video corpo

Outdoor disconnectors, Outdoor earthing switches
20Pages

{{requestButtons}}

Catalog excerpts

Outdoor disconnectors, Outdoor earthing switches - 2

The 1- and 3-pole OutdoorDisconnectors FTr areapplicable for a rated voltage range of 12 kV to 38,5 kV and a rated current range from 630 Ato 4000 A. The rated short time current upto 50 kAfor a duration of 3s depending on the type has been tested. The 3-pole > Installation can be carried out at heights of up to 1000 m above sea level. At heights above 1000 m the rated insulating level of the switch must be cor- rected accordingly. The switches are designed for normal operating conditions according to IEC 62271-1.According to this the following limiting values applies:Ambient temperature:...

Open the catalog to page 2
Outdoor disconnectors, Outdoor earthing switches - 3

12 kV50 Hz31,5 kA3 s80 kA75 kV 28 kV33 kgPD 3E0FT3-1083952-75314400 Type FES 12-20 Rated voltageRated frequency Rated short time current Rated duration of short-time circuit Rated peak withstand current Rated impulse withstand voltage - Phase to Earth Rated power frequency withstand voltage - Phase to Earth Weight approx. Pollution degree of the insulator Electrical life Drawing no. Part no. U > r 12 kV50 Hz20 kA3 s50 kA75 kV 28 kV31 kgPD 3E0FT3-44202/12-75314304 f > r I > k t > k I > p U > p U > d All switches are available with higher pollutiondegree on request! >

Open the catalog to page 3
Outdoor disconnectors, Outdoor earthing switches - 4

Type FES 24-20 FES 24-31,5 FES 24-63 Rated voltageRated frequency Rated short time current Rated duration of short-time circuit Rated peak withstand current Rated impulse withstand voltage - Phase to Earth Rated power frequency withstand voltage - Phase to Earth Weight approx. Pollution degree of the insulator Electrical life Drawing no. Part no. U > r 24 kV50 Hz20 kA3 s50 kA125 kV50 kV37 kgPD 3E0FT3-44202/52-75344305 24 kV50 Hz31,5 kA3 s80 kA125 kV50 kV46 kgPD 3E0FT3-1080502-75344405 24 kV50 Hz63 kA1 s160 kA125 kV50 kV49 kgPD 3E0FT3-44203/52-75344605 f > r I > k t > k I > p U > p U > d All...

Open the catalog to page 4
Outdoor disconnectors, Outdoor earthing switches - 5

FTr 12-630-25 FTr 12-1600-40 FTr 12-2500-40 FTr 12-4000-40 Rated voltageRated frequency Rated current Rated short time current Rated duration of short-time circuit Rated peak withstand current Rated impulse withstand voltage - Phase to Earth - Across the Open Gap Rated power frequency withstand voltage - Phase to Earth - Across the Open Gap Weight approx. Mechanical life Pollution degree of the insulator U > r 12 kV50 Hz630 A25 kA3 s63 kA75 kV85 kV28 kV32 kV138 kgM2PD 3 12 kV50 Hz1600 A40 kA3 s100 kA75 kV85 kV28 kV32 kV179 kgM2PD 3 12 kV50 Hz2500 A40 kA3 s100 kA75 kV85 kV28 kV32 kV200...

Open the catalog to page 5
Outdoor disconnectors, Outdoor earthing switches - 7

Type FTr 24-400-20 FTr 24-630-25 FTr 24-1600-40 FTr 24-2500-40 FTr 24-4000-40 Rated voltageRated frequency Rated current Rated short time current Rated duration of short-time circuit Rated peak withstand current Rated impulse withstand voltage - Phase to Earth - Across the Open Gap Rated power frequency withstand voltage - Phase to Earth - Across the Open Gap Weight approx. Mechanical life Pollution degree of the insulator U > r 24 kV50 Hz400 A20 kA3 s50 kA125 kV145 kV50 kV60 kV138 kgM2PD 3 24 kV50 Hz630 A25 kA3 s63 kA125 kV145 kV50 kV60 kV138 kgM2PD 3 24 kV50 Hz1600 A40 kA3 s100 kA125...

Open the catalog to page 7
Outdoor disconnectors, Outdoor earthing switches - 10

Type FTr 38,5-400-20 FTr 38,5-630-25 FTr 38,5-1600-31,5 FTr 38,5-2500-40 Rated voltageRated frequency Rated current Rated short time current Rated duration of short-time circuit Rated peak withstand current Rated impulse withstand voltage - Phase to Earth - Across the Open Gap Rated power frequency withstand voltage - Phase to Earth - Across the Open Gap Weight approx. Mechanical life Pollution degree of the insulator U > r 38,5 kV50 Hz400 A20 kA3 s50 kA180 kV210 kV80 kV90 kV128 kgM2PD 3 38,5 kV50 Hz630 A25 kA3 s63 kA180 kV210 kV80 kV90 kV138 kgM2PD 3 38,5 kV50 Hz1600 A31,5 kA3 s80 kA180...

Open the catalog to page 10
Outdoor disconnectors, Outdoor earthing switches - 14

All switches are available with higher pollution degree on request! > Type FTr 12-630-25-1 FTr 24-630-25-1 FTr 24-1600-40-1 FTr 38,5-630-25-1 Rated voltageRated frequency Rated current Rated short time current Rated duration of short-time circuit Rated peak withstand current Rated impulse withstand voltage - Phase to Earth - Across the Open Gap Rated power frequency withstand voltage - Phase to Earth - Across the Open Gap Weight approx. Mechanical life Pollution degree of the insulator U > r 12/√3 kV50 Hz630 A25 kA3 s63 kA75 kV85 kV28 kV32 kV12 kgM2PD 3 24/√3 kV50 Hz630 A25 kA3 s63 kA125...

Open the catalog to page 14
Outdoor disconnectors, Outdoor earthing switches - 19

Figure 1. Outdoor disconnector with fuse holders mounted below, with single drive2. Outdoor disconnector with earthing switch mounted below, with double drive Item 1a Single box-type actuator AZ4-7530/1, stroke 110 or 140 mm 1b Double box-type actuator AZ4-7530/2** 2 Single intermediate bearing AZ3-15936/1 2a Double intermediate bearing AZ3-15936/2 3 Single reversible bearing AZ3-17130/1 4 Double reversible bearing AZ3-17130/2 5 Forked clamping crank AZ3-9610/1 (gauge from 73 to 132.5 mm; hole matrix 8.5 mm)6 Single rod head AZ3-9609/7 (with link bush) 7Lower linkage rod, with bearing bush...

Open the catalog to page 19

All Fritz Driescher & Söhne GmbH catalogs and technical brochures

  1. B785

    12 Pages

  2. 780e

    12 Pages

  3. MCC_e

    4 Pages

  4. 881e

    16 Pages

  5. 843e

    12 Pages

  6. 786e

    8 Pages

  7. 788e

    12 Pages

  8. 787e

    8 Pages

  9. FTr 3-2000

    4 Pages