydrostatic Test Pressure of 500 PSI (35 Bar), and Min Operating Pressure of 7 PSI (0.5 Bar).
  • Temperature Ratings: Range from 57°C (135°F) to 182°C (360°F).
  • Finishes: Brass, Chrome Plated, White Painted (RAL9010).
Product Description
The sprinklers are designed for light and ordinary hazards, featuring a compact design with various finishes and temperature ratings. Pendent sprinklers are installed in a pendent position, while upright sprinklers are installed upright. Recessed Pendent Sprinklers are used with escutcheon plates for finished ceilings.
Operation and Handling
The sprinklers operate using a heat-responsive frangible glass bulb. Proper care includes storing at ambient temperature, using original packing for shipment, and inspecting for damage before installation. Installation requires Teflon tape or soft thread sealant for leak-tight joints, and excessive torque should be avoided.
Maintenance and Inspection
Maintenance should follow NFPA 25 guidelines or other relevant authorities. The document emphasizes the importance of maintaining the fire protection system in proper condition.
Sprinkler Ratings
The document provides a table of sprinkler temperature classifications, NFPA maximum ceiling temperatures, and corresponding glass bulb colors.
Material Specifications
Key materials include brass for the deflector, load screw, and frame, copper for the cap, and a Belleville Washer coated with Teflon Tape for the seal.
Warranty and Liability
HD FIRE offers a two-year warranty against defects in material and workmanship under normal use. The warranty excludes misuse, improper installation, and unauthorized repairs. HD FIRE's liability is limited to the sale price of the product.
Notice
Installation must comply with NFPA standards and government codes. The company reserves the right to modify specifications without prior notice.
See more

Catalog excerpts

UPRIGHT, PENDENT AND RECESSED  PENDENT SPRINKLER-1

UPRIGHT, PENDENT AND RECESSED PENDENT SPRINKLER (standardTECHNICAL DATA Style Upright, Pendent and Recessed Pendent Temperature Standard Response - 5mm Response glass bulb Quick Response - 3mm glass bulb Coverage Standard Coverage Nominal Thread Vs” BSPT (NPT Optional) Pressure Factory Hydrostatic 500 PSI (35 Bar) Test Pressure Min. Operating 7 PSI (0.5 Bar) Pressure Temp. Rating 57°C (135° F), 68°C (155° F), Finish Brass, Chrome Plated, White Painted White shade is RAL9010. For other shades, contact marketing. Ordering Style, Temp. Rating & Information Response, Thread type, Finish, Approval required -UL or UL & FM SIN Number HD101 - Pendent, SR DESCRIPTION Pendent & Upright Sprinklers HD Pendent and Upright sprinklers are designed for use in light and ordinary hazards. The temperature response is standard response (5 mm glass bulb) and quick response (3mm glass bulb). The sprinklers come with compact design, glass bulb type, available in several different finishes and temperature ratings. The pendent sprinklers must be installed in pendent position, and upright sprinklers are to be installed in the upright position. Pendent Recessed Sprinklers are installed with adjustable or non-adjustable Escutcheon plates (also termed as Rosette plates). These are intended to be installed with finished ceilings. Escutcheon plate adjustment provides convenience in Pendent Sprinkler installation in case of areas with finished ceilings or walls. Response Type

 Open the catalog to page 1
UPRIGHT, PENDENT AND RECESSED  PENDENT SPRINKLER-2

Sprinkler Operation The Sprinkler operating device is state of the art heat responsive frangible glass bulb supplied by a world leader in this innovative technology. The glass bulb contains fluid which expands when exposed to heat. When rated temperature is reached, the bulb shatters and water flows through the sprinkler and strikes deflector, forming a uniform water spray pattern to control or extinguish fire. Care and Handling Sprinklers must be handled with due care, they must be stored at ambient temprature for best results. Storage as well as any onward shipment is to be made in original...

 Open the catalog to page 2
UPRIGHT, PENDENT AND RECESSED  PENDENT SPRINKLER-3

PENDENT & UPRIGHT SPRINKLER RECESSED PENDENT

 Open the catalog to page 3
UPRIGHT, PENDENT AND RECESSED  PENDENT SPRINKLER-4

LIMITED WARRANTY HD FIRE PROTECT PVT. LTD. hereby referred to as HD FIRE warrants to the original purchaser of the fire protection products manufactured by HD FIRE and to any other person to whom such equipment is transferred, that such products will be free from defect in material and workmanship under normal use and care, for two (2) years from the date of shipment by HD FIRE. Products or Components supplied or used by HD FIRE, but manufactured by others, are warranted only to the extent of the manufacturer’s warranty. No warranty is given for product or components which have been subject to...

 Open the catalog to page 4
*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.