 Disconnectors, Earthing switches, Fuse bases-2

The 1-, 2- and 3-pole Disconnectors ITr are appli-cable for a rated voltage range of 12 kV, 24 kV 36 kV, 38,5 kV and a rated current range from 630 A to 6300 A. The rated short time current upto 63 kAfor a duration of 3 s depending on the model has been tested. The 3-pole > Installation can be carried out at heights of up to 1000 m above sea level. At heights above 1000 m the rated insulating level of the switchgear must be corrected accordingly. The switches are designed for normal operating condtions according to IEC 62271-1.According to this the following limiting values applies:Ambient temperature:...

 Open the catalog to page 2
 Disconnectors, Earthing switches, Fuse bases-3

Type ES 12-20 Rated voltageRated frequency Rated short time current Rated duration of short-time circuit Rated peak withstand current Rated short-circuit making current Rated impulse withstand voltage - Phase to Earth Rated power frequency withstand voltage - Phase to Earth Drawing no. Mechanical life Weight approx. U > r 12 kV50 Hz20 kA3 s50 kA 50 kA75 kV 28 kVIT3-096806M119 kg f > r I > k t > k I > p I > ma U > p U > d Drawing for ES 12-20 / Drawing no. IT3-096806 Drawing for ES 12-31,5 / Drawing no. IT3-096809 3 >

 Open the catalog to page 3
 Disconnectors, Earthing switches, Fuse bases-4

ES 24-31,5 Type ES 24-20 24 kV50 Hz31,5 kA3 s80 kA 80 kA125 kV50 kVIT3-096810M127 kg Rated voltageRated frequency Rated short-time current Rated duration of short-time circuit Rated peak withstand current Rated short-circuit making current Rated impulse withstand voltage - Phase to Earth Rated power frequency withstand voltage - Phase to Earth Drawing no. Mechanical life Weight approx. U > r 24 kV50 Hz20 kA3 s50 kA 50 kA125 kV50 kVIT3-096807M124 kg f > r I > k t > k I > p I > ma U > p U > d Drawing for ES 24-20 / Drawing no. IT3-096807 Drawing for ES 24-31,5 / Drawing no. IT3-096810 4 >

 Open the catalog to page 4
 Disconnectors, Earthing switches, Fuse bases-5

ES 36-31,5 ES 36-20 38,5 kV50 Hz31,5 kA3 s80 kA50 kA*180 kV80 kVIT3-104999M146 kg Type ES 36-20 36 kV50 Hz31,5 kA3 s80 kA50 kA*170 kV70 kVIT3-096811M143 kg 38,5 kV50 Hz20 kA3 s50 kA 50 kA180 kV80 kVIT3-103626M143 kg Rated voltageRated frequency Rated short time current Rated duration of short-time current Rated peak withstand current Rated short-circuit making current Rated impulse withstand voltage - Phase to Earth Rated power frequency withstand voltage - Phase to Earth Drawing no. Mechanical life Weight approx. U > r 36 kV50 Hz20 kA3 s50 kA 50 kA170 kV70 kVIT3-096808M140 kg f > r I > k t >...

 Open the catalog to page 5
 Disconnectors, Earthing switches, Fuse bases-6

Type ITr 12-630-20 ITr 12-1600-40 ITr 12-2500-40 ITr 12-4000-50 ITr 12-6300-63 Rated voltageRated frequency Rated current Rated short time current Rated duration of short-time circuit Rated peak withstand current Rated impulse withstand voltage - Phase to Earth - Open Gap Rated power frequency withstand voltage - Phase to Earth - Open Gap Drawing no. Mechanical life Motor drive opt. Earthing switch (see page 3) Weight approx. U > r 12 kV50 Hz630 A20 kA3 s50 kA75 kV85 kV28 kV32 kVIT3-099824M2opt.ES 12-2020 kg 12 kV50 Hz1600 A40 kA3 s100 kA75 kV85 kV28 kV32 kVIT3-102832M2opt.ES 12-31,532 kg 12...

 Open the catalog to page 6
 Disconnectors, Earthing switches, Fuse bases-7

Drawing for ITr 12-1600-40 / Drawing no. IT3-102832 Drawing for ITr 12-2500-40 / Drawing no. IT3-100813 7 >

 Open the catalog to page 7
 Disconnectors, Earthing switches, Fuse bases-8

Drawing for ITr 12-4000-50 / Drawing no. IT3-103229 Drawing for ITr 12-6300-63 / Drawing no. IT3-096072 8 >

 Open the catalog to page 8
 Disconnectors, Earthing switches, Fuse bases-9

Type ITr 24-630-20 ITr 24-1600-31,5 ITr 24-2500-40 ITr 24-4000-50 ITr 24-6300-63 Rated voltageRated frequency Rated current Rated short time current Rated duration of short-time current Rated peak withstand current Rated impulse withstand voltage - Phase to Earth - Across the Open Gap Rated power frequency withstand voltage - Phase to Earth - Across the Open Gap Drawing no. Mechanical life Motor drive opt. Earthing switch (see site 4) Weight approx. U > r 24 kV50 Hz630 A20 kA3 s50 kA125 kV145 kV50 kV60 kVIT3-099825M2opt.ES 24-2031 kg 24 kV50 Hz1600 A31,5 kA3 s80 kA125 kV145 kV50 kV60 kVIT3-099847M2opt.ES...

 Open the catalog to page 9
 Disconnectors, Earthing switches, Fuse bases-10

Drawing for ITr 24-1600-31,5 / Drawing no. IT3-099847 Drawing for ITr 24-2500-40 / Drawing no. IT3-100812 10 >

 Open the catalog to page 10
 Disconnectors, Earthing switches, Fuse bases-11

Drawing for ITr 24-4000-50 / Drawing no. IT3-104607 Drawing for ITr 24-6300-63 / Drawing no. IT3-099510 11 >

 Open the catalog to page 11
 Disconnectors, Earthing switches, Fuse bases-12

Type ITr 36-630-20 ITr 36-1600-40 ITr 36-2500-50 Rated voltageRated frequency Rated current Rated short time current Rated duration of short-time current Rated peak withstand current Rated impulse withstand voltage - Phase to Earth - Across the Open Gap Rated power frequency withstand voltage - Phase to Earth - Across the Open Gap Drawing no. Mechanical life Motor drive opt. Earthing switch (see site 5) Weight approx. U > r 36 kV50 Hz630 A20 kA3 s50 kA170 kV195 kV70 kV80 kVIT3-099826M2opt.ES 36-2040 kg 36 kV50 Hz1600 A40 kA3 s100 kA170 kV195 kV70 kV80 kVIT3-102811M2opt.ES36-31,5*63 kg 36 kV50...

 Open the catalog to page 12
 Disconnectors, Earthing switches, Fuse bases-13

Drawing for ITr 36-1600-40 / Drawing no. IT3-102811 Drawing for ITr 36-2500-50 / Drawing no. IT3-101187 13 >

 Open the catalog to page 13
 Disconnectors, Earthing switches, Fuse bases-14

Type ITr 38,5-630-20 ITr 38,5-1600-40 Rated voltageRated frequency Rated current Rated short time current Rated duration of short-time current Rated peak withstand current Rated impulse withstand voltage - Phase to Earth - Across the Open Gap Rated power frequency withstand voltage - Phase to Earth - Across the Open Gap Drawing no. Mechanical life Motor drive opt. Earthing switch (see site 5) Weight approx. U > r 38,5 kV50 Hz630 A20 kA3 s50 kA180 kV210 kV80 kV90 kVIT3-099827M2opt.ES 38,5-2043 kg 38,5 kV50 Hz1600 A40 kA3 s100 kA180 kV210 kV80 kV90 kVIT3-104596M2opt.ES 38,5- 31,5*66 kg f > r I...

 Open the catalog to page 14
 Disconnectors, Earthing switches, Fuse bases-18

ITr 24-630-20-2 Type ITr 12-630-20-2 24 kV50 Hz630 A20 kA3 s50 kA125 kV145 kV50 kV60 kVIT3-104987M2opt. opt.45 kg Rated voltageRated frequency Rated current Rated short time current Rated duration of short-time current Rated peak withstand current Rated impulse withstand voltage - Phase to Earth - Across the Open Gap Rated power frequency withstand voltage - Phase to Earth - Across the Open Gap Drawing no. Mechanical life Motor drive Earthing switch Weight approx. (without Motor drive) U > r 12 kV50 Hz630 A20 kA3 s50 kA75 kV85 kV28 kV32 kVIT3-100427M2opt. opt.30 kg f > r I > r I > k t > k I >...