High temperature
16Pages

{{requestButtons}}

Catalog excerpts

High temperature - 1

Gcu>e low voltage electrical manufacturer

Open the catalog to page 1
High temperature - 2

Fire rated switch disconnectors Switch disconnectors Ventilation and smoke extraction systems aim to help safe working conditions on building evacuation and fire rescue operations, diminishing roof temperatures and delaying lateral fire expansion in order to permit an effective fight against fire expansion. Standard EN- 12101-3:2015 applies to Smoke and heat control systems detailing on part 3 specifications for powered smoke and heat exhaust fans. In order to guarantee installation safety under emergency conditions all ventilation system components must comply with this...

Open the catalog to page 2
High temperature - 3

Fire rated switch disconnectors Tests The development of products rated to provide fire resistance in order to guarantee electrical functional integrity under extreme circumstances, does require the employment of specialist laboratories capable to reproduce, on a controlled manner, similar conditions to those that take place when a fire occurs. The recognized* AFITI laboratory has facilities that allow constant pressure and temperature monitoring on the testing area thus ensuring that the temperature curve is replicated as established by the standard. *ENAC Spanish recognized part of ILAC...

Open the catalog to page 3
High temperature - 4

Switch disconnectors Design and innovation A rapidly changing environment with increasing standard requirements on design and installation characteristics, motivates a technical team used to work on product solutions. The employment of innovative engineering techniques, use of advanced engineering tools, and operation with the latest manufacturing process, guarantee an excellent final outcome. LGAI Technological Center, S.A. Campus UAB s/n Apartado de Correos 18 E - 08193 Bellaterra (Barcelona) T +34 93 567 20 00 F +34 93 567 20 01 www.applus.com LGAI LGAI Technological Center, S.A. Campus...

Open the catalog to page 4
High temperature - 5

low voltage electrical manufacturer Fire rated switch disconnectors fAPRDTEC Temperature classification Switch disconnectors testing must be conducted according to procedures established in standard EN 12101-3:2015 annex C. Fire rating categories are based on temperature and minimum time resistance according to EN 13501-4. F Class B XXX 41 F4- APadlockable handle B Padlockable in position 0 L Padlockable in position 0 and 1 Auxiliary contacts (12A) A 1 N.O. auxiliary contact G 1 N.O. + 1 N.C. auxiliary contacts Electrical schemes 552 Switch 3P

Open the catalog to page 5
High temperature - 6

Switch disconnectors General characteristics Stringent requirements according to standards EN 12101-3 have originated a highly demanding research task aiming to reach optimal resistance to high temperature operation Enclosure The enclosure has direct contact with the heating source and acts as a firewall diminishing direct heat into the switch. IP65 protection Sealing injected on the enclosure lid ensuring an IP65 degree of protection according to EN 60529. Advanced materials High performance polymers mixed with additives succeed to obtain high temperature switches able to resist erosion...

Open the catalog to page 6
High temperature - 7

low voltage electrical manufacturer Fire rated switch disconnectors fA PRDTEC Auxiliary contacts Maximum reliability, contact cams operated with the same shaft of main contacts. Construction with the same materials as main contacts avoids temperature related unbalance. Handle Safety/emergency handle with padlockable facility (up to 4 padlocks) on the disconnect position in order to guarantee safety during maintenance operations. Optionally padlockable in all positions. Surface finish Enclosure coated with epoxi polyester powder grey colour (RAL 7032 aluminium -7035 steel) semi-gloss...

Open the catalog to page 7
High temperature - 8

Switch disconnectors The range of F300 and F400 switch disconnectors share the aluminium enclosures that offer a high IP and IK rating. The F300 range is limited at 40A and the F400 is limited to 125A when using aluminium enclosures. F400 higher ratings (160-250A) use lightweight sheet steel enclosures for easy handling and installation. All the range follows a surface treatment consisting of a epoxy polyester powder coating by electrostatic projection and high temperature oven drying that provides excellent protection against chemical agents.

Open the catalog to page 8
High temperature - 9

low voltage electrical manufacturer Fire rated switch disconnectors fA PRDTEC F300 Classification F300 switches are based on advanced polyether polymers that are widely used on the motor and aeronautic industry due to its high temperature resistance combined with excellent wear, chemical and hydrolytic behaviour. Standard references

Open the catalog to page 9
High temperature - 10

Switch disconnectorsF400 Classification Standard references The stringent requirements on class F400 under fire conditions require the use of special composite materials that must combine good resistance to extreme temperatures while maintaining electrical characteristics requirements under IEC 947-3 when operating on normal conditions. To guarantee insulation characteristics we need the use of an specific contact block dedicated to F400 classified switches. Mechanical components also must be modified in order to pass product testing sequence which requires a minimum functioning period of...

Open the catalog to page 10
High temperature - 11

Fire rated switch disconnectors Enclosures and auxiliary contacts Reference

Open the catalog to page 11
High temperature - 12

Switch disconnectors Safety interlock High rating F400 switches (160-250A) are base mounted designs using sheet steel enclosures that grant easy cabling operations. They are equipped with a door interlock system that prevents access to live parts when in operati

Open the catalog to page 12
High temperature - 13

low voltage electrical manufacturer Fire rated switch disconnectors Fire rated F600 Constructing F600 switch disconnectors does require the use of very special materials able to overcome the extreme conditions under this category. The enclosure is on cold-laminated steel resistant to 600°C temperature. Developing a particular mechanical block for high temperature has also improved switch behaviour when shortcircuit occurs while keeping the electrical characteristics when operating under normal conditions. Technical characteristics

Open the catalog to page 13
High temperature - 14

Switch disconnectors Standard references 3 Poles Reference Enclosure size Enclosure size

Open the catalog to page 14