DRIESCHER -Low voltage fused-switch-disconnector system 403 • Rated current 400 A upto 1445 A
Open the catalog to page 1protected against accidental contact according to BGV A2, 1-pole and 3-pole switchable Index Technical data General Fused-switch disconnector system 403, 400 A and 630 A, 1 - and 3 pole switchable Fused-switch disconnector system 403, 400 A and 630 A, with conn. routed up or below Connection types for fused-switch disconnector system 403, 400 A, 630 A and 909 A Feeder circuits for transformers up to 1000 kVA (1445 A) Feeder and coupling circuits 400 A and 630 A Feeder and coupling circuits 1000 A Accessories Earthing and shorting arrangement Mounting of busbars with width more than 40 mm Technical...
Open the catalog to page 2protected against accidental contact according to BGV A2, 1-pole and 3-pole switchable The requirement of protection against accidental 50 ON-OFF operations each were carried out at contact as well as switching under load was taken 550 V/320 V AC and cos 9 = 0,7 by 500 A, 750 A and into consideration when developing this system. 1000 A successfully. By all switching operations the That means: maximum possible operational and arc was successfully extinguished . functional saftey! The distribution system is made of high quality plastic press parts and guarantees an ideal circulation of...
Open the catalog to page 3protected against accidental contact according to BGV A2, 1-pole and 3-pole switchable 1) possible connection types, see page 6 2) Cable-covering bonnet, see page 10, on ordering Part-no. Rated Current For lv-fuses Operation b in mm f in mm g in mm s in mm Weig. in kg 4) Use of lv-fuses size 1 in 400 A system and size 2 in 630 A system, possible without changing the connecting element.
Open the catalog to page 4protected against accidental contact according to BGV A2, 1-pole and 3-pole switchable 1) 2) Cable-covering bonnet, see page 10, on order Part-no. Rated current for lv-fuses Operation Use of lv-Fuses size 1 in 400 A and size 2 in 630 Asystem, is possible without changing the connecting element.
Open the catalog to page 5protected against accidental contact according to BGV A2, 1-pole and 3-pole switchable Version with built in current transformers up to max. 630 A (Connection screws M12 x 55) Version with built in current transformers up to max. 1250 A (Connection screws M12 x 55) ® Transformer bus for system 403 up to max. 630 A (Connection type acc. to Pos. 1 to 4 @ Transformer bus for system 403 up to max. 1250 A (Connection screws M12 x 55) 1) for example 843 22 113 means distribution system 403 / 400 A, 1-pole switchable
Open the catalog to page 6protected against accidental contact according to BGV A2, 1-pole and 3-pole switchable 630 kVA (909 A) connection above 1) Cable-covering bonnet, see page 10, on ordering 1000 kVA (1445 A) connection below Transformer-rating Part-no. lv-fuses Connection Operation Drawing-Nr. Weight in kg
Open the catalog to page 7protected against accidental contact according to BGV A2, 1-pole and 3-pole switchable Examples for arrangement from incomer and outgoing circuit as well as from coupling and outgoing circuit The dimensions k, l and m are dependent on the different system sizes. 1) Cover (page 10) and 3 cap nut made of plastic only on ordering. Screw extension from metal nut 8 mm to 15 mm. Connecting bracket (drawing-no. NN4-40947) coupler circuit and busbars only on ordering. Rated current Incomer or coupler Part-no. Part-no. Rated current k Connection on theleft Connection on the right outgoing circuit...
Open the catalog to page 8843 DRIESCHER - Low voltage fused-switch disconnector system 403 protected against accidental contact according to BGV A2, 1-pole and 3-pole switchable Feeder and coupler 1000 A consisting of two parallel connected distribution system 403, 630 A System 403, 630 A, parallel connected 1) Current transformer is not included in the delivery System 403, 630 A, parallel connected Coupling circuit 1000 A according to drawing NN3-71307 Outgoing section 2) Cover (page 10) and 3 cap nuts made of plastic only on ordering. Screw extension from metal nut 8 mm to 15 mm. 2) Connecting bracket (drawing-no. NN4-40947),...
Open the catalog to page 9protected against accidental contact according to BGV A2, 1-pole and 3-pole switchable Accessories Busbar-covering plate for the distribution system 301 and 403 Made of GFK • 2,5 mm, grey colour with cap nuts made of plastic ■ for system 301/160 A Part-no. 840 30005 for system 403/400 A Part-no. 840 30001 for system 403/630 A Part-no. 840 30002 ■ for coupling circuit Part-no. 840 30003 Work and covering bonnet for distribution system type 403 acc. to BGVA2 • acc. to drawing NN4-39041 and NN4-41231 Pic. Application ■0 Covering bonnet for system with normal conn. © Covering bonnet for system with...
Open the catalog to page 10843 DRIESCHER - Low voltage fused-switch disconnector system 403 protected against accidental contact according to BGV A2, 1-pole and 3-pole switchable Earthing and shorting arrangements Earthing slider (without earthing set), for conventional earthing accessories with 35 mm2 and 50 mm2 • for rated current 400 A Part-no. 840 31031 Drawing-no. NN4-71309 • for rated current 630 A Part-no. 840 31032 Drawing-no. NN4-71309 Earthing accessories Part-no. 773 11535 Part-no. 773 11550 Earthing accessory ∅ Cu 35 mm2 Earthing accessory ∅ Cu 50 mm2 Universal earthing case with earthing accessory ∅ Cu 35...
Open the catalog to page 11protected against accidental contact according to BGV A2, 1-pole and 3-pole switchable Version 1a and 1b (Picture left) The busbars (> 40 mm) are connected to fused switch disconnector system 403 with distance pieces. Part-no. Rated Current Operation Connection Drawing-no. 843 62143 400 A 3-pole M12 x 35 NN4-22049 Copper-brackets can also be used instead of distance pieces (see Pic. 1b). Version 2 (Picture right) The busbar (> 40 mm) is connected to the fused switch dis-conector system 403 with distance pieces. Due to the extended distance pieces current transformers can be mounted for three...