Relief Valves

Relief Valves

Relief Valves

Product catalog summary
Introduction: This document provides guidelines for the installation, operation, and maintenance of Hayward relief valves. It emphasizes the importance of following instructions to prevent injury and damage.

Guarantee and Responsibility: Hayward guarantees its products against defects in material and workmanship but does not assume responsibility for damages due to improper installation, misuse, or chemical incompatibility. Users should verify compatibility and suitability for their specific applications.

Specifications: - Maximum fluid velocity: 8 feet per second.
- Designed for non-compressible liquids only.
- Avoid using with compressible fluids like compressed air or nitrogen.
- Consider temperature effects on piping systems.
- Caution advised for PVC and CPVC products below 40°F.

Installation: - Install valves close to the component needing protection.
- Minimize outlet piping length and avoid backpressure.
- Preset relief pressure before installation.
- Use a pressure gauge for accurate pressure setting.
- Follow specific guidelines for threaded connections using Teflon tape.

Adjustment: Relief valves are not factory set. Adjust the relief pressure by loosening the locknut and turning the adjustment screw. Tighten the locknut once the desired pressure is set.

Operation: Relief valves protect systems from overpressure. As pressure exceeds the set point, the piston lifts, allowing flow through the valve. Consider using different valve sizes or parallel installations based on system requirements.

Example: For a system with a maximum working pressure of 35 PSI and a relief pressure of 40 PSI, a 3/4” relief valve is suitable to pass a minimum of 13 GPM at 50 PSI.

Conclusion: Proper installation and maintenance of Hayward relief valves are crucial for system safety and efficiency. Always consult Hayward literature for specific operating conditions and limitations.
See more

Catalog excerpts

Relief Valves-1

1. Hayward guarantees its products against defective material and workmanship only. Hayward assumes no responsibility for damage or injuries resulting from improper installation, misapplication, or abuse of any product. 2. Hayward assumes no responsibility for damage or injury resulting from chemical incompatibility between its products and the process fluids to which they are subjected. Compatibility charts provided in Hayward literature are based on ambient temperatures of 70F and are for reference only. Customer should always test to determine application suitability. 3. Consult Hayward literature to determine operating pressure and temperature limitations before installing any Hayward product. Note that the maximum recommended fluid velocity through any Hayward product is eight feet per second. Higher flow rates can result in possible damage due to the water hammer effect. Also note that maximum operating pressure is dependent upon material selection as well as operating temperature. 4. Hayward products are designed primarily for use with non-compressible liquids. They should NEVER be used or tested with compressible fluids such as compressed air or nitrogen. 5. Systems should always be depressurized and drained prior to installing or maintaining Hayward products. 6. Temperature effect on piping systems should always be considered when the systems are initially designed. Piping systems must be designed and supported to prevent excess mechanical loading on Hayward equipment due to system misalignment, weight, shock, vibration, and the effects of thermal expansion and contraction. 7. Because PVC and CPVC plastic products become brittle below 40F, Hayward recommends caution in their installation and use below this temperature. 8. Published operating torque requirements are based upon testing of new valves using clean water at 70F. Valve torque is affected by many factors including fluid chemistry, viscosity, flow rate, and temperature. These should be considered when sizing electric or pneumatic actuators. 9. Due to differential thermal expansion rates between metal and plastic, transmittal of pipe vibration, and pipe loading forces DIRECT INSTALLATION OF METAL PIPE INTO PLASTIC CONNECTIONS IS NOT RECOMMENDED. Wherever installation of plastic valves into metal piping systems is necessary, it is recommended that at least 10 pipe diameter in length of plastic pipe be installed upstream and downstream of the plastic valve to compensate for the factors mentioned above. CARE MUST BE TAKEN TO AVOID OVER TIGHTENING A GAUGE IN THE RELIEF VALVE BODY > AS THIS MAY INDUCE EXCESSIVE STRESS THAT COULD CAUSE BODY FAILURE. A plastic nipple with a brass coupling can be used to avoid problems. The instrument can serve as a check of the system pressure , and helps to accurately set the desired relief pressure. The valve should be installed as close as practical to the component requiring protection. The length of outlet piping should be kept to a minimum. Backpressure on the outlet should be avoided, as backpressure will effect the performance of the valve. It is recommended that the desired relief pressure be preset before the valve is installed in the system. A 1/4 NPT plastic pipe plug is installed in the valve body when shipped. Before pressurizing the system, this plug may be removed , and replaced with a pressure gauge or combination gauge guard and gauge. > Threaded end connections are manufactured to ASTM specifications D2464-88. F437-88 and ANSI B2.1. Wrap threads of pipe with Teflon tape of 3 to 3-1/2 mil thickness. The tape should be wrapped in a clockwise direction starting at the first or second full thread. Overlap each wrap by, 1/2 the width of the tape. The wrap should be applied with sufficient tension to allow the threads of a single wrapped area to show through without cutting the tape. The wrap should continue for the full effective length of the thread. Pipe sizes 2Ԕ and greater will not benefit with more than a second wrap, due to the greater thread depth. To provide a leak proof joint, the pipe should be threaded into the end connection hand tightӔ. Using a strap wrench only . (Never use a stillson type wrench) tighten the joint an additional 1/2 to 1-1/2 turns past hand tight. Tightening beyond this point may induce excessive stress that could cause failure. > The relief valve is NOT factory set. To adjust the relief pressure, loosen the locknut, (see figure) and turn the adjustment screw counter clockwise to decrease the set relief pressure. Turn the adjustment screw clockwise to increase the set pressure. When the desired relief pressure has been set, tighten the locknut. >

 Open the catalog to page 1
Relief Valves-2

Hayward Relief valves are designed for use in piping systems where over pressure of the system may cause damage or failure to other components, such as filters, gauges, or tanks. As the line pressure in the system increases past the set relief pressure of the valve, the piston starts lifting off the seat. The higher the over pressure, the higher the piston lifts off the seat, the greater the flow rate through the valve. (See Chart) It may be desirable to select a relief valve different in size from that of your piping system, or to install two relief valves in parallel, depending upon your requirements....