Transmitter EC22 DS

Transmitter EC22 DS

Transmitter EC22 DS

Product catalog summary
Overview: The EC22 DS Transmitter is designed for monitoring exhaust gases, specifically carbon monoxide (CO) and nitrogen oxides (NO and NO₂), from gasoline and diesel engines in enclosed spaces. It addresses risks associated with high concentrations of these gases.
Specifications:
  • Measuring Principle: Electrochemical (EC)
  • Measuring Ranges: CO (0-200/300/500 ppm), NO (0-10/20/30/40/50 ppm), NO₂ (0-10/20/30/40/50 ppm)
  • Temperature Range: -20 to +50 °C
  • Humidity: 15 to 90% relative humidity
  • Air Pressure: 80 to 120 kPa
  • Power Supply: 6 to 30 V DC
  • Output Signal: RS-485
  • Protection Class: IP40
  • Dimensions: 97 x 123 x 50 mm
  • Weight: 125-150 g
Features:
  • Utilizes a proven electrochemical measuring principle for high sensitivity and accuracy.
  • Digital signal transmission via RS-485 interface (Modbus/RTU).
  • Integrated temperature compensation ensures measurement accuracy.
  • Service-friendly with app-based configuration, adjustment, and calibration via infrared interface.
  • Smart, plug-and-play sensors that are easily replaceable and automatically recognized.
Applications: Suitable for use in environments where internal combustion engines operate in enclosed or partially enclosed spaces, ensuring safety by monitoring and controlling gas concentrations.
Contact Information: GfG Gesellschaft für Gerätebau mbH, Klönnestraße 99, 44143 Dortmund, Germany. Phone: +49 231 56400-0, Email: [email protected]
See more

Catalog excerpts

Transmitter EC22 DS-1

Fixed gas detection systems Monitor exhaust gases from gasoline and diesel engines

 Open the catalog to page 1
Transmitter EC22 DS-2

Monitor exhaust gases from gasoline and diesel engines Wherever internal combustion engines are used in enclosed or partially enclosed spaces or buildings, there may be elevated concentrations of carbon monoxide (CO) and nitrogen oxides. Risks arise both from high instantaneous values and from exceeding the maximum short-term or long-term occupational exposure limits. information about the transmitter at hand and the adjustment of settings is done with one click. The EC22 DS dual sensor transmitter is designed to provide reliable and cost effective monitoring of these gases. Depending on the...

 Open the catalog to page 2
*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.