1. Catalogs
  2. Furness Controls
  3. FCO432 - Differential Pressure Transmitter

FCO432 - Differential Pressure Transmitter

FCO432 - Differential Pressure Transmitter

FCO432 - Differential Pressure Transmitter

Product catalog summary
Overview: The FCO432 is a differential pressure transmitter designed for ultra-low pressure measurement in clean environments. It offers high accuracy, wide span adjustment, and multiple output configurations.
Key Features:
  • Accuracy: 0.25% of reading
  • Output: 2-wire mA or 4-wire voltage
  • Display: High brightness with optional OLED or LCD
  • Relays: Two configurable relays for alarms
  • Measurement Functions: Linear, square-root, and custom linearisation
  • Zero Control: Automatic or remote options
Models and Ranges: The transmitter is available in various models with pressure ranges from ±50Pa to -1bar to +10bar.
Output Options:
  • 2-wire 4-20mA (models 1 to 7)
  • 4-wire isolated 4-20mA and voltage options
Performance:
  • Enhanced Accuracy: <0.25% reading for 10% to 100% range
  • Standard Accuracy: <0.5% reading for 10% to 100% range
  • Temperature Coefficients: Enhanced zero and range <0.02%/°C
  • Long Term Drift: Typically 0.2% per annum
Construction:
  • Enclosure: IP54 rated ABS
  • Dimensions: W120mm x H85mm x D58mm
  • Materials: Copper, brass, nickel, mica, and PVC
  • Media Compatibility: Air and non-corrosive gases
Power Supply: Configurations include 9 to 40Vdc for 2-wire and 24Vdc for 4-wire setups.
Additional Information: The document notes that all information is provisional and subject to change without notice.
See more

Catalog excerpts

FCO432 - Differential Pressure Transmitter-1

Pressure Transmitter Accuracy 0.25% of reading Ultra low pressure measurement Wide span adjustment 2-wire mA or 4-wire voltage output High brightness display Two configurable relays Square-root output for flow/velocity Auto zero and remote zero options Suitable for a variety of clean environment applications, the FCO432 low differential pressure transmitter is available in a variety of voltage or current loop configurations. The output is scalable as linear to differential pressure or as a square-root function to facilitate the use of Pitot Static Tubes or other primary flow elements. Optional OLED or LCD may display a variety of engineering units, and two independent relays can provide alarm signals.

 Open the catalog to page 1
FCO432 - Differential Pressure Transmitter-2

Furness Controls has a UKAS accredited laboratory which offers pressure calibration from 0 to 40 kPa and flow calibration from 0.1 ml/min to 2000 litres/min Beeching Road • Bexhill On Sea East Sussex • UK • TN39 3LG Tel: +44 1424 819980 Email: [email protected] Web: www.furness-controls.com 27/11/2018

 Open the catalog to page 2
*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.