Overview: The document provides detailed technical specifications and operational guidelines for the DRIESCHER Indoor Switch-Disconnector H 22. It covers various types of switch-disconnectors, their advantages, energy storage mechanisms, arc extinction processes, and technical data.
Specifications: The switch-disconnectors are three-pole devices with rated voltages of 12 kV, 24 kV, 36 kV, and 38.5 kV, and rated currents of 630 A and 1250 A. They comply with DIN VDE 0670, part 301 / IEC 60265-1 standards.
Types of Switch-Disconnectors: The document describes different types of switch-disconnectors, including H 22 EK (without trip-free release), H 22 EA (with trip-free release), and H 22 SEA (with trip-free release and additional features like cross rails and HV HBC fuse holders).
Operating Conditions: Designed for normal operating conditions as per IEC 60697, class "Minus 5 Indoor", with ambient temperature peaks at 40°C and average 24-hour values at 35°C. Adjustments are necessary for altitudes over 1000 m due to reduced insulating power.
Arc Extinction: The arc extinction process involves a closed arcing chamber with pressure and expansion sections. Extinguishing plates and gases effectively cover the entire current range without requiring maintenance.
Main Advantages: The switch-disconnectors offer absolute operational reliability, visible isolating distance after load disconnection, convenient dimensions, easy operation, and high operating frequency with minimal maintenance.
Energy Storage Mechanism: The EK mechanism uses a single torsion spring for quick-make and quick-break operations, while the EA mechanism uses two torsion springs for trip-free operations. Actuation can be manual or motor-operated.
Technical Data: Detailed technical data includes rated voltage, frequency, current, peak withstand current, short-time current, making and breaking currents, and insulation levels. The document also provides part numbers and dimensions for various configurations.
Additional Features: Options for mounting earthing switches, mechanical interlocking, and release coils are available. The document emphasizes the importance of following transportation, mounting, and service instructions.