The Tia1 is a temperature converter designed for DIN rail mounting, converting signals from an RTD100 sensor to a 4-20mA current signal. It is suitable for installation in hazardous areas and complies with various safety and performance standards.

Specifications
  • Input: RTD100, 2 or 3 wires, compliant with EN60751.
  • Measuring Range: -220°C to 850°C, with a minimum span of 10°C.
  • Output: 4-20 mA current signal.
  • Power Supply: Standard model: 8V to 30V DC; ATEX version: 8V to 28V DC.
  • Accuracy: ≤ 0.1% F.S. or ≤ 0.5°C.
  • Response Time: Less than 2 seconds.
  • Warm-up Time: 5 minutes.

Certifications
  • EMC: EN 61326 & IEC 61000-6-2.
  • Intrinsic Safety: EN 60079-0, EN 60079-11, EN 60079-26.
  • ATEX and IECEx certified with certificate numbers INERIS 13ATEX0015X & INE13.0022X.

Electrical and Mechanical Characteristics
  • Load Resistance: Calculated as (Vsupply-8) / 0.0215 Ω.
  • Line Resistance Effect: 2.5°C/Ω for 2-wire RTD, configurable compensation.
  • Housing: Polycarbonate, dimensions 13mm x 110mm x 110mm, IP20 protection.
  • Weight: Approximately 200g.
  • Operating Temperature: -40°C to 85°C (non-ATEX version).
  • Storage Temperature: -40°C to 85°C.
  • Humidity: 5% to 95% without condensation.

Configuration
The Tia1 can be configured using ProgressXmanager Software or FDT/DTM. Configuration must be performed in a safe area and not connected to a probe in a hazardous area. The device connects to a computer via the TiX’link serial interface series. Configurable parameters include TAG number, response to probe and cable line fault, measurement range, and lead resistance for 2-wire circuits. Factory settings are for a 2-wire RTD100, a 0-200°C range, and a fault detection set to 21.5mA.

ATEX and IECEx Classification
The Tia1 is classified for use in explosive atmospheres with specific temperature ratings for gas and dust environments, ensuring compliance with safety standards.
See more

Catalog excerpts

Tia 1 - Temperature converter DIN rail mounting - RTD100 input-1

Tial Convertisseur de temperature montage rail DIN - Entree PtIOO Temperature converter DIN rail mounting - RTD100 input i Fonction Convertisseurs de temperature Tial destines a la conversion du signal issu d'une sonde Pt100 en un courant 4/20mA. Montage sur rail DIN. Installables en zone explosible (C.F. codification). J Caracteristiques electriques Entree capteur Pt100 2 ou 3 fils selon EN60751 Etendue de mesure max. -220°C a 850°C Gamme minimale 10°C Sortie 4/20 mA Alimentation Modele standard 8V ... 30 Vcc Version ATEX 8V ... 28 Vcc selon la valeur maximale Resistance de charge (Valimentation-8) / 0,0215 0 Detection de rupture de sonde ou de court circuit : Configurable 3,5 mA ou 21,5 mA NAMUR NE 43 Haut d'echelle 21,5 mA NAMUR NE 43 Bas d'echelle 3,5 mA Temps de chauffe 5 minutes Temps de reponse < 2 secondes Derive Tension d'alimentation : <0,01% du courant de boucle pour une variation de 0,1% de la tension d'alimentation Temperature : < 10% de la precision / degre Erreur due a la resistance de ligne : Pt100 2 fils 2,5°C/ 0 compensable par configuration Pt100 3 fils 2,5°C/ 0 de desequilibre entre fils i Function Tia1 temperature converters aimed at converting signals from RTD100 sensor to a standard 4 to 20mA current signal. Din rail mounting product. Certified to be installed in hazardous area (See codification). j Electrical data Input RTD100 2 or 3-wires according to EN60751 Max measuring range -220 to 850°C Minimum span 10°C Output Power supply Standard model ATEX version Accuracy 4/20 mA 8V ... 30 Vdc 8V ... 28 Vdc < 0.1% F.S. or < 0.5°C according to the maximal value (Vsupply-8) / 0.0215 0 Load resistance Shorted or broken line detection: Configurable 3.5 mA to 21.5 mA NAMUR NE43 Upscale 21.5 mA NAMUR NE43 Downscale 3.5 mA Warm-up time 5 minutes Drift Voltage supply: < 0.01% of the current in the loop for a variation of 0.1% of Vsupply Temperature: < 10% of accuracy / degree Line resistance effect 2-wires RTD 2.5 °C / 0, compensation is configurable Mechanical data Presentation Protection Masse T° d'utilisation T° de stockage Humidite relative Raccordement Taille maxi des fils BoTtier polycarbonate l = 13 mm, h = 110 mm, p = 110 mm IP 20 approx. 200 g. -40°C a +85°C (modeles NON ATEX) -40°C a +85°C 5% a 95% sans condensation. Bornes a visser demontables de 1x0,2 mm2 a 1x2,5 mm2 Housing Protection Weight Working T° Storage T° Relative humidity Connection Max. wire size Polycarbonate l = 13 mm, h = 110 mm, p = 110 mm IP 20 approx. 200 g -40°C to 85°C (non ATEX version) -40°C to 85°C 5% to 95% without condensing Removable screw terminals from 1x0,2 mm2 to 1x2,5 mm2 Concernant les produits ATEX et lECEx : Securite Intrinseque EN 60079-0 & CEI 60079-0 EN 60079-11 & CEI 60079-11 EN 60079-26 & CEI 60079-26 N° d'attestation INERIS 13ATEX0015X & INE13.0022X For ATEX and IECEx products: Intrinsic Safety EN 60079-0 & IEC 61241-0 EN 60079-11 & IEC 60079-11 EN 60079-26 & IEC 60079-26 Certificate N° INERIS 13ATEX0015X & INE13.0022X Classement IECEx / IECEx Classification ^BParametres ATEX de securite / ATEX safety parameters Parametres d'entree / Input parameters Entre les bornes / Between terminals «1» & «2» U. I. P. C L Nota : Le cable d'alimentation du Tia1 ne doit pas exceder une inductance de 20mH. The supplying cable of the Tia1 must have a maximum inductance of 20mH. Parametres de sortie / Output parameters Entres les bornes / Between terminals «3», «4», «7» & «8» I u; i; p; c L~ FC-Tial-FREN-29-03-2013 Subject to modifications due to technical advances / Soucieux d'ameliorer nos produits, nous nous reservons le droit de reviser sans preavis les caracteristiques de nos produits

 Open the catalog to page 1
Tia 1 - Temperature converter DIN rail mounting - RTD100 input-2

Tial Convertisseur de temperature montage rail DIN - Entree PtIOO Temperature converter DIN rail mounting - RTD100 input Raccordement typique / Typical wiring Type de protection Method of protection 2 ways of configuration are possible: - With ProgressXmanager Software - With FDT/DTM These programming supports (ProgressXmanager, CommDTM GEORGIN and DTM Tial) are available on our web site. Product configuration must be done in SAFE AREA and not connected to a probe in hazardous area. Connection to the computer must be done with the TiX'link serial interface series. Configurable parameters: - TAG...

 Open the catalog to page 2

All GEORGIN S.A. catalogs and technical brochures

  1. S5UI

    2  Pages

  2. GP Serie

    2  Pages

  3. GS/GSX

    2  Pages

  4. SR2 series

    2  Pages

  5. TR/TA.02

    2  Pages

  6. TR/TA.01

    2  Pages

  7. GR/GA

    2  Pages

  8. (D)MLFK

    2  Pages

  9. AIRGAS

    2  Pages

  10. U series

    2  Pages

  11. P Series

    16  Pages

  12. SG

    2  Pages

  13. BVL/M/NT(I)

    2  Pages

  14. BEKA's range

    182  Pages

  15. GN 25000

    2  Pages

  16. GN 21000

    2  Pages

  17. GH 11000

    2  Pages

  18. GC 52500

    2  Pages

  19. GC 52100

    2  Pages

  20. GB 64000

    2  Pages

  21. fc-pn

    48  Pages

  22. fc-gc6rfbg

    2  Pages

  23. fc-fm

    39  Pages

  24. A3300-31/51

    2  Pages

Archived catalogs

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.