1. Catalogs
  2. H&b Sensors
  3. Isomators SEM1200

Isomators SEM1200

Isomators SEM1200

Product catalog summary
Overview: The SEM1200 is a dual output isolator designed to provide two separate isolated 4 to 20mA current signals from a primary loop. It requires external power for the output loops and allows for minor calibration adjustments via front-panel accessible potentiometers.
Specifications:
  • Input Type: Current input, 2-wire loop powered, with a range of 4 to 20 mA (maximum 30 mA).
  • Protection: Reverse connection protection.
  • Voltage Drop: Maximum of 5.0 V.
  • Output: Two 4 to 20 mA current sink outputs at 15 V DC.
  • Loop Voltage: 5 to 32 V DC, reverse protected, with specific load requirements based on voltage and ambient conditions.
  • Connection: Captive clamp screws, supporting cable sizes up to 4 mm sq solid or 2.5 mm sq stranded.
  • Case Material: Grey Polyamide, flammability rated to UL94-VO VDE 0304 Part 3, Level IIIA.
  • Dimensions: 60 x 75 x 12.5mm, with a mounting height of 67.5mm above the rail.
  • Mounting: Snap on "top hat" rail (DIN EN 50022-35).
  • Isolation: 500 V DC, flash tested at 1 kV, using opto coupler/transformer method.
  • Electrical Safety: Complies with BS EN61010-1, Pollution Degree 2, Installation Category II, Class I.
  • Ambient Conditions: Operates between 0 to 70ºC and 10 to 95% RH non-condensing.
  • Accuracy: ±0.05% (±0.008 mA) of full range output.
  • Stability: 0.01% per ºC.
  • Response Time: Less than 100 ms to reach 70% of the final value.
  • EMC: Tested to BS EN 61326.
  • Adjustments: Zero and Span Adjustment available for each channel.
Key Features: The SEM1200 provides reliable isolation and signal splitting for industrial applications, ensuring accurate and stable performance across a range of environmental conditions. It is designed for easy installation and adjustment, making it suitable for various industrial settings.
See more

Catalog excerpts

Isomators SEM1200-1

SEM1200 Loop Splitter Two 4 to 20mA Outputs The SEM1200 isolator is a dual output isolator, providing two separate isolated 4 to 20mA current signals from a primary loop. The output loops must be powered externally. Minor adjustments can be made to the calibration of the device via the two frontpanel accessible calibration potentiometers. Specification Input Type Range Protection Voltage Drop Output 1 & Output 2 @ 15 V dc Type 2 Wire current sink 4 to 20 mA Loop Voltage 5 to 32 V d.c. (reverse protected) Loop Volt Drop = 5 V Load = 900 ohm @ Vs = 24 V Load = 1200 ohm @ Vs 30 V Loop must be > 250Ω for ambients > 50 ºC Current input 2 wire Loop powered 4 to 20 mA (30 mA MAX) Reverse connection 5.0 V Maximum Connection Cable Size Case Material Flammability Dimensions Mounting Captive clamp screws Maximum 4 mm sq solid / 2.5 mm sq stranded Grey Polyamide To UL94-VO VDE 0304 Part 3, Level IIIA 60 x 75 x 12.5mm (67.5 above rail) Snap on “top hat” rail (DIN EN 50022-35) 500 V DC (flash tested @ 1 kV) between each port (Isolation method, opto coupler / transformer) Electrical Safety BS EN61010-1 POLLUTION DEGREE 2; INSTALLATION CAT II; CLASS I Ambient 0 to 70ºC ; 10 to 95 % RH non condensing Accuracy ±0.05 % (±0.008 mA ) of full range output Stability 0.01 % / ºC Response Time Less than 100 mS to reach 70 % of final value. EMC Tested to BS EN 61326 Adjustments Zero and Span Adjustment for each channel H&B Sensors Ltd | Odyssey House | Durban Road | Bognor Regis | West Sussex | PO22 9RH | United Kingdom Tel: +44(0)1243 866866 | Email: [email protected] | www.hbsensors.com

 Open the catalog to page 1
*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.