video corpo

data sheet ENERGYMID
1 / 11Pages

Catalog excerpts

data sheet ENERGYMID - 1

energy meter for 2, 3 and 4-wire systems with 5 (80) A direct connection or 1 (6) A transformer connection (also includes 5(6) A)  Accuracy class B for industrial and commercial use, as well as for household use with highly demanding requirements  MID approval (conformity assessment procedure, modules B and D)  Configurable, multifunctional variants for acquiring reactive energy and grid state variables  4 quadrant measurement (import and export)  Universal pulse output (double) with adjustable pulse rate and pulse duration, as well as selectable voltage range via integrated interfaces: LON, M-Bus, Modbus RTU, TCP/IP (BACnet / Modbus TCP / HTTP), LPWAN (wireless interface supporting the LoRaWAN® protocol)  4 tariffs (hardware-controlled as standard feature), plus 4 additional tariffs (software controlled) with bus (features W1 / W2 / W4 / W7)  Certified load profile in accordance with PTB-A 50.7 and PTB-A 50.7-1 (feature Z2)  Indicates installation errors: phase sequence phase failure, reversed transformer polarity, overload  Tamper-proof cover, configuration disabling  Quality product made in Germany (Product characteristics are model and feature-dependent. See this document.) APPLICATIONS The MID1 certified energy meters included in the ENERGYMID product range are used to acquire and bill active energy in industrial, household, commercial and building management applications. Integrated 4-quadrant measurement permits measurement of energy import and export. 4 tariffs (hardware-controlled as standard feature) and, depending on model or version, 4 additional tariffs (software-controlled) can be selected. In combination with national approval of the integrated load profile (Z2) in accordance with PTB-A 50.7, this energy meter is also suitable for fulfilling legal energy requirements. Energy data are transmitted to superordinate management systems via various communication interfaces, e.g. for acquisition and optimization, as well as for building automation and control technology. Thanks to simple installation including detection of connection errors and flexible configuration options, it performs all measuring tasks highly proficiently.

Open the catalog to page 1
data sheet ENERGYMID - 2

Simply and conveniently specify the technical characteristics and other functions (e.g. pulse output, bus connection type and load profile) for your ENERGYMID energy meter via configurable features when placing your order – you get an individualized, device-specific variant which is perfectly matched to your needs. MULTIFUNCTIONAL VERSION Depending on the type of multifunctional variant, the meter is also capable of acquiring reactive power and indicating up to 33 additional measured quantities directly at the display. Voltage level, utilization of individual phases, reactive power...

Open the catalog to page 2
data sheet ENERGYMID - 3

TECHNICAL DATA Some of the technical data are model and feature-dependent: Device type and (optional) order features are selected when ordering  “Order Information” 8. All options are listed with corresponding identification in the following tables. DEVICE CHARACTERISTICS Connection Measurement type Multifunctional version Load profile Approval Accuracy class EM2281 / EM2289: direct EM2381 / EM2387 / EM2389: via transformer 4-quadrant measurement Optional: U, I, P, Q, S, PF, f, THD, IN (M1) / reactive energy (M2) / U, I, P, Q, S, PF, f, THD, IN THD, IN, reactive energy (M3) 1 Optional:...

Open the catalog to page 3
data sheet ENERGYMID - 4

ELECTRICAL SAFETY MECHANICAL DESIGN Pollution degree Protection class Insulating group Utilization category (electrical switchgear) (only for meters with direct connection) UC-2 (per EN 60947) Nominal insulation voltage Insulation test voltage Overload capacity Inputs: Output: Mechanical classification Input  output/housing: 4 kVAC Output  housing: 500 V (bus/S0) with V0 / V1 / V2 / V7 / V8 / V9 4 kV (pulse) with V3 / V4 All meters: continuous 1.15 Ur and Imax Direct connection: 5 × 3 s, Ur and 100 A (5 min. interval) Direct connection: 1 × 1 s, Ur and 250 A, 10 ms 2400 A Current...

Open the catalog to page 4
data sheet ENERGYMID - 5

DISPLAY LAYOUT INTERFACES The energy meters are equipped with two pulse outputs or one bus output as a standard feature. Main display (active energy* in kWh or MWh) (M2/M3: reactive energy* in kVArh or MVArh) Auxiliary display 1 (active power* in kW or MW) (M2/M3: reactive energy* or reactive power* in kVAr(h) or MVAr(h)) PULSE OUTPUT Auxiliary display 2 (e.g. IN, OUT for import or export) In case of error: error code alternates with momentary display * Transformer meter EM238x: CT and VT are taken into account / power: negative sign for export DIMENSIONAL DRAWING / INSTALLATION Pulse...

Open the catalog to page 5
data sheet ENERGYMID - 6

CONNECTIONS CIRCUIT DIAGRAMS – PULSE OUTPUT MECHANICAL CHARACTERISTICS All connection components are laid out as self-locking screw terminals, except for the TCP/IP interface which is equipped with an RJ-45 connector and the LPWAN interface which has an SMA antenna connector. External 24 VDC Voltage Source + t Energy Import (export) Feature V3 / V4: External AC/DC Voltage Source 24 Energy Import (export) Current input Fine wire: 6 to 16 mm² Solid wire: 6 to 25 mm² With wire end ferrule: 6 to 16 mm² Fine wire: 0.5 to 4 mm² Solid wire: 0.5 to 6 mm² With wire end ferrule: 0.5 to 2.5 mm²...

Open the catalog to page 6
data sheet ENERGYMID - 7

WIRING DIAGRAMS – CURRENT AND VOLTAGE EM2281 – Direct Connection 2-Wire System, Any Load 11 1 L1 N EM2289 – Direct Connection 4-Wire AC System, Any Load 11 1 L1 L2 L3 N EM2381 – Transformer Connection 2-Wire AC System, Any Load 1 L1 N EM2387 – Transformer Connection 3-Wire AC System, Any Load L1 L2 L3 EM2389 – Transformer Connection 4-Wire AC System, Any Load

Open the catalog to page 7
data sheet ENERGYMID - 8

ORDER INFORMATION Designation Article Number / Feature EM2281 energy meter for 2 wire system, 230 V, direct connection, 5(80) A EM2289 energy meter for 4-wire system, any load, direct connection, 5(80) A EM2381 energy meter for 2-wire system, 230 V, transformer connection,1(6) A (incl. 5(6) A) EM2387 energy meter for 3-wire system, any load, transformer connection, 1(6) A (incl. 5 (6) A EM2389 energy meter for 4-wire system, any load, transformer connection, 1(6) A (incl. 5 (6) A Programmable rate: 1 … 50,000 pulses per kWh sec. S0, programmable With reactive energy 1 With U, I, P, Q, S,...

Open the catalog to page 8

All GOSSEN METRAWATT GmbH catalogs and technical brochures

  1. METRAOHM 10

    3 Pages

  2. ENERGY METER

    4 Pages