PL630

Product catalog summary
Maximum Quantity of Entries Per Face: The document specifies the maximum number of entries per face for different thread sizes ranging from M16 to M75, with quantities varying from 1 to 10 depending on the size.
Enclosure Type: The enclosure type is PL630, made from glass-reinforced polyester, and is certified for increased safety under ATEX and IECEx standards.
Terminal Capacity: The document provides detailed specifications for terminal types WDU 2.5 to WDU 70N, including conductor size, maximum volts, and terminal content at maximum amps. The terminals operate at a minimum temperature of -50°C.
Technical Data: Key technical data includes increased safety certification (II 2 GD Exe II ExtD), certificate numbers, suitability for use in hazardous zones, construction and test standards, ingress protection ratings (IP66 and IP67), deluge protection, and operating temperature range (-60°C to +75°C). The temperature class is T6 at 40°C, with an optional T5 for higher ambient temperatures.
Certification and Standards: The document lists various certifications and standards, including IEC/EN 60079-0, IEC/EN 60079-7, IEC/EN 61241-0, and IEC/EN 61241-1. It also mentions alternative certification options and approvals for use in Kazakhstan.
Additional Notes: The document includes notes on junction box wattage factor, combined terminal resistance, and optional earth continuity plate specifications.
See more

Catalog excerpts

PL630-1

Enclosure Type: PL630 Glass Reinforced Polyester Increased Safety Exe Dual Certified ATEX / IECEx Technical Data • Increased Safety II 2 GD Exe II ExtD. • PL630 Certificate No’s: Baseefa06ATEX0117X and • Suitable for use in Zone 1, Zone 2, Zone 21 and • FACE C 4 off - 7mm mounting holes MAXIMUM QUANTITY OF ENTRIES PER FACE Thread Size Zone 22. Construction and Test Standards: IEC/EN 60079-0, IEC/EN 60079-7, IEC/EN 61241-0 and IEC/EN 61241-1. Ingress Protection: IP66 and IP67 to IEC/EN 60529. Deluge Protection to DTS01. Operating Temperature Range: -60°C to +75°C. Temperature Class and Ambient: T6 40°C, optional T5 with ambients up to 65°C. Pl630 Assembly Instruction Sheet: AI 273. ZPl630 Assembly Instruction Sheet: AI 272. Alternative certification options available: Exe II AExe II / Exe II GOST R-Exe IIU GOST K- Approved for use in Kazakhstan # Not possible with an Earth Continuity Plate. Optional: Earth Continuity Plate. For full technical specification, see Page 16 TERMINAL CAPACITY Terminal Type Max. Physical Terminal Content Reduced Terminal Content at Max. Terminal Amps Terminal Qty. Amps 23 17 For Junction Box Wattage Factor and Combined Terminal Resistance, see Pages 43 & 44 An earth terminal equal to that of the largest power terminal will be fitted. The terminals listed are restricted to a minimum operating temperature of -50°C.

 Open the catalog to page 1

Archived catalogs

  1. Cable Glands

    83  Pages

  2. Ex Connectors

    8  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.