EFX60

EFX60

Product catalog summary
Overview: The Navigator® emergency thermostatic mixing valves are designed to provide tepid water by mixing cold and hot water to a predetermined temperature, ensuring compliance with ANSI standards for emergency fixtures.
Specifications:
  • Temperature Range: 15.5°–37.7°C
  • Maximum Operating Pressure: 860 kPA
  • Maximum Inlet Temperature: 82°C
  • Recommended Inlet Temperature: 49°C – 60°C
  • Standard Set Point: 29°C
Features:
  • Exceeds ANSI Z358.1 standards
  • Integral Strainer Checkstops on Inlets
  • Adjustable Set Point within Temperature Range
  • Built-in Cold Water Bypass for safety
  • Positive Shutoff of Hot Supply when Cold Supply is lost
  • Easy Installation and Serviceability
  • Dirt and Lime Resistant
  • Includes Dial Thermometer
  • Factory Assembled and Tested
  • Universal Mounting Capability
Product Information: The Navigator EFX60, Art. no. 755 9753, is designed to ensure safety and compliance in emergency situations by providing a reliable source of tepid water, encouraging injured workers to remain under the water flow for the required duration.
See more

Catalog excerpts

EFX60-1

EMERGENCY MIXING VALVENAVIGATOR EFX60 Art. no. 755 9753 The Navigator® emergency thermostatic mixing valves provide tepid water (15.5°-37.7°C) by mixing cold and hot water to a predetermined temperature. Tepid water encourages injured workers to remain beneath the deluge of water released from the emergency fixture, for the entire ANSI required 15-minute flush. ANSI Z358.1-1998 first required tepid water and the 2004 standard outlined that definition of the temperature range in its appendix. Each Navigator Emergency TMV features a fixed cold-water bypass that will allow cold water to flow should the hot water exceed the predetermined temperature reflecting Bradley's commitment to customers, quality and its dedication to manufacturing quality products that protect your employees. • Exceeds ANSI Z358.1 • Integral Strainer Checkstops on Inlets • Adjustable Set Point within Temperature Range • Built-in Cold Water Bypass, Assuring Cold Flow • Positive Shutoff of Hot Supply When Cold Supply is Lost • Easy Installation and Serviceability • Dirt and Lime Resistant • Dial Thermometer • Factory Assembled and Tested • Universal Mounting Capability Maximum Operating Pressure 860 kPA Maximum Inlet Temperature 82°C Recommended Inlet Temperature 49°C - 60°C Temperature Range Set Point Std. 18°C to 32°C 29°C Flow Capacities- L/min.

 Open the catalog to page 1
*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.