1. Catalogs
  2. FRER
  3. MID Energy meter
video corpo

MID Energy meter

MID Energy meter

MID Energy meter

Product catalog summary
Technical Specifications
The document provides detailed technical specifications for energy meters. Key features include a backlighted LCD display, accuracy class B for kWh and class 2 for kVArh, and various test device resolutions depending on the current (6A, 40A, 80A). The meters can handle short-term overcurrent up to 20 times the maximum current for 0.5 seconds and operate within a voltage range of ±20% of the nominal voltage at frequencies of 50/60Hz. They are self-supplied with a voltage circuit consumption of less than 7.5VA and can operate in temperatures ranging from -20°C to +55°C, with storage temperatures from -25°C to +75°C. The humidity tolerance is up to 80% without condensation. The meters are made from self-extinguishing thermoplastic material with protection ratings of IP50 for housing and IP20 for terminals. They comply with standards EN50470-1, EN50470-3, EN62053-23, and EN62053-31.
Tariff and Pulse Outputs
The meters feature an active optoisolated tariff switching input with a voltage range of 80 to 276 Vac/dc, excluding Ethernet models. Pulse outputs are passive optoisolated, with maximum values of 27 Vdc at 27mA and 250 Vac/dc at 100mA for IR models. Pulse values vary by model, with durations of 50 ±2ms for both ON and OFF times.
Ordering Codes and Communication
The document lists various models with different communication capabilities, including RS485 Modbus RTU, Ethernet, and M-Bus, each with specific configurations for single-phase and three-phase systems. Communication modules are detailed on page 9.18.
Dimensions and Wiring Diagrams
Additional technical data includes dimensions and wiring diagrams for different models, highlighting the configurations for three-phase systems with either 3 or 4 wires.
Measurement and Recorded Data
The meters measure instantaneous values such as phase voltage, line current, power factor, apparent power, active power, reactive power, frequency, phase sequence, and power direction. Recorded data includes total active, reactive, and apparent energy, tariff energy counters, resettable partial energy counters, and energy balance.
Other Information
Additional features include monitoring of present tariff, voltage, current, and frequency limits, partial counters, active communication, active S0 pulse, and error conditions. Communication interfaces include RS485, Ethernet, and M-Bus, each with specific standards, protocols, and speed ranges.
See more

Catalog excerpts

MID Energy meter-1

CONTATORI DI ENERGIA MID MID Energy meter DATI TECNICI - Technical data visualizzazione classe di precisione dispositivi di prova (risoluzione) sovracorrente di breve durata tensione di funzionamento frequenza di riferimento alimentazione consumo circuiti di tensione temperatura di funzionamento temperatura di magazzinaggio umidità relativa prova tensione d’impulso prova tensione AC custodia in materiale termoplastico autoestinguente grado di protezione custodia grado di protezione morsetti conforme a Tab.1 Rapporoto TA - CT ratio value 1÷4 5÷24 25÷124 125÷624 625÷3124 3125÷10000 Ingresso cambio tariffa tensione min÷max Impulsi S0 - S0 pulses 1000 /kWh - kVArh - kVAh 200 /kWh - kVArh - kVAh 40 /kWh - kVArh - kVAh 8 /kWh - kVArh - kVAh 1 /kWh - kVArh - kVAh 0,1 /kWh - kVArh - kVAh Uscite impulsive nr./valori massimi peso impulso durata impulso display accuracy class test devices (resolution) LCD retroilluminato / backlighted LCD B (kwh), 2 (kVArh) LED 10000 imp/kWh (6A) LED 5000 imp/kWh (40A) LED 1000 imp/kWh (80A) short-term overcurrent 20 x Imax (0,5 sec.) operating voltage ±20%Un reference frequency 50/60Hz aux. supply voltage autoalimentato / self-supplied voltage circuits consumption < 7,5VA operating temperature -20…+55°C storage temperature -25…+75°C humidity (without condensation) max. 80% pulse voltage test 1,2kV/50μs, 6kV AC voltage test 4kV self estinguishing thermoplastic material UL 94-V0 protection for housing IP50 protection for terminals IP20 according to EN50470-1, EN 50470-3 EN62053-23, EN62053-31 Tariff switching input Optoisolato attivo/Active optoisolated min÷max voltage 80÷276 Vac/dc (non per/not for ETHERNET models) Pulse output Optoisolate passive/Passive optoisolated nr./maximum values 1x 27 Vdc - 27mA 2x 250 Vac/dc - 100mA (only IR models) pulse value C18QSL040 1000/Kwh C35QSL080 500/Kwh - kVArh - kVAh C70Q...L080 100/Kwh - kVArh - kVAh C70Q...L vedi/see Tab.1 pulse duration 50 ±2ms ON time - 50 ±2ms OFF time CODICI DI ORDINAZIONE - Ordering codes CONTATORI DI ENERGIA MID - MID ENERGY METERS Comunicazione - Communication: Sistema - System: Ingressi - Input: Nessuna - None Monofase - Single-phase Monofase - Single-phase Trifase , 4 fili, carico squilibrato - Three-phase, 4 wires unbalanced load Trifase , 4 fili, carico squilibrato - Three-phase, 4 wires unbalanced load Trifase , 4 fili, carico squilibrato - Three-phase, 4 wires unbalanced load Trifase , 4 fili, carico squilibrato - Three-phase, 4 wires unbalanced load Monofase - Single-phase Trifase , 4 fili, carico squilibrato - Three-phase, 4 wires unbalanced load Trifase , 4 fili, carico squilibrato - Three-phase, 4 wires unbalanced load Monofase - Single-phase Trifase , 3 o 4 fili, carico squilibrato - Three-phase, 3 or 4 wires unbalanced load Trifase , 3 o 4 fili, carico squilibrato - Three-phase, 3 or 4 wires unbalanced load Ethernet (integrata-built-in) Porta ottica * - Optical port *: * Moduli di comunicazione vedi pag. 9.18 - * Communication modules see pag. 9.18

 Open the catalog to page 1
MID Energy meter-2

MID DATI TECNICI AGGIUNTIVI - Additional technical data ModBus RTU interfaccia velocità (bps) unit load protocollo indirizzamento interface speed (bps) unit load protocol addressing range ETHERNET normativa interfaccia protocolli velocità (bps) M-Bus normativa interfaccia velocità (bps) unit load protocollo indirizzamento standard interface protocols speed (bps) standard interface speed (bps) unit load protocol addressing range MISURE - Measurement integrata - built-in RS485 isolata/insulated 300...57600 1/8 RTU = 8N1 - ASCII =7E2 01…F7 Hex integrata - built-in IEEE 802.3 ETHERNET isolata/insulated...

 Open the catalog to page 2

Archived catalogs

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.