Indoor Switches for Railway lines
Open the catalog to page 1767 DRIESCHER - Indoor switches for railway lines according to EN 50152-2 1-pole indoor disconnector with earthing switch L 31; Un 15 kV, 1600 A Fuse-holders L 31; Un 27.5 kV, High-voltage high-breaking-capacity fuses 24 kV and 36 kV Stroke limitation pads General These Driescher indoor switching devices are specifically designed for railway applications. They are in compliance with the specifications according to EN 50152-2. The 1-pole switches can be used for a rated voltage range of 15 kV to 27.5 kV, depending on the respective design, and for a rated current range of 400 A to 4000 A. References:...
Open the catalog to page 2DRIESCHER - Indoor switches for railway lines1-pole indoor switch-disconnector H 27-1B; Un 15 kV Type H 27-1B Rated insulation level UNm 17.5 kV Rated impulse voltage UNi 125 kV Short-duration power-frequency test level Ua 50 kV Rated breaking current I1 400 A Rated short-time withstand current Ik 16 kA Rated duration of short-curcuit current tk 1 s Rated peak withstand current Ip 40 kA Rated short-circuit making current Ima 40 kA • with motordrive and release coil • signalling contact (6-pole) and terminal strip • for contact line feeders and transformer-train preheating • Equipment Switch Wiring...
Open the catalog to page 3DRIESCHER - Indoor switches for railway lines1-pole indoor switch-disconnector H 29-1B; Un 15 kV Type H 29-1B Rated insulation level UNm 17.5 kV Rated impulse voltage UNi 125 kV Short-duration power-frequency test level Ua 50 kV Rated breaking current I1 100 A Rated short-time withstand current Ik 20 kA Rated duration of short-curcuit current tk 1 s Rated peak withstand current Ip 50 kA Rated short-circuit making current Ima 5 kA • with motordrive and release coil • signalling contact (6-pole) and terminal strip • for contact line feeders and transformer-train preheating Switch Wiring Motor-...
Open the catalog to page 41-pole indoor switch-disconnector H 22-1B; Un 27.5 kV Type H 22-1B Nominal voltage Rated current Rated insulation level Rated impulse voltage Short-duration power-frequency test level Rated frequency (A.C.) Rated breaking current Rated short-time withstand current Rated duration of short-curcuit current Rated peak withstand current Rated short-circuit making current Typetests • according to DIN EN 50152-2 03/1998 (VDE 0115 part 320-2) • with motordrive and release coil • with signalling contact (6-pole) and terminal strip • for contact line feeders and transformer-train preheating • Equipment...
Open the catalog to page 5DRIESCHER - Indoor switches for railway lines1-pole indoor disconnector L 31; Un 15 kV, In 630 A Type L 31/070194 Rated insulation level UNm 17.5 kV Rated impulse voltage UNi 125 kV Short-duration power-frequency test level Ua 50 kV Rated short-time withstand current Ik 20 kA Rated duration of short-curcuit current tk 1 s Rated peak withstand current Ip 50 kA • with motordrive Switch Wiring Motor- Motordrive Motordrive Weight Type Drawing-no. Part-no. plan-no. voltage mechanism Type approx. kg mounting side
Open the catalog to page 6DRIESCHER - Indoor switches for railway lines1-pole indoor disconnector L 31; Un 15 kV, In 1600 A Nominal voltage Rated current Rated insulation level Rated impulse voltage Short-duration power-frequency test level Rated frequency (A.C.) Rated short-time withstand current Rated duration of short-curcuit current Rated peak withstand current Typetests • according to DIN EN 50152-2 03/1998 (VDE 0115 part 320-2) • with motordrive • Equipment Switch Wiring Motor- Motordrive Motordrive Weight Type Drawing-no. Part-no. plan-no. voltage mechanism Type approx. kg mounting side
Open the catalog to page 7DRIESCHER - Indoor switches for railway lines1-pole indoor disconnector L 31; Un 27.5 kV, In 630 A / 1250 ATypetests 1-pole indoor-disconnector L 31 • according to DIN EN 50152-2 03/1998 • with motordrive Switch Wiring Motor- Motordrive Motordrive Weight Type Drawing-no. Part-no. plan-no. voltage mechanism Type approx. kg mounting side
Open the catalog to page 8• with motordrive Switch Wiring Motor- Motordrive Motordrive Weight Type Drawing-no. Part-no. plan-no. voltage mechanism Type approx. kg mounting side
Open the catalog to page 91-pole indoor disconnector with mounted earthingswitch • each with motordrive • each with 4-pole signalling contact • Equipment Switch Wiring Motor- Motordrive Motordrive Weight Type Drawing-no. Part-no. plan-no. voltage mechanism Type approx. kg mounting side
Open the catalog to page 10DRIESCHER - Indoor switches for railway lines1-pole indoor slide-disconnector L 31; Un 15 kV, 630 A Type L 31/059871 Rated insulation level UNm 17.5 kV Rated impulse voltage UNi 125 kV Short-duration power-frequency test level Ua 50 kV Rated short-time withstand current Ik 20 kA Rated duration of short-curcuit current tk 1 s Rated peak withstand current Ip 50 kA • with motordrive left or right Switch Wiring Motor- Motordrive Motordrive Weight Type Drawing-no. Part-no. plan-no. voltage mechanism Type approx. kg mounting side
Open the catalog to page 11DRIESCHER - Indoor switches for railway lines1-pole indoor slide-disconnector L 31; Un 15 kV, 1600 A Type Rated insulation level UNm 17.5 kV Rated impulse voltage UNi 125 kV Short-duration power-frequency test level Ua 50 kV Rated short-time withstand current Ik 31.5 kA Rated duration of short-curcuit current tk 1 s Rated peak withstand current Ip 80 kA • according to din en 50152-2 03/1998 • with motordrive left or right ' Equipment Switch Motordrive mechanism mounting side
Open the catalog to page 12DRIESCHER - Indoor switches for railway lines1-pole indoor earthing switch L 31; Un 15 kVType L 31/090323 Nominal voltage Un 15 kV Rated insulation level UNm 17.5 kV Rated impulse voltage UNi 125 kV Short-duration power-frequency test level Ua 50 kV Rated short-time withstand current Ik 31.5 kA Rated duration of short-curcuit current tk 1 s Rated peak withstand current Ip 80 kA Rated short-circuit making current Ima 80 kA 1-pole indoor earthing switch L 31/090323 • with motordrive • Equipment Switch Wiring Type Drawing-no. Part-no. plan-no. Motordrive mechanism mounting side right