Catalog excerpts
S3 Series Control Panel Description Small Addressable Fire Alarm Control Panel The Gamewell-FCI, S3 Series Intelligent Fire Alarm Control Panel provides the latest innovative high-end processing power. The S3 Series is a digital, microprocessor-based system that offers a simple, intuitive solution for the small to mid-sized fire alarm applications. In standalone or network configurations, the S3 Series complies with most fire alarm application requirements. It supports either of the following types of networks. • Up to 64 nodes using the 7100 Series panel. • Up to 122 nodes using the S3 Series or E3 Series® panels. Use either twisted-pair wire or fiber-optic to network panels at a high-speed 625K baud ARCNET network bus. With flexible Boolean logic, intelligent detection, and Ethernet connectivity, this system provides power and versatility that surpasses comparable, small addressable fire alarm systems. The basic S3 Series consists of an SLP (Smart Loop Panel) main board, LCD-SLP touchscreen display, SLC loop personality modules, and 7 amp power supply. The SLP provides either one or two SLC loops in Class A or B configuration that supports either of the following protocols: • Up to 318 devices per loop using the System Sensor® protocol. If you add a second loop module, it increases the maximum device count to 636 devices. • Up to 126 devices per loop using the Apollo protocol. If you add a second loop module, it increases the maximum device count to 252 devices. Four Class B or two Class A NACs can be wired and synchronized using the System Sensor, Cooper-Wheelock, or Gentex strobes. To retrofit the SLP on the existing audible/ visual appliances, the on-board Electronic EOL (EEOL) automatically adjusts to the EOL resistor in the field. A 4.3" (10.92 cm) color touchscreen display screen shows the following: • Events on the system • Status of analog addressable devices • Complete diagnostic fault codes/messages • Five programmable function buttons with LED status for accessibility to the following functions: - Disable/Enable - Trouble Acknowledge - Bypass Output - Alarm Acknowledge - Lamp Test - Custom-defined • Listed per ANSI/UL® Standard 864 9th Edition. • IBC Seismic Certified. • Allows one SLC loop (expandable to two loops) that supports either System Sensor or Apollo devices in Class A or Class B (Style 4, 6 or 7). • System Sensor supports up to 318 intelligent devices and each SLC loop supports the following. - up to 159 detectors. - up to 159 modules (expandable to 636 maximum per panel). • Apollo supports up to 126 intelligent detectors and modules per SLC. (Expandable to 252 maximum per panel). • Includes a high resolution (4.3”) (10.92 cm) color touchscreen display. • Supports a network system of up to 122 nodes (includes E3 Series® panels) or up to 64 nodes (includes 7100 Series). • Provides 7.0 amp power supply (120VAC or 240VAC). • Includes four Class B or two Class A built-in Notification Appliance Circuits (NAC). Provides selectable System Sensor, Cooper-Wheelock, or Gentex strobe synchronization. • Supports up to 32 serial annunciators (LCD, LED-only, LED Switch). SIGNALING ® ® ® E3 Series , System Sensor and FocalPoint are registered trademarks of Honeywell International Inc. ® UL is a registered trademark of Underwriters Laboratories Inc. City of Chicago Approved FDNY: COA-#6162 7165-1703:0176 Class 1 Reference Certificate 12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118 Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use. www.gamewell-fci.com 9021-60730 Rev. F1 page 1 of 4 ©2015 by Honeywell International Inc. All rights reserved.
Open the catalog to page 1Application The S3 Series Fire Alarm and Life Safety System is an easy-to-use intelligent fire alarm solution designed for the small to mid-sized buildings. Analog technology delivers the benefits of a simple system installation, while a userfriendly interface makes panel operation and system maintenance quick and intuitive. Smart Panel Programming Using Boolean logic programming, the installer may customize the system to precisely suit the needs of the building owner. Auto-programming allows the installer to instantly locate all the devices on the SLC loop. Simple, Intuitive Display The...
Open the catalog to page 2Figure 2 illustrates the SLP-BB Cabinet Enclosure. Device Loops SLP-BB CABINET BACKBOX 14 1/2 "W SLP-BB CABINET OUTER DOOR 4 NAC Operating Voltage NAC Minimum Voltage SLC Loop Circuit Operating Voltage Input Voltage Up to two Class A or B, System Sensor units, each loop supporting up to 318 device addresses. OrApollo units, each loop supporting up to 126 device addresses per loop. 4 Class B or 2 Class A (2.0 A each circuit), 6.0 A total 24 VDC 19.5 VDC @ 20.4 V battery voltage 24 V peak-to-peak 120 VAC, 60 Hz 240 VAC 50-60 Hz Input Current 120 VAC, 2.75 amps max. 240 VAC, 1.4 amps max. Aux...
Open the catalog to page 3Ordering Information Ordering Information (Continued) Part Number SLP addressable FACP in black SLP-BB enclosure. Requires either an SLC-PM or an SLC95-PM for SLC loops. SLP addressable FACP with red door and black SLP-BB backbox. Requires either an SLC-PM or an SLC95-PM for SLC loops. SLP addressable FACP 240VAC power supply with red door and black SLP-BB backbox. Requires either an SLC-PM or an SLC95-PM for SLC loops. System Sensor Loop Card - 1 loop used for 159 sensors and 159 modules. For use with the SLP-E3 panels only. Apollo Loop Card-1 loop used for 126 sensors and modules. For use...
Open the catalog to page 4All Gamewell-FCI catalogs and technical brochures
-
IdentiFlex 100
2 Pages
-
7100 Series
3 Pages
-
Sensepoint Pro
6 Pages