Overview: The document is a technical data sheet for the FKBDM series of pressure transmitters by Georgin, designed for absolute, differential, and gauge pressure measurements with remote seals. These transmitters are part of the ProcessX series and are known for their high accuracy and advanced features.
Features:
  • High Accuracy: Differential and gauge models offer 0.065% accuracy, while absolute models provide 0.2% accuracy.
  • Design and Inventory: Interchangeable electronics and housing across all ProcessX transmitters, with a welded design for high pressure services.
  • Environmental Protection: Advanced Floating Cell design minimizes temperature and overpressure effects.
  • Communication Protocols: Supports both Georgin proprietary and HART® protocols.
  • Application Flexibility: Options include hazardous area approvals, RFI filters, lightning arresters, and various material selections.
  • Programmable Output: Output signal can be programmed with up to 14 compensated points.
  • Burnout Current Flexibility: Adjustable burnout signal levels.
  • Dry Calibration: Reliable dry calibration without reference pressure.
Specifications:
  • Types: FKD (differential), FKB (gauge), FKM (absolute) pressure transmitters.
  • Service: Suitable for liquid, gas, or vapor.
  • Output Signal: 4 to 20 mA DC with digital signal superimposed.
  • Power Supply: Operates on 10.5 to 45 V DC.
Performance:
  • Accuracy: Varies by model and span, with specific ratings for different conditions.
  • Stability: ±0.2% of URL for 10 years.
  • Temperature Effect: Detailed effects on zero shift and total effect for different models.
  • Zero/Span Adjustment: Adjustable via HHC or external screws.
Installation and Safety:
  • Explosion Proof and Intrinsic Safety: ATEX and IECEx certified for various hazardous locations.
  • Mounting: Options for direct or pipe/wall mounting.
  • Environmental Protection: Rated IP66/IP67 and NEMA4X.
Optional Features:
  • Indicators: Analog and LCD options available.
  • Surge Protection: Built-in arrester for lightning surges.
  • Material Compliance: Meets NACE MR 0175/ISO 15156 standards.
Conclusion: The FKBDM series offers robust and flexible solutions for pressure measurement in various industrial applications, with advanced features for accuracy, communication, and environmental protection.
Specifications:
The document outlines the specifications for pressure transmitters and diaphragm seals used in various industrial applications. It includes details on conduit connections, diaphragm seal ratings, and span ranges for different pressure levels. The standard fill fluid for measuring cells is silicone oil, with other fluids available upon request. Bolts and nuts must conform to NACE MR 0175/ISO 15156 standards for certain services.

Procedures:
Mounting designs are specified for both capillary and rigid configurations, with temperature corrections required for certain designs. The document also details the requirements for hazardous location approvals, including ATEX and IECEx certifications.

Norms and Standards:
The document emphasizes compliance with NACE MR 0175/ISO 15156 for bolts and nuts, and provides guidelines for operating pressures and materials used in construction. It also specifies the ambient and process temperature limits for different mounting designs.

Recommendations:
For optimal performance, a turn down of 100:1 is recommended, but should be used at spans greater than 1/10 of the maximum span. The document advises consulting Georgin for specific applications and operating conditions.

Key Data from Tables:
The tables provide detailed information on the types of transmitters, conduit connections, diaphragm seal ratings, and span ranges. They also list the materials used for wetted parts and other components, emphasizing the use of stainless steel and other corrosion-resistant materials.

Critical Information:
It is critical to use the correct bolts and nuts for NACE MR 0175/ISO 15156 service, and to ensure that the appropriate approvals are obtained for hazardous locations. The document also highlights the importance of temperature correction for transmitters with different diaphragm seals or capillary lengths.
Diaphragm Seal Types: The document outlines various diaphragm seal types suitable for different mounting and operating conditions, including flush mounting designs, seals with extensions, and those for sanitary applications adhering to DIN, SMS, or Tri-Clamp standards.
Pressure Limits: The working pressure is limited by the static pressure or the nominal flange rating of the diaphragm seal. For vacuum service, the lowest vacuum for differential or gauge pressure transmitters is 20 Torr or 27 mbar abs, while absolute pressure transmitters can be used down to absolute zero.
Performance Specifications: The total performance is calculated by adding the performances of both the transmitter and the diaphragm seals. The accuracy error increases by 0.1% of the span when diaphragm seals are assembled on a transmitter. Ambient and process temperature effects are detailed, with specific values provided for different diaphragm materials and configurations.
Filling Fluids: Various filling fluids are specified, including silicone oil, fluorinated oil, and sanitary fill fluid, each with different temperature resistances and densities. Special applications may require consultation with Georgin for appropriate filling fluids.
Design and Material Options: The document provides detailed specifications for diaphragm seal designs, including material options like SS 316L, Hastelloy-C, Monel, and others. It also covers transmission methods from diaphragm seal to measuring cell, including capillary and rigid designs.
Outline Dimensions: Dimensions for different mounting designs, including rigid and capillary mounted diaphragm seals, are provided. The document includes weight specifications and additional options like indicator and stainless steel housing.
Flange and Adaptor Dimensions: Detailed dimensions for flanges and adaptors according to DIN and ANSI standards are included, along with weight considerations for various configurations.
Sanitary Applications: Seals for sanitary and pharmaceutical applications are available in DIN, SMS, and Tri-Clamp standards, with specific designs for DIN 11851 and SMS.
Specifications:
The document provides specifications for diaphragm seals and their dimensions according to DIN 11851 and SMS standards. It lists the nominal diameter (DN), pressure nominal (PN), and other dimensions such as D, h, dM, and G for various sizes.

Standards and Compliance:
The document states that all models of the ProcessX series transmitters comply with the EMC Directive (2004/108/EC) and are in accordance with harmonized standards EN 61326-1:2006 and EN 61326-2-3:2006. These standards pertain to electrical equipment for measurement, control, and laboratory use, focusing on EMC requirements.

Emission and Immunity Requirements:
Emission limits are specified for frequency ranges from 30 to 1000 MHz, with limits set at 40 dB and 47 dB (µV/m) measured at 10 m distance, according to EN 55011 / CISPR 11 standards. Immunity requirements are detailed with test values for various phenomena such as electrostatic discharge, electromagnetic fields, magnetic fields, burst, surge, and conducted RF, referencing standards like EN 61000-4 series.

Performance Criteria:
Performance criteria are categorized as A and B, where A indicates normal performance within specification limits during testing, and B indicates temporary degradation or loss of function that is self-recovering.

Contact Information:
Contact details for GEORGIN France and Belgium are provided, including telephone, fax, and email addresses.
See more

Catalog excerpts

FKBDM - Absolute, differential and gauge pressure transmitter for remote seal(s)-1

FKBDM Absolute, differential and gauge pressure transmitter for remote seal(s) Span, range, and overrange limit : ■ DATA SHEET The ProcessX series absolute, differential and gauge pressure transmitters accurately measures and transmits proportional 4 to 20 mAdc signal. The transmitters utilize the unique micromachined capacitive silicon sensor with state-of-the-art microprocessor technology to provide exceptional performance and functionality. ■ FEATURES 1. High accuracy 0.065% accuracy is a standard feature for differential and gauge pressure models and 0.2% accuracy for absolute pressure models. The microcapacitance silicon sensor assures this feature for all elevated or suppressed calibration ranges without additional adjustment. 2. Minimum inventory and design Electronics unit, local indicators and electronics housing are interchageable among all ProcessX transmitters. Our differential, gauge and absolute pressure transmitters for remote seal(s) are welded design with reduced volume flange welded on cell's body to guarantee a perfect vac-cum tightness and high pressure services. 3. Minimum environmental influence The "Advanced Floating Cell" design which protects the pressure sensor against changes in temperature, and overpressure substantially reduces total measurement error in actual field applications. 4. Georgin/HART® bilingual communications protocol ProcessX series transmitter offers bilingual communications to speak both Georgin proprietary protocol and HART®. Any HART® compatible devices can communicate with ProcessX. 5. Application flexibility Various options that render the ProcessX suitable for almost any process applications include : • Full range of hazardous area approvals • Built-in RFI filter and lightning arrester • 5-digit LCD meter with engineering unit • Stainless steel electronics housing • Wide selection of materials • High temperature, high vacuum seals. 6. Programmable output Linearization Function Output signal can be freely programmable. Up to 14 compensated points at approximation. 7. Burnout current flexibility (Under Scale : 3.2 to 4.0 mA, Over Scale : 20.0 to 22.5 mA) Burnout signal level is adjustable using Model FXW or Hand Held Communicator (HHC) to comply with NAMUR NE43. 8. Dry calibration without reference pressure Thanks to the best combination of unique construction of mechanical parts (Sensor unit) and high performance electronics circuit (Electronics unit), reliability of dry calibration without reference pressure is at equal level as wet calibration. i Specifications Type : FKD : differential pressure transmitter with remote seal(s) FKB : gauge pressure transmitter with remote seal FKM : absolute pressure transmitter with remote seal Service : Liquid, gas, or vapour Remark : To minimize environmental influence, span should be greater than 1/40 of the max. span in most applications. *Important : For FKD#49, max possible overload pressure on LP side must be < 100 bar. The accuracy is not guaranteed when used at negative DP. Output signal : 4 to 20 mA DC (linear or square root) with digital signal superimposed on the analogic signal. Power supply : Transmitter operates on 10.5 to 45 V DC at transmitter terminals. 10.5 to 32 V DC for the units with optional arrester.

 Open the catalog to page 1
FKBDM - Absolute, differential and gauge pressure transmitter for remote seal(s)-2

FKBDM Absolute, differential and gauge pressure transmitter for remote seal(s) Load limitations : see figure below Note) The load resistance varies with the upper limit of the saturation current [I max] (I max [mA]+0.9)x10-3 Note : For communication with HHC(1) min. of 250 0 is required. Hazardous locations : Refer to the package insert for safe use.

 Open the catalog to page 2
FKBDM - Absolute, differential and gauge pressure transmitter for remote seal(s)-3

Under scale Probable over range (Note) (1) HHC : Hand Held Communicator Zero/span adjustment : Zero and span are adjustable from the HHC(1). Zero and span are also adjustable externally from the adjustment screw. Damping : Adjustable from HHC or local adjustment unit with LCD display. The time constant is adjustable between 0,06 to 32 sec. Zero elevation/suppression : Zero can be elevated or suppressed within the specified range limit of each sensor model between -100% to + 100% of URL for FKD. FKB : -1 bar to 100% of URL. Normal/reverse action : Selectable from HHC(1). Indication : Analog indicator...

 Open the catalog to page 3
FKBDM - Absolute, differential and gauge pressure transmitter for remote seal(s)-4

Absolute, differential and gauge pressure transmitter for remote seal(s) Static pressure effect (FKD) : Option : fluorinated oil Mounting bracket : SS 304L or SS 316L. Environmental protection : Zero shift : 0,2% of URL, for any overrange pressures (limited to the max. overrange pressure) Mounting bracket : Without : direct mounting With (option) : on 50 mm (2”) pipe or direct wall mounting. Overrange effect (FKD) : Zero shift : ± 0,15% of URL / 160 bar limit Supply voltage effect : Mass {weight}: Less than 0.005% of calibrated span per 1 V Refer to outline dimensions page 12 to 17. Diaphragm...

 Open the catalog to page 4
FKBDM - Absolute, differential and gauge pressure transmitter for remote seal(s)-5

Notes* : 1- Turn down of 100:1 is possible, but should be used at the span greater than 1/10 of the maximum span for better performance.. 2- Consult Georgin for your application with the specific operating conditions 3- For DN < 50 consult Georgin for your application with the specific operating conditions 4- Flange rating according max. operating pressure - for DN < 50 flange size and / or PN > 150, consult Georgin 5- Transmitter with capilary design has a standard mounting bracket - Rigid mounting design are always without mounting bracket 6- Codify bolts and nuts for all mounting even if p...

 Open the catalog to page 5
FKBDM - Absolute, differential and gauge pressure transmitter for remote seal(s)-6

Absolute, differential and gauge pressure transmitter for remote seal(s) Differential pressure transmitter - Smart, 4-20 mAdc + Georgin/Hart® digital signal Conduit connection T M20 x 1.5 Diaphragm seal rating 2 0 to 2/200 bar Indicator, arrester and initial setting Indicator Analog, 0-100% linear scale None None Initial setting Analog, Custom scale Analog, double scale Analog, 0-100% linear scale Analog, Custom scale Analog, double scale Digital, Custom scale digital signal Hart /Georgin Digital, Custom scale Digital, 0-100% with push button Digital, Custom scale with push button Digital, 0-100%...

 Open the catalog to page 6

All GEORGIN S.A. catalogs and technical brochures

  1. S5UI

    2  Pages

  2. GP Serie

    2  Pages

  3. GS/GSX

    2  Pages

  4. SR2 series

    2  Pages

  5. TR/TA.02

    2  Pages

  6. TR/TA.01

    2  Pages

  7. GR/GA

    2  Pages

  8. (D)MLFK

    2  Pages

  9. AIRGAS

    2  Pages

  10. U series

    2  Pages

  11. P Series

    16  Pages

  12. SG

    2  Pages

  13. BVL/M/NT(I)

    2  Pages

  14. BEKA's range

    182  Pages

  15. GN 25000

    2  Pages

  16. GN 21000

    2  Pages

  17. GH 11000

    2  Pages

  18. GC 52500

    2  Pages

  19. GC 52100

    2  Pages

  20. GB 64000

    2  Pages

  21. fc-pn

    48  Pages

  22. fc-gc6rfbg

    2  Pages

  23. fc-fm

    39  Pages

  24. A3300-31/51

    2  Pages

Archived catalogs

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.