Overview: The FCO342 is a low differential pressure transmitter designed for clean environment applications. It features a robust IP64 stainless steel enclosure and offers various voltage or current loop configurations. The device is suitable for measuring ultra-low pressure with high accuracy and can be adjusted via PC using the FCO301 software utility.
Key Features:
  • Accuracy of 0.25% reading.
  • Ultra-low pressure measurement with wide span adjustment.
  • 2-wire mA, 3-wire, or 4-wire voltage output options.
  • Two configurable relays for alarm signals.
  • Square-root output for flow/velocity measurement.
  • Auto zero and remote zero options.
  • Large LCD display for various engineering units.
Models and Ranges:
  • Model1: ±50Pa
  • Model2: ±150Pa
  • Model3: ±500Pa
  • Model4: ±2500Pa
  • Model5: ±10kPa
  • Model6: ±20kPa
  • High pressure ranges available on request.
Output Options:
  • 2-wire 4-20mA
  • 3-wire voltage: 0-1 VDC to 0-10VDC full scale
  • 4-wire voltage: 0-1 VDC to 0-10VDC full scale
  • 4-wire voltage: ±1 VDC to ±10 VDC full scale
  • 4-wire isolated: any of the mA or voltages above
Performance:
  • Enhanced accuracy at 20°C: < ± (0.25% reading +1 digit) for 10% to 100% range.
  • Standard accuracy at 20°C: < ± (0.5% reading +1 digit) for 10% to 100% range.
  • Long-term drift: Typically 0.2% per annum.
  • Temperature coefficients: Standard zero < 0.2%/°C, range < 0.4%/°C; Enhanced zero < 0.02%/°C, range < 0.02%/°C.
  • Working temperature: -10 to 60°C.
Construction:
  • Enclosure: IP64 rated stainless steel with flush or wall mounting options.
  • Dimensions: Flush mount 160 x 160 x 54mm, Wall mount 156 x 162 x 56mm.
  • Materials in contact with media: Copper, brass, nickel, mica & PVC.
  • Media compatibility: Air and non-corrosive gases, max 95% humidity non-condensing.
  • Weight: 1.6kg.
See more

Catalog excerpts

FCO342 - Differential Pressure Transmitter-1

Furness Controls Pressure Transmitter Accuracy 0.25% Reading Ultra low pressure measurement Wide span adjustment 2-wire mA, 3-wire or 4-wire voltage output Two configurable relays Square-root output for flow/velocity Auto zero and remote zero options Robust stainless steel enclosure Suitable for a variety of clean environment applications the FCO342 low differential pressure transmitter is housed in a IP64 brushed stainless steel enclosure and is available in a variety of voltage or current loop configurations. The output is scalable as linear to differential pressure or as a square-root function to facilitate the use of Pitot Static Tubes or other primary flow elements. The large LCD may display a variety of engineering units, and two independent relays can provide alarm signals. The FCO342 can be adjusted from a PC using the FCO301 software utility and cable.

 Open the catalog to page 1
FCO342 - Differential Pressure Transmitter-2

Features Models/Ranges Output Options Furness Controls Display (Optional) Adjustable Damping Square Root function Trip Level Relays Zero Control Pneumatic Ports Model1: ±50Pa Model4: ±2500Pa High pressure ranges available on request Model2: ±150Pa Model5: ±10kPa Model3: ±500Pa Model6: ±20kPa 2 wire 4-20mA 3 wire voltage: 0-1 VDC to 0-10VDC full scale 4 wire voltage: 0-1 VDC to 0-10VDC full scale 4 wire voltage: ±1 VDC to ±10 VDC full scale 4 wire isolated: any of the mA or voltages above Most common differential pressure, volumetric flow, mass flow, and velocity units 0.0 to 60.0 seconds Optional...

 Open the catalog to page 2
*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.