• Products
  • Catalogs
  • News & Trends
  • Exhibitions

711

711

Product catalog summary
Ordering Information: The format for ordering cable glands/connectors is specified as Cable Gland/Connector Type, Size, and Thread. An example provided is '711 C 1" NPT'. Each cable gland comes with a two-part sealing compound and assembly instructions.
Cable Glands Overview: These are North American cable glands/connectors that are explosion-proof and approved under IECEx and ATEX standards for Flameproof Exd, Increased Safety Exe, and Restricted Breathing ExnR. They are dual marked with UL and ATEX as standard.
Features: The cable glands provide 360° armor grounding, a barrier seal to prevent explosion products from entering the cable, and an outer deluge seal to prevent moisture ingress. They are available in various materials including Brass, Nickel Plated Brass, 316 Stainless Steel, and Aluminium.
Applications: Suitable for outdoor or indoor use with continuous corrugated aluminium Metal Clad (MCHL) cable. Installation rules and regulations are detailed in the technical section.
Technical Data: The glands are UL listed (No: E84940) and suitable for use in various hazardous locations including Class 1, Division 1, and Class 1, Zone 2. They meet several construction and test standards such as UL 2225 and IEC/EN 60079 series. They offer ingress protection ratings of IP66, IP67, and IP68, and deluge protection to DTS01. The operating temperature range is -50°C to +60°C (UL) and -60°C to +80°C (ATEX/IECEx).
Cable Gland Selection Table: The table provides detailed specifications for different size references, including entry thread size, cable acceptance details, and hexagon dimensions. Sizes range from A (½" or ¾" NPT) to H (3½" NPT), with dimensions provided in inches and millimeters.
See more

Catalog excerpts

711-1

Cable Glands North American Cable Glands/Connectors Explosion Proof IECEx and ATEX Approved Flameproof Exd, Increased Safety Exe and Restricted Breathing ExnR (Note: Dual Marked UL & ATEX as standard). 'G' Approx (Fully Compressed Length) Compound Deluge Boot Entry Thread Size Size Ref. • Outdoor or indoor use. • For use with continuous corrugated aluminium Metal Clad (MCHL) cable. • See technical section for installation rules and regulations. Across Flats Across Corners All dimensions in inches (except * where dimensions are in millimetres). A - F size metric entry threads are 1.5mm pitch as standard, 15mm length of thread. For H size glands, a 2mm pitch is supplied as standard, 20mm length of thread (1.5mm pitch with 15mm length of thread can be supplied) please specify when ordering Technical Data • UL Listing No: E84940. • Suitable for use in: • Class 1, Division 1, Gas Groups A, B, C and D • Class 1, Zone 2, Gas Groups IIA, IIB and IIC • AExd IIC and AExe II Class 1, Zone 2. • Flameproof Exd, Increased Safety Exe II 2 GD and Restricted Breathing ExnR II 3G. • Certificate No’s: Sira 06ATEX1295X and IECEx SIR 06.0082X. • Suitable for use in Zone 1, Zone 2, Zone 21, Zone 22 and in Gas Groups IIA, IIB and IIC. • Construction and Test Standards: UL 2225, IEC/EN 60079-0, • • • • • IEC/EN 60079-1, IEC/EN 60079-7, IEC/EN 60079-15, IEC/EN 61241-0 and IEC/EN 61241-1. Ingress Protection: IP66, IP67 and IP 68 (30 metres for 7 days) to IEC/EN 60529 and NEMA 4X. Deluge Protection to DTS01. Operating Temperature Range: -50°C to +60°C (UL) and -60°C to +80°C (ATEX / IECEx). Assembly Instruction Sheet: AI 317 (UL) and AI 338 (ATEX / IECEx). Alternative certification options available: DNV Marine Approval • Provides 360° armour grounding which is fully Inspectable. • Grounding Device remains in contact with cable when disassembled for inspection. • Provides a barrier seal between the individual insulated • • • • • conductors within the cable and prevents entry of the products of an explosion into the cable. Assembly of the cable gland compresses and distributes the compound evenly to effect a barrier seal at the point of entry into the enclosure. Provides an outer deluge seal to prevent moisture ingress to the cable armour and enclosure. Deluge seal is coloured red to indicate Hazardous Location product. Provides a cable retention and low smoke and fume, zero halogen seal onto the cables outer jacket. Manufactured in Brass (standard), Nickel Plated Brass, 316 Stainless Steel or Aluminium. Brass NPT entries are nickel plated as standard. Ordering Information Format for ordering is as follows: Cable Gland / Connector Type 711 Two part sealing compound and assembly instructions are supplied with the cable gland. Connection Solutions www.ehawke.com

 Open the catalog to page 1

Archived catalogs

  1. Cable Glands

    83  Pages

  2. Ex Connectors

    8  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.