D Series Sensors for Humidity and Temperature Measurement with calibrated dModul
10Pages

{{requestButtons}}

Catalog excerpts

D Series Sensors for Humidity and Temperature Measurement with calibrated dModul - 1

Galltec Mess- und Regeltechnik GmbH D-71149 Bondorf . Germany Tel. +49 (0)7457-9453-0 . Fax +49 (0)7457-3758 E-Mail: sensoren@galltec.de . Internet:www.galltec-mela.de MELA Sensortechnik GmbH D-07987 Mohlsdorf-Teichwolframsdorf . Germany Tel. +49(0)3661-62704-0 . Fax +49(0)3661-62704-20 E-Mail: mela@melasensor.de . Internet: www.galltec-mela.de D Series Sensors for Humidity and Temperature Measurement with calibrated dModul Type DK Industrial version, duct version Optional display • dynamic MELA® humidity sensing element • output of all hx values • calibrated dModul for humidity and temperature measurement • in situ alignment • easy to install • operating temperatures up to 80°C • optional USB interface The core part of the D Series is the digital calibrated dModul, which processes the measurement values of relative humidity and temperature individually. The values are compared to the calibration values stored in the dModul and communicated digitally to the transmitter electronics, where they are processed to standardised current and voltage signals. The housings of the industrial versions provide protection in accordance with IP 65. Only a single screw is required to close it securely. Technical data Humidity Electrical data measuring element output range measuring uncertainty 10...90 %RH at 10...40°C < 10 %RH or > 90 %RH at 10...40°C influence of temperature <10°C or >40°C output ranges 0...+50°C -30...+70°C 0...+100°C fully user configurable via optional USB interface measuring uncertainty with voltage output at 10...40°C with current output at 10...40°C influence of temperature <10°C or >40°C consumption of electronics (voltage output) load resistance (voltage output) Temperature measuring element voltage supply load RL (current output) Directive about electromagnetic compatibility 2014/30/EU DIN EN 61326-1 DIN EN 61326-2-3

Open the catalog to page 1
D Series Sensors for Humidity and Temperature Measurement with calibrated dModul - 2

General data measuring medium hx Values, selectable for two outputs air, pressureless, non-aggressive max. air speed protective cage w. membrane (basic equipment) min. air speed operating temperatures transformer part/housing (with display) (without display) at the sensor head storage temperatures connection wire diameter per connector total diameter cable degree of protection / measuring head protective cage w. membrane (basic equipment) PTFE sinterd filter (optional) relative humidity temperature -30...+70°C 0...100°C 0...50°C fully user configurable via optional USB interface absolute...

Open the catalog to page 2
D Series Sensors for Humidity and Temperature Measurement with calibrated dModul - 3

Product key D Series Thanks to the hx-converter the D Series offer a wide range of types. The product no. of each type consists of a 16-digit alpha numeric code that descibes the sensor The product key enables you to order the exact type of sensor for your application. Series Design Physical outputs Output signals Operating conditions / Special version Measured variable and Output range 1 Measured variable and Output range 2 Supply voltage (please observe specifications in order code table ) Measuring head / Filter / Diameter Design description Design description / sensor tube Order codes...

Open the catalog to page 3
D Series Sensors for Humidity and Temperature Measurement with calibrated dModul - 4

Technical Data Measured value and output range 1 Measured value and ouput range 2 hx-values (as shown on the right) only available for industrial versions DKK and DWK 6...30 V DC or 6...26 V AC / Sensors w. 0...1 V output signal 15...30 V DC or 13...26 V AC / Sensors w. 0...10 V output signal 10...30 V DC with galvanic isolation from the power supply / sensors w. 4...20mA output signal ZE08: protective cage, plastic, w. membrane, Ø 12 mm ZE05: sintered PTFE filter, IP65, Ø 12 mm Supply voltage Measuring head / Filter / Diameter Design description / options Order code Duct version without...

Open the catalog to page 4
D Series Sensors for Humidity and Temperature Measurement with calibrated dModul - 5

sintered filter made of fine-pored PTFE, IP 65, Ø 12 mm fixing flange, synthetic material, with fixing mechanism for easy sensor mounting and removal for sensors Ø 12 mm, with rubber sealing (enclosed in delivery) humidity standard to check the accuracy of the sensor at 12 %RH humidity standard to check the accuracy of the sensor at 75 %RH humidity standard to check the accuracy of the sensor at 33 %RH humidity standard to check the accuracy of the sensor at 84 %RH testing adapter for humidity standards for sensor tubes Ø 12 mm Drilling pattern The drilling pattern for mounting the sensor...

Open the catalog to page 5
D Series Sensors for Humidity and Temperature Measurement with calibrated dModul - 6

output humidity output humidity Electrical isolation from the power supply is necessary when using the USB interface! Electrical isolation from the power supply is necessary when using the USB interface! output humidity 0…1 V Ausgang Temperatur 0…10 V output humidity Ausgang Temperatur 0…1 0…10VV output humidity output humidity ESD protection advice The sensors of the D Series contain components, which can be damaged by the effects of electrical fields or by charge equalisation when touched. The following protective measures must be taken when the housing of the sensor is to be opened for...

Open the catalog to page 6
D Series Sensors for Humidity and Temperature Measurement with calibrated dModul - 7

(Instruction for transmitters without USB interface) During the in situ alignment the sensor does not necessarily have to be taken out of the control circuit. We offer humidity standards for alignment of the sensors (page 5: Accessories). Before calibrating the sensor, standards should remain at least 2 hours on the sensors. The temperature must remain constant during this time. For the correct temperature according to the humidity standard used, please refer to data sheet F5.2 Humidity Standards. During calibration temperature and humidity must remain constant. During calibration,...

Open the catalog to page 7
D Series Sensors for Humidity and Temperature Measurement with calibrated dModul - 8

Option: transmitter USB interface Figure 1 General information: The following settings can be made using the „Galltec-Mela USB Configuration Software“ and a standard micro USB cable. The transmitter is powered via USB. Except for adjustments, the transmitter requires no power via a power supply unit. Change of physically measured values Change of analogue output scaling / measuring range Change of temperature variables to °C or °F Air pressure input Single point adjustment of temperature and relative humidity Download: Software System requirements: Operating system USB Port: Software...

Open the catalog to page 8