1. Catalogs
  2. FRICO
  3. Corinte ACCS E/W

Corinte ACCS E/W

Corinte ACCS E/W
1 / 14 PagesView full catalog

Corinte ACCS E/W

Product catalog summary

Product Overview

The Corinte air curtain is engineered for premium entrances requiring elegant design and low noise. Available in two models (ADCS and ACCS), it supports both horizontal and vertical mounting. Constructed from stainless steel with polished, mirror-polished, or brushed finishes, it features black intake and outlet grilles (RAL 9005). The unit incorporates Thermozone technology for optimized airflow and is controlled via the SIRe system, which offers Basic, Competent, and Advanced control levels.

Specifications

  • Mounting: Horizontal (recommended height 3 m) and Vertical (recommended width 5 m with two units flanking the opening).
  • Dimensions: Lengths vary by model and orientation (e.g., ACCS horizontal: 1–3 m; vertical: 2–3 m).
  • Heating Options: Ambient (no heat), Electrical (ADCS: 15–22.5 kW; ACCS: 8–23 kW), Water heating with high (WH) or low temperature (WL) coils.
  • Airflow & Velocity: Velocity ranges from ~3.0 m/s to 11.0 m/s depending on model and mounting.
  • Compliance: CE certified, IP20 protection class.

Technical Data

Detailed specs include output power, airflow rates, temperature rise, sound levels, voltage, amperage, and weight per model. For example, the ACCS25E20 electrical heating model delivers 6.6–19.8 kW output, airflow between 2340–4500 m³/h, and noise levels of 48–65 dB(A). Water heating models specify supply/return temperatures, flow rates, pressure drops, and outlet air temperatures for both high and low temperature coils.

Installation and Mounting

  • Horizontal: Mounted near doors with air grille facing down; connections on left or right. Electrically heated units require minimum 1800 mm outlet-to-floor clearance. Installation options include wall, ceiling, or hanging with supplied brackets.
  • Vertical: Installed vertically near doors, typically two units for symmetry. Connections can be top or bottom. Units rest on adjustable feet and must be secured at the top.

Connections and Controls

Integrated SIRe PC board manages control with modular connectors for external devices. Electrical connections differ by mounting and heating type, with separate power/control supplies for electrical heating. Water connections use DN20 (horizontal) or DN25 (vertical) inside thread fittings. Valve kits manage water flow and are compatible with SIRe control levels.

Valve Kits and Water Control

  • VOS: On/off two-way valves with shut-off.
  • VOSP: Pressure-independent on/off valves ensuring constant flow.
  • VMO: Modulating valves with stepless actuator control.
  • VMOP: Pressure-independent modulating valves combining constant flow and modulation.
  • VOT & VMT: Three-way valves with on/off or modulating actuators.

Valve kits come in DN15, DN20, DN25 sizes with specified Kv values and max flow rates at 10 kPa pressure drop.

Accessories

  • ACCW: Wall brackets for horizontal mounting in various stainless steel finishes.
  • ACCSEH: Extension hood for vertical mounting to fill ceiling gaps (height adjustable 100–1000 mm).
  • AXP300: Floor collision protection to prevent damage.
  • FH1025: Flexible hose (DN25, 1" inside thread) for pipe connections.

Performance and Output Charts

Water-heated ACCS WH models include charts detailing airflow, heat output, return water temperature, water flow, pressure drop, and outlet air temperature at supply water temps of 110 °C and 90 °C with room temp at +18 °C. These assist in selecting appropriate models and settings.

Summary of Critical Information

  • Designed for high-end entrances prioritizing design, low noise, and energy efficiency.
  • Flexible mounting and sizing options for tailored installations.
  • Multiple heating options with detailed performance data.
  • Integrated SIRe control system with scalable functionality and compatible valve kits.
  • Accessories enhance installation flexibility and protection.
  • Comprehensive technical data and charts support system design and optimization.

Detailed Performance Specifications

Extensive tabulated data covers airflow (950–5100 m³/h), heating output (5.4–29.4 kW), water temperatures (various supply/return scenarios from 55/35 °C up to 110/80 °C), water flow rates (0.03–0.62 l/s), pressure drops (0.03–1.31 kPa), and recommended outlet air temperature (+35 °C) for comfort and efficiency. Data is provided for both vertical and horizontal mounting with fan positions indicating max/min airflow.

Operating Conditions and Recommendations

Standard room temperature is +18 °C. The recommended outlet air temperature is +35 °C to ensure comfort and optimal heating output. Nominal outputs correspond to specific supply/return water temperatures to aid system design.

Wiring Diagrams and Electrical Details

  • Includes wiring for electrical and water heating units.
  • Details actuator and motor protection on 230V supply.
  • Transformer connections with multiple voltage taps (230V down to 100V).
  • Integration of internal and room sensors.
  • Color-coded wiring for clarity.
  • Separate diagrams for each model variant (ACCS10 to ACCS30, electrical and water heating).

Notes and References

  • Maintaining recommended outlet air temperature is critical for comfort and efficiency.
  • Nominal outputs are tied to specific water temperature conditions.
  • Additional detailed data and calculations are available on the manufacturer’s website (www.frico.se).
  • Some operating points may yield outlet air temperatures below 35 °C, noted in data tables.

Summary Table of Key Parameters

ModelMax Airflow (m³/h)Max Output (kW)Water Temp. (Supply/Return °C)Water Flow (l/s)Pressure Drop (kPa)Recommended Outlet Air Temp. (°C)
ACCS10WH190010.980/600.135.435
ACCS20WH380021.7 - 29.455-110 (varies)0.07 - 0.241.5 - 12.935
ACCS25WH450025.8 - 26.055-110 (varies)0.09 - 0.272.2 - 7.135
ACCS30WH510029.2 - 29.455-110 (varies)0.08 - 0.521.2 - 6.935

Conclusion

This document serves as a comprehensive technical reference for engineers and HVAC professionals specifying Corinte ACCS air curtains. It provides detailed performance data across multiple models, mounting options, and heating configurations, alongside wiring diagrams for installation and maintenance. Adhering to recommended outlet air and water temperatures is essential for achieving optimal comfort and system efficiency.

See more

Catalog excerpts

Corinte ACCS E/W-1

Corinte Design air curtain for exclusive entrances, with intelligent control • Horizontal mounting - Recommended installation height 3 m* - Lengths ADCS: 1,7 and 2,2 m - Lengths ACCS: 1, 1,5, 2, 2,5 and 3 m • Vertical mounting - Recommended installation width 5 m* (2 units), one on each side - Lengths ADCS: 2,2 and 2,5 m - Lengths ACCS: 2, 2,5 and 3 m 1 Ambient, no heat 3 Electrical heat ADCS: 15–22,5 kW 3 Electrical heat ACCS: 9–23 kW 2 Water heat WH, WL Application Corinte is intended for exclusive shop entrances and other environments with high demands in respect of design and soundlevel. Mounted with one unit on either side of the opening, thus creating a classic symmetry, the curtain effect and comfort is optimized. The air curtain has many intelligent and energy saving features which provide fully automatic protection for the entrance, adaptable to each area of use. Design Corinte is a stylish and exclusive, stainless steel air curtain for horizontal or vertical installation. Corinte is available in two models; ADCS and ACCS that have varying dimensions and performance. The product key offers many options for the design and finish of both models. Optimized airflow with Thermozone technology. Product specifications • Prepared for the SIRe control system whose preprogrammed default settings and many features make it easy to install and use the air curtain. Read more about the SIRe controls package in the "Controls" section. • Customised production based on the product key. • Available for horizontal or vertical mounting. • For vertical mounting, electricity and/or water may be connected from above or below. • Available in polished, mirror-polished or brushed stainless steel. Colour intake and outlet grille: black, RAL 9005. Measurements according to ISO 27327-1. Average values for products in the series. 2013-05-11 *) Recommended installation height and width varies depending on the relevant premises.

 Open the catalog to page 1
Corinte ACCS E/W-2

Corinte ACCS • Horizontal mounting - Recommended installation height 3 m* - Lengths: 1, 1,5, 2, 2,5 and 3 m • Vertical mounting - Recommended installation width 5 m* (2 units), one on each side - Lengths: 2, 2,5 and 3 m 3 Electrical heat: 8–23 kW 2 Water heat WH, WL Corinte is available in two versions; ADCS and ACCS. Read more about ADCS in the beginning of this section. *) Recommended installation height and width varies depending on the relevant premises.

 Open the catalog to page 2
Corinte ACCS E/W-3

Corinte ACCS Technical specifications Airflow*2 At*4 Sound Voltage Amperage Voltage [V] Length Weight level*3 motor motor Amperage [A] 6 Water heat - ACCS WH, coil for high temperature water (>80 °C) Output*5 Airflow*2 At*4-5 Water volume Sound Voltage Amperage Length Weight 6 Water heat - ACCS WL, coil for low water temperature (<80 °C) Type Output*6 Airflow*2 At*4-6 Water volume Sound Voltage Amperage Length Weight *1) Available only for horizontal mounting. *2) Lowest/highest airflow of totally 5 fan steps. *3) Conditions: Distance to the unit 5 metres. Directional factor: 2. Equivalent absorption...

 Open the catalog to page 3
Corinte ACCS E/W-4

Corinte ACCS Vertical mounting Bottom part of the unit seen from above. Connection dimensions, inside thread: 1", DN25

 Open the catalog to page 4
Corinte ACCS E/W-5

Corinte ACCS Dimensions Horizontal mounting Connection dimensions, inside thread: 3/4", DN20 Mounting The air curtain range includes variants for horizontal and vertical installation. Horizontal mounting The air curtain is installed horizontally with the supply air grille facing downwards as close to the door as possible. It must be specified when ordering whether the connections are to be on the left or right hand side (seen from inside the premises). The air curtain may be mounted on the wall or on the ceiling with the enclosed brackets (accessory). The air curtain can also be mounted hanging...

 Open the catalog to page 5
Corinte ACCS E/W-6

Corinte ACCS Connection The PC board SIRe is built into the air curtain on delivery and is equipped with modular connectors for easy connection of external components. Read more about the SIRe control system in the "Controls" section. Unit with electrical heating The electrical connection may be done from above or below when mounted vertically, and from left or right when mounted horizontally, according to ordering key. Control (230V~) and power supply for heat (400V3~) should be connected to a terminal block. For units with electrical heating, power and control should be supplied separately....

 Open the catalog to page 6
Corinte ACCS E/W-7

Corinte ACCS Accessories ACCW, wall bracket Brackets for installing unit horizontally on a wall. Two are required for 1 and 1.5 metre units, while 2 and 2.5 metre units need three and 3 metre units need four. Available in three designs: - ACCWBB, brushed stainless steel - ACCWBP, polished stainless steel - ACCWBMP, mirror polished stainless steel ACCSEH, extension hood Fills the space between the unit and the ceiling for vertical mounting and provides a neater installation. Special order to required dimension. Height 100-1000 mm. AXP300, collision protection Floor placed protection against impact...

 Open the catalog to page 7
Corinte ACCS E/W-8

Corinte ACCS Controls Advanced Competent This air curtain is supplied with an intregrated PC board SIRe. There are three different levels with different functionality to choose from, Basic, Competent or Advanced. Read more about the SIRe control system in the "Controls" section. Control system SIRe Basic Control system SIRe Competent Control system SIRe Advanced Water control Used with SIRe Basic and Competent. VOS Used with SIRe Advanced. VOT Valve kit VOS(P), VOT, VMO(P) or VMT is used to control the water flow. For more information see the "Controls" section. Valve kit on/off, low flow, DN15...

 Open the catalog to page 8
Corinte ACCS E/W-9

Water control Choose valve kit Water heated units that are controlled by SIRe are supplemented with valve kits. It’s easy to choose the right valve kit. Look at the guide for the level of SIRe chosen - Basic, Competent or Advanced and select the valve kit which suits the system requirements and characteristics. SIRe Basic, SIRe Competent VOS, valve kit on/off • Complete kit with two way control and adjustment valve, on/off-actuator, shut-off valve and bypass. VOS15LF • Kvs 0,90 • Max flow at 10 kPa: 0,079 l/s • DN15 VOS15NF • Kvs 1,8 • Max flow at 10 kPa: 0,158 l/s • DN15 VOS20 • Kvs 3,4 • Max...

 Open the catalog to page 9

All FRICO catalogs and technical brochures