video corpo

Model TAUB-L/H
16Pages

{{requestButtons}}

Catalog excerpts

Model TAUB-L/H - 1

Tube Axial Roof Upblast Model TAUB with Fabricated Steel Propeller • Belt Drive • Low and High Pressure mGREENHECK Building Value In Air.

Open the catalog to page 1
Model TAUB-L/H - 2

[B.GREENHECK Building Value in Air. Tube Axial Roof Upblast Fans Greenheck belt drive tube axial upblast roof exhausters, Models TAUB-L and TAUB-H, are designed to efficiently remove and disperse contaminated air. Model TAUB-L is designed for low pressure applications, Model TAUB-H for high pressure applications. The upblast configuration is ideal for exhausting contaminants away from a building to prevent roof damage and recirculation of exhaust air. With the selection of the appropriate high temperature option, the TAUB-L and TAUB-H can also exhaust heat and smoke for either emergency...

Open the catalog to page 2
Model TAUB-L/H - 3

Value Added Features Page Header AMCA Licensed & UL/cUL Listed All sizes and configurations of the TAUB-L and TAUB-H have AMCA licensed air and sound performance data. In addition, UL/cUL 705 and UL Power Ventilators for Smoke Control Systems listings are available for TAUB models. Motors may be either 50 or 60 Hz. Greenheck Fan Corporation certifies that the TAUB-L and TAUB-H fans shown herein are licensed to bear the AMCA Seal. The ratings shown are based on tests and procedures performed in accordance with AMCA Publication 211 and AMCA Publication 311 and comply with the requirements of...

Open the catalog to page 3
Model TAUB-L/H - 4

Tests were conducted at Greenheck’s research and design facilities using a 3.3 million BTU gas-fired burner capable of generating airstream temperatures in excess of 1000°F (538°C). Temperatures were monitored at the following critical locations throughout the tests: bearings, bearing compartment, belt tube, motor, motor compartment, airstream, and fan housing. The following high temperature options and their construction are a result of this extensive testing. CONTINUOUS HI-TEMP OPERATION • HT Option I - 200°-500°F (93o-260°C) The Model TAUB can be built to operate at up to 500°F...

Open the catalog to page 4
Model TAUB-L/H - 5

[^GREENHECK Building Value in Air. In 1972, Greenheck took the lead as the first commercial and industrial fan manufacturer to introduce electrostatic powder coatings. Today, Greenheck continues to lead by being the first to offer a superior zinc-rich powder basecoat and powder coating finish. This zinc-rich basecoat technology is used extensively outside the HVAC industry to protect bridge beams, automotive components and other heavy-gauge steel products. Now this advanced technology is exclusively available on Greenheck welded steel products. Greenheck’s coating process starts with a...

Open the catalog to page 5
Model TAUB-L/H - 6

Standard Construction Housing Housing is continuously welded to prevent air leakage. The fan tube, curb cap, windband and motor cover are constructed of heavy gauge steel with Permatector™ coating. Butterfly Dampers Butterfly style dampers feature rolled edges for strength and weather protection. Damper stops maintain proper blade position when fan is operating. Gaskets line the edge of fan discharge for quiet damper closure. For sizes 24-30 aluminum material is standard and steel is standard for sizes 36-60. Aluminum blades optional on larger sizes. Bearings Bearings are air handling...

Open the catalog to page 6
Model TAUB-L/H - 7

Page Header Outlet Screen Fusible Link Damper Lifter Butterfly Dampers Motor Cover Tie Down Points (4 per unit) Adjustable Motor Base Inspection Door Inlet Guard

Open the catalog to page 7
Model TAUB-L/H - 8

[B.GREENHECK Building Value in Air. Performance Data Imperial data — Metric data Material Gauges Minimum CFM required to open butterfly dampers All dimensions in inches (millimeters). TAUB-24L (Low Pressure) Performance ratings do not include the effects of appurtenances (accessories). Power ratings (BHP) does not include transmission losses. The sound ratings shown are loudness values in fan sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for Installation Type A: free inlet hemispherical sone levels. The AMCA Certified Ratings Sound...

Open the catalog to page 8
Model TAUB-L/H - 9

[^GREENHECK Building Value in Air. Performance Data Imperial data — Metric data Material Gauges Minimum CFM required to open butterfly dampers All dimensions in inches (millimeters). TAUB-30L (Low Pressure) Performance ratings do not include the effects of appurtenances (accessories). Power ratings (BHP) does not include transmission losses. The sound ratings shown are loudness values in fan sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for Installation Type A: free inlet hemispherical sone levels. The AMCA Certified Ratings Sound...

Open the catalog to page 9
Model TAUB-L/H - 10

[B.GREENHECK Building Value in Air. Performance Data Imperial data — Metric data Material Gauges Minimum CFM required to open butterfly dampers All dimensions in inches (millimeters). TAUB-36L (Low Pressure) Performance ratings do not include the effects of appurtenances (accessories). Power ratings (BHP) does not include transmission losses. The sound ratings shown are loudness values in fan sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for Installation Type A: free inlet hemispherical sone levels. The AMCA Certified Ratings Sound...

Open the catalog to page 10
Model TAUB-L/H - 11

[^GREENHECK Building Value in Air. Performance Data Imperial data — Metric data Material Gauges Minimum CFM required to open butterfly dampers All dimensions in inches (millimeters). TAUB-42L (Low Pressure) Performance ratings do not include the effects of appurtenances (accessories). Power ratings (BHP) does not include transmission losses. The sound ratings shown are loudness values in fan sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for Installation Type A: free inlet hemispherical sone levels. The AMCA Certified Ratings Sound...

Open the catalog to page 11
Model TAUB-L/H - 12

[B.GREENHECK Building Value in Air. Performance Data Imperial data — Metric data Material Gauges Minimum CFM required to open butterfly dampers All dimensions in inches (millimeters). TAUB-48L (Low Pressure) Performance ratings do not include the effects of appurtenances (accessories). Power ratings (BHP) does not include transmission losses. The sound ratings shown are loudness values in fan sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for Installation Type A: free inlet hemispherical sone levels. The AMCA Certified Ratings Sound...

Open the catalog to page 12

All Greenheck catalogs and technical brochures

  1. Model AX