1. Catalogs
  2. Grünbeck Wasseraufbereitung
  3. Partial flow filter GENO-VARIO 3000 for heating and cooling cycles

Partial flow filter GENO-VARIO 3000 for heating and cooling cycles

Partial flow filter GENO-VARIO 3000 for heating and cooling cycles

Partial flow filter GENO-VARIO 3000 for heating and cooling cycles

Product catalog summary
Overview: The GENO®-VARIO 3000 is a partial flow filter designed for heating and cooling cycles, aimed at improving the quality of circulation water in closed networks. It operates by removing impurities and softening the water, ensuring compliance with VDI 2035 and AGFW 510 (VdTÜV 1466) guidelines.
Key Features:
  • Removes rust and impurities through a sand filter stage.
  • Softens water using an ion exchanger system.
  • Automatic backwash and regeneration processes, eliminating the need for filter material replacement.
  • Optional module for automatic make-up water feed with integrated leakage monitoring.
Functional Description: The system features a fully automatic control unit that monitors all functions, including differential pressure-controlled backwash and softener unit regeneration. This minimizes operating costs and maintenance efforts.
Technical Specifications:
  • Connection diameter: 1"
  • Max. capacity: 2.5 m³/h
  • Max. water/ambient temperature: 80/40°C
  • Nominal pressure: 10 bar
  • Power supply: 230 V/50 Hz
  • Dimensions: 1,100 x 1,650 x 765 mm
System Requirements: Information needed includes the type of water used, current water analysis, existing treatment systems, and any previous corrosion issues.
Recommendations: According to AGFW worksheet FW 510, 1-3% of the circulation water volume should be treated daily in the partial flow.
See more

Catalog excerpts

Partial flow filter GENO-VARIO 3000 for heating and cooling cycles-1

Partial flow filter GENO ®-VARIO 3000 for heating and cooling cycles 5 VDI 203 rding to Acco W 510 and AGF 1466) (VdTÜV NEW G Removal of rust and impurities G Softening G Automatic backwash and regeneration G No replacement of filter material required G Optional module for automatic make-up water feed with integrated leakage monitoring

 Open the catalog to page 1
Partial flow filter GENO-VARIO 3000 for heating and cooling cycles-2

GENO®-Vario 3000 | Partial flow filter for heating and cooling cycles Functional description The partial flow filter GENO®-VARIO 3000 is designed for the continuous improvement of the circulation water of closed heating or cooling networks. The circulation water is treated in two steps: By means of the sand filter stage, at first, all insoluble elements such as scale, rust or dirt particles are removed. Then, the ion exchanger system installed downstream completely softens the water. This is how a water quality complying with the applicable guidelines VDI 2035 and AGFW 510 (VdTÜV 1466) is attained....

 Open the catalog to page 2
*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.