General Information
DRIESCHER has been a partner of Deutsche Bahn AG since the 1950s, focusing on reliable traction power supply. This collaboration led to the development of outdoor line sectionalizers with vacuum interrupters. The product range includes 1-pole and 2-pole switches for global railway operations, with projects in Spain, China, and South Africa.
Operating Conditions
The equipment is designed for installation up to 1000 meters above sea level, with necessary adjustments for higher altitudes. It complies with EN 62271-1, with ambient temperature limits of +40°C maximum and -40°C minimum.
Vacuum Switching
Vacuum technology offers reliable switching with minimal contact erosion and no oxidation. The FLa 15/97-1B switch is suitable for voltages from 15 kV to 29 kV, providing advantages like distinct separation between main and switching contacts and high loading capacity.
Technical Description
These switches are designed for railway applications and meet EN 50152-2 specifications. They feature silver-plated copper live parts, hot-galvanized steel parts, and optional silicon insulators. The switches operate with a visible isolating distance and can include earthing contacts.
Product Specifications
  • 1-pole Outdoor Switch-Disconnector FLa 15/97-1B: Available for 15 kV to 29 kV, with rated currents up to 2000 A. Features cast-resin insulators and U-profile baseframes.
  • 2-pole Outdoor Switch-Disconnector FLa 15/97-2B: Designed for 25 kV, with similar specifications and additional coupling shafts.
  • 1-pole Outdoor Disconnector FTr 25-2000-1B: Available for 25 kV and 27.5 kV, featuring cast-resin insulators and U-profile baseframes.
  • 2-pole Outdoor Disconnector FTr 25-2000-2B: Similar to the 1-pole version but with sheet metal baseframes and composite insulators.
Conclusion
DRIESCHER's outdoor switches for railway lines are designed to meet rigorous standards, offering reliable performance across various international railway projects. The use of vacuum technology and robust materials ensures long-lasting and efficient operation.
Overview
The document provides technical specifications and descriptions for various outdoor switches and disconnectors used in railway lines, manufactured by DRIESCHER. It includes details on different types of switches, their specifications, and operational arrangements.
Specifications
  • FTr 25-2000-2B: Nominal voltage of 29 kV, rated current of 2000 A, and a peak withstand current of 50 kA. It features a sheet metal baseframe and hot galvanized steel parts.
  • FTr 25-630-S1B: Nominal voltage of 25 kV, rated current of 630 A, and a peak withstand current of 50 kA. It includes an L-profile baseframe and cast-resin insulators.
  • FLaV 25-2000-16-1B and -2B: Designed for a nominal voltage of 25 kV and rated current of 2000 A, with a short-circuit making current of 40 kA. These switches are equipped with silicone composite insulators for adverse conditions.
  • FLa 15/9700-1B: Nominal voltage of 25 kV, rated current of 1600 A, and a peak withstand current of 80 kA. It features a steel baseframe and composite insulators.
Operational Arrangements
  • Details on crank inter-measurements, rotation angles, and torque for various types, including the universal motor drive UM 90.
Outdoor Fuse-Holders
  • FSu 25-200-1B: Nominal voltage of 25 kV, rated current of 200 A, and a creepage distance of 1550 mm. It is designed to hold high-voltage high-breaking-capacity fuses.
Standards and Testing
  • Type tests conducted according to EN 50152-2, EN 60129, EN 60694, and DIN EN 60282-1.
Product Range
  • Includes medium-voltage systems, low-voltage systems, driving gear, and accessories for various voltage levels.
See more

Catalog excerpts

DRIESCHER-Outdoor Switches for Railway lines-1

DRIESCHER -Outdoor Switches for Railway lines • 1-pole and 2-pole design • Nominal voltage up to 29 k' • Rated current up to 2000 A

 Open the catalog to page 1
DRIESCHER-Outdoor Switches for Railway lines-2

768 DRIESCHER - Outdoor switches for railway lines according to EN 50152-2 The general trend is now to use a vacuum, advantages Technical description, operating mode 1-pole outdoor switch-disconnector FLa 15/97-1B; cast-resign; Un 27.5 kV and 29 kV 2-pole outdoor switch-disconnector FLa 15/97-2B; cast-resign; Un 25 kV 1-pole outdoor switch-disconnector FLa 15/97-1B; composite; Un 25 kV and 27,5 kV 2-pole outdoor switch-disconnector FLa 15/97-2B; composite; Un 2 x 25 kV a. 52 kV AT 1-pole outdoor disconnector FTr-1B; cast-resign; Un 25 kV 2-pole outdoor disconnector FTr-2B; cast-resign; Un 25...

 Open the catalog to page 2
DRIESCHER-Outdoor Switches for Railway lines-3

768 DRIESCHER - Outdoor switches for railway lines Vacuum switching • The trend is to use a vacuum Basic research on switching in a vacuum began in Germany during the Seventies. At this time low-oil switches had become firmly established in medium voltage networks, based on their reliable operation over decades, and were accepted by users as reliable devices. In laboratory tests it proved that the vacuum switches were superior by far to the conventionally applied switching principles. All these requirements necessitate a switching unit with electrical properties that preferably do not change...

 Open the catalog to page 3
DRIESCHER-Outdoor Switches for Railway lines-4

768 DRIESCHER - Outdoor switches for railway lines Technical description General These Driescher outdoor switches are specially designed for railway applications. They meet the specifications according to the EN 50152-2. The 1-pole and 2-pole switches are designed for a rated voltage range from 15 kV to 29 kV and a rated current range of 630 A and 2000 A. The types of outdoor switch-disconnector and outdoor disconnecting switch mostly differ through the application of different cast-resin insulators (length and height of creepage path) as well as in the baseframes (U-profile and sheet-metal frame)....

 Open the catalog to page 4
DRIESCHER-Outdoor Switches for Railway lines-5

Typetests • according to DIN EN 50152-2 03/98 (VDE 0115 Part 320-2) U-Profile baseframe Steel parts hot galvanized according to QTL 0200, additional paint (accord. DB rule, material-no. 675.61) Cast-resin insulators

 Open the catalog to page 5
DRIESCHER-Outdoor Switches for Railway lines-6

Typetests • according to DIN EN 50152-2 03/98 (VDE 0115 Part 320-2) • U-Profile baseframe • Steel parts hot galvanized according to QTL 0200, additional paint (accord. DB rule, material-no. 675.61) • Cast-resin insulators

 Open the catalog to page 6
DRIESCHER-Outdoor Switches for Railway lines-7

Sheet metal baseframe Steel parts hot galvanized according to QTL 0200, additional paint (accord. DB rule, material-no. 675.61) Cast-resin insulators Coupling shaft with adjustable square-head operating crank

 Open the catalog to page 7
DRIESCHER-Outdoor Switches for Railway lines-8

Typetests • according to DIN EN 50152-2 03/98 (VDE 0115 Part 320-2) • U-Profile baseframe • Steel parts hot galvanized according to QTL 0200, additional paint (accord. DB rule, material-no. 675.61) • Composite insulators

 Open the catalog to page 8
DRIESCHER-Outdoor Switches for Railway lines-9

Type FLa 15/97-2B Nominal voltage Rated current Rated insulation level Rated impulse voltage Short-duration power-frequency test level Ua Rated breaking current I1 2000 A Rated cable-charging breaking current I4a 32 A Rated short-time withstand current Rated duration of short-curcuit current Rated peak withstand current Typetests • according to DIN EN 50152-2 03/98 (VDE 0115 Part 320-2) Rated short-circuit making current Creepage distance approx. Distance between phases min. Drawing-no. Part-no. Weight approx. • Sheet metal baseframe • Steel parts hot galvanized according to QTL 0200, additional...

 Open the catalog to page 9
DRIESCHER-Outdoor Switches for Railway lines-10

Typetests • according to DIN EN 50152-2 03/98 (VDE 0115 Part 320-2)

 Open the catalog to page 10
DRIESCHER-Outdoor Switches for Railway lines-11

768 DRIESCHER - Outdoor switches for railway lines 2-pole outdoor disconnector type FTr 25-2000-2B Type Nominal voltage Rated current Rated insulation level Rated impulse voltage Short-duration power-frequency test level Rated frequency (A.C.) Rated cable-charging breaking current Rated transformer breaking current Rated short-time withstand current Rated duration of short-curcuit current Rated peak withstand current Creepage distance approx. Distance between phases min. Typetests • according to DIN EN 50152-2 03/98 (VDE 0115 Part 320-2) Drawing-no. Part-no. Weight approx. • Sheet metal baseframe...

 Open the catalog to page 11
DRIESCHER-Outdoor Switches for Railway lines-12

Typetests • according to DIN EN 50152-2 03/98 (VDE 0115 Part 320-2) • Sheet metal baseframe • Steel parts hot galvanized according to QTL 0200, additional paint (accord. DB rule, material-no. 675.61) • Composite insulators

 Open the catalog to page 12
DRIESCHER-Outdoor Switches for Railway lines-13

768 DRIESCHER - Outdoor switches for railway lines 2-pole outdoor disconnector type FTr 25-2000-2B Type Nominal voltage Rated current Rated insulation level Rated impulse voltage Short-duration power-frequency test level Rated frequency (A.C.) Rated cable-charging breaking current Rated transformer breaking current Rated short-time withstand current Rated duration of short-curcuit current Rated peak withstand current Creepage distance approx. Distance between phases min. Typetests • according to DIN EN 50152-2 03/98 (VDE 0115 Part 320-2) Drawing-no. Part-no. Weight approx. • Sheet metal baseframe...

 Open the catalog to page 13
DRIESCHER-Outdoor Switches for Railway lines-14

768 DRIESCHER - Outdoor switches for railway lines 1-pole outdoor disconnector type FTr 25-630-S1B Type Nominal voltage Rated current Rated insulation level Rated impulse voltage Short-duration power-frequency test level Rated frequency (A.C.) Rated cable-charging breaking current Rated transformer breaking current Rated short-time withstand current Rated duration of short-curcuit current Rated peak withstand current Creepage distance approx. Drawing-No. Part-No. Weight approx. Typetests • according to EN 50152-2 03/98 (EN 60129 and EN 60694) • Steel parts hot galvanized • L-Profile baseframe...

 Open the catalog to page 14
DRIESCHER-Outdoor Switches for Railway lines-15

1-pole und 2-pole outdoor switch-disconnector FLaV 25- The 1-pole and 2-pole outdoor switch-disconnectors, types FLaV 25-2000-16-1B and -2B, are innovations developed specifically for the railway sector. Compared with the FLa 15/97-1B type, they offer increased short-circuit withstand capability. For this to be realised, it was necessary to provide the switching device with additional pre-arcing electrodes. Because of its modified functional characteristics, the switch-disconnector switch is capable of switching not only its rated making current of In 2000 A but also a short-circuit current of...

 Open the catalog to page 15

All Fritz Driescher & Söhne GmbH catalogs and technical brochures

  1. 780e

    12  Pages

  2. 881e

    16  Pages

  3. 843e

    12  Pages

  4. 786e

    8  Pages

  5. 788e

    12  Pages

  6. 787e

    8  Pages

  7. FTr 3-2000

    4  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.