881e - 1

DRIESCHER Low-voltage distribution • series type 81, 84 und 86 • series type D 103 • according to EN 60439-1 6300A Moosburg • Eisleben ELEKTROTECHNISCHE WERKE FRITZ DRIESCHER & SÖHNE GMBH D-85366 MOOSBURG • TEL. +49 87 61 6 81-0 • FAX +49 87 61 68 11 37 http://www.driescher.com infoservice@driesch

Open the catalog to page 1
881e - 2

General description Type 81, open design for non-accesible compact substation Type 84, steel sheet encapsulated design, space-saving Type 86, steel sheet encapsulated design Type 86-3519 NZM-403, steel sheet encapsulated design Type 86-5019 NW-403, steel sheet encapsulated design Type D103 Auxiliary equipment with digital indicating instruments of type 81,84 and 86 Low-voltage switches, distribution systems type 202, 301 and 403 Accessories for low-voltage distributic Accessories '% Custom-made models, remarks number Check-list for planning - Agents in your country CERTIFICATE...

Open the catalog to page 2
881e - 3

• Typ D 103 open type for non-accessible compact substations • Typ 81, open type for non-accessible compact substations • Typ 84, sheet steel-enclosed type, space-saving • Typ 86, sheet steel-enclosed type for accessible substations The following standard design consisting of standard mounting systems is available: • closed version, type 84/86 • open-framework design, type 81 In accessible electrical operating areas low voltage systems in closed version (sheet steel-enclosed), type 84/86 ,are used (protection type: IP 2X). Distribution systems in framework design (type 81) are...

Open the catalog to page 3
881e - 4

• Type 81 (open design) for non-accessible compact sub-stations Measuring in input or output panels can be realized as well with analog and digital built-in measuring instruments The output panels are factory-designed in such a way that the outer outputs can be refitted (even later) with switches 630 A and this does not depend on the width of the panel. Instead of a 400 A / 630 A output two distributions systems of 160 A can also be mounted. On request back covers are also available. For a free standing version fixing angles can be mounted on option. Tecnical data: Rated voltage Ue Rated...

Open the catalog to page 4
881e - 5

DRIESCHER - Low-voltage distribution • Type 84 (steel sheet encapsulated design) space saving Tecnical data: Rated voltage Ue Rated insulation voltage Ui Rated current Ie Protection type Protection class Possible electrical fittings: • supply with compact circuit breaker NZM4 A, manufacturer: Moeller (from above) with analog I and U measuring • outgoings in downward direction, with Driescher distribution systems, type 403 (page 12)

Open the catalog to page 5
881e - 6

DRIESCHER - Low-voltage distribution • Type 86 sheet steel encapsulated design It is possible to have a combination of several input and output panels and retrofitting at any time. The instrumental covers of the supply and outgoing panels are hinged up in upward direction , the front covers in front of the cable compartment are pluggable. Measuring in input or output panels can be realized as well with analog and digital built-in measuring instruments. single-pole and 3-pole measuring of the outgoing circuit is possible. On request on top of the disconnector and the outgoing circuits...

Open the catalog to page 6
881e - 7

DRIESCHER - Low-voltage distribution • Type 86-3519 NZM-403 sheet steel encapsulated design Tecnical data: Rated voltage Ue Rated insulation voltage Ui Rated current Ie Protection type Class of protection Possible electric fittings: • supply with compact circuit breaker , type NZM, manufacturer: Moeller with analog current and voltage measuring (on request "multifunction unit") • outgoing circuits with fuse switch disconnector systems, Type 403, manufacturer: Driescher (see page 12) relais space in outgoing panel with inspection window and street lightning set

Open the catalog to page 7
881e - 8

DRIESCHER - Low-voltage distribution • Type 86-5019 NW-403 sheet steel encapsulated design Tecnical data: Rated voltage Ue Rated insulation voltage U| Rated current Ie Protection type Possible electical fittings: • input (from top) with open circuit breaker, type NW, manufacturer: Schneider with digital current indicator system and indicator of utilisation of power system "micrologic" panel doors in input panel lockable with profile cylinder. • outgoing circuits with fuse switch disconnector systems Type 403, manufactured by Driescher (see page 12)

Open the catalog to page 8
881e - 9

• Type D 103 open design The low voltage system D 103 was designed within the M100 series as model especially for the application in accessible and non-accessible substations. The basic conception of the system is a modular design consisting of a self-supporting basic plate made of sheet steel. For the choice of material the latest state-of-the-art on leakage current according to Generic Standards (EN 50081) has been taken into consideration. For this the completely closed sheet steel rear panel offers best possibilities. Furthermore, due to the best possible design of a moulded holding...

Open the catalog to page 9
881e - 10

Digital multi purpose instrument, type EMM-5 • clear structure • easy to handle • lighted LCD-Display • RS 485 interface Modbus (option) • query by modem • measuring values: U, I, Ithmax, f, cos (phi), P, Pthmax, S, Q • Counter: WP ^ WQ imp, WP exp, WQ exp • 2 impulse outgoings for counter • evaluating software Selectable measuring values: • voltage display, conductor-conductor and conductor-earth (+/- 1%) • frequency display (+/- 0,1 Hz) • current display L1 / L2 / L3 (+/- 1 %) • thermic electricity load (lth) • effective power (P) and maximal power Pmax) • apparent power (S) and idle...

Open the catalog to page 10
881e - 11

low-voltage distribution system 403 • protection against contact according VBG 4 Technical data • single-pole and 3-pole switchable, according to DIN VDE 0660 Rated current 400 A Standard frequency ratings 45 - 65 Hz Impulse strength (Uimp) 8,0 kV 50 on/off switching operations with 500 V / cos phi 0,7 400 A 50 on/off switching operations with 500 V / cos phi 0,2 400 A Short circuit making operation with l.v.h.b.c. fuses Admissible ambient temperature Protection type Leaking current —Zp- Brochure 843 Mechanical operating cycles Electrical operating cycles For more detailed...