1. Catalogs
  2. FUJI ELECTRIC France
  3. Datasheet temperature controller PXE4

Datasheet temperature controller PXE4

Datasheet temperature controller PXE4

Datasheet temperature controller PXE4

Product catalog summary
Overview: The PXE Digital Temperature Controller is a compact and versatile device designed for temperature regulation using thermocouples and RTD inputs. It supports ON-OFF and PID control methods.
Features:
  • Compact design with a depth of 62 mm.
  • Simple key operation.
  • Supports PID, fuzzy, and 2-degrees-of-freedom PID control.
  • NEMA 4X front panel for durability.
  • Dual control for heating and cooling.
  • Interface for parameter loader cable and free loader software.
Specifications:
  • Power Supply: 100 V (-15%) to 240 V (+10%) AC, 50/60 Hz.
  • Power Consumption: 5 VA or less at 100 V AC, 6 VA or less at 220 V AC.
  • Insulation Resistance: 20 MΩ or more (500 V DC).
  • Dielectric Strength: 1500 V AC for 1 min between power supply and others.
  • Input Impedance: Thermocouple: 1 MΩ or more.
  • Control Functions: PID, fuzzy, and 2-degrees-of-freedom PID control with auto-tuning, ON-OFF control.
  • Input Signals: Thermocouple types J, K, R, B, S, T, E, N, PLII, and RTD Pt100.
  • Output Options: Relay contact or SSR drive output.
Operation and Display:
  • Digital setting via 4 keys with key lock function.
  • Independent display of process and set values on a 4-digit, 7-segment LED.
  • Setting accuracy of 0.1% or less of measuring range.
Alarm and Control Output:
  • Supports absolute, deviation, and zone alarms with upper and lower limits.
  • Alarm ON-delay setting from 0 to 9999 sec.
  • During dual control, alarm output 1 functions as control output 2.
Additional Functions:
  • Parameter mask function for display customization.
  • Memory protection via non-volatile memory.
  • Self-check with program error supervision by watchdog timer.
Environmental Conditions:
  • Operating temperature: -10°C to 55°C.
  • Storage temperature: -20°C to 60°C.
  • Humidity: Less than 90% RH (no condensation).
Structure and Compliance:
  • Panel flush mounting with a protective structure equivalent to NEMA4X and IP66.
  • Complies with EU Directives LVD, EMC, and RoHS.
Dimensions: 48 × 48 × 63.5 mm, weight approximately 100g.
See more

Catalog excerpts

Datasheet temperature controller PXE4-1

Temperature Controller Digital temperature controller PXE is a compact and versatile controller that accepts thermocouples and RTD inputs and controls temperature with the ON-OFF control and PID control. 1. Compact design with a depth of 62 mm including 1.6 mm front panel 4. NEMA 4X front panel 5. Heating and cooling dual control 6. Interface for parameter loader cable (bus-power available) and free loader software SPECIFICATIONS 2. Control function Power supply voltage Control action Input signal 4. Output section of standard type (control output 1) Control output Select one as follows Relay contact: SPST contact: Electrical life 100,000 operations (rated load) Minimum switching current 100mA (24V DC) SSR drive (Voltage pulse): ON: 10.2 to 15 V DC OFF: 0.5V DC or less Max. current: 20mA or less

 Open the catalog to page 1
Datasheet temperature controller PXE4-2

11. Structure Parameter setting method 6. Alarm or control output 2 (option) Mounting method Alarm kind Table 1 Measuring range table During dual control, the alarm output 1 functions as the control output 2. The alarm is not turned ON immediately even when the process value is in the alarm band. It turns ON when it goes out the alarm band and enters again. Lower limit alarm ■ Lower limit alarm . (with hold) Parameter mask Selectable the Display/Non-display of all function parameters by parameter setting Settable the Display/Non-display of each __parameter block_ | Memory protection | Held by...

 Open the catalog to page 2
Datasheet temperature controller PXE4-3

Insulation block diagram Basic insulation (1500 V AC) Power Process value input Internal circuit Control output 1 (relay contact) Alarm output 1 (relay contact) or Control output 2 (relay contact) Alarm output 1 (relay contact) or Control output 2 (relay contact) Alarm output 2 (relay contact) Alarm output 2 (relay contact) When the 9th code is “J”: Each of the alarm output 1 and the alarm output 2 has independent COM terminal. When the 9th code is “1” or “2”: COM terminal is shared between the alarm output 1 and the alarm output 2 SSR drive control output 1 Thermocouple, Resistance bulb Pt100...

 Open the catalog to page 3
Datasheet temperature controller PXE4-4

CONNECTION DIAGRAM Alarm output 1 (AL1) or Control output 2 (OUT2)*1 ⑦ Relay contact output Thermocouple input Alarm output 1 (AL1) or Control output 2 (OUT2)*1 Alarm output 1 (AL1) or Control output 2 COM Relay contact output Thermocouple input *1: During dual control, the alarm output 1 functions as the control output 2. Caution on Safety *Before using this product, be sure to read its instruction manual in advance. Instrumentation & Sensors Planning Dept. 1, Fuji-machi, Hino-city, Tokyo 191-8502, Japan http://www.fujielectric.com Phone: +81-42-514-8930 Fax: +81-42-583-8275 http://www.fujielectric.com/products/instruments/...

 Open the catalog to page 4
*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.