Current & voltage transformers, shunts & voltage dividers

Current & voltage transformers, shunts & voltage dividers
1 / 134 PagesView full catalog

Current & voltage transformers, shunts & voltage dividers

Product catalog summary
General Information
Current and voltage transformers are designed for use with measuring instruments or plant protection devices, operating at a standard voltage of 0.72kV and a frequency between 50 and 60Hz. Current transformers (CTs) have primary currents ranging from 1A to 8000A, with secondary currents of 1A or 5A. Voltage transformers (VTs) have primary voltages between 100:√3V and 1200V, with secondary voltages of 100V or 100:√3V. These transformers are intended for indoor installations, manufactured in thermal class E, and can be mounted in various positions.
Measuring and High Accuracy Transformers
Measuring transformers are available in classes 0.5, 1, and 3, while high accuracy transformers are available in classes 0.2, 0.5S, and 0.2S. They maintain precision even when the primary current is reduced by winding the primary cable through the CT window.
Protection Transformers
Protection transformers are available in classes 5P5, 5P10, 5P15, 5P20, 3P, 6P, and PX, designed to handle overvoltages and overheating. The primary current can be adjusted using a primary cable of appropriate dimensions.
UL Certified and Customizable Transformers
UL certified transformers are available, as well as customizable options to meet specific performance requirements while maintaining precision.
Certification for Fiscal Use
FRER transformers can be certified for fiscal use, with sealable terminal covers and certification managed by FRER with a third-party authority recognized by UTF.
Installation and Connection
Transformers can be fixed on DIN rails or directly on busbars using screws. Secondary connections are available for models with integrated terminals, and protective caps for fixing screws are available on request.
Error Limits
Error limits are specified for different classes of transformers, detailing ratio and phase errors to ensure precision and performance standards.
Technical Specifications
CTs are available with secondary currents of 1A and 5A, housed in self-extinguishing thermoplastic material compliant with UL94-V0 standards. They operate at a frequency of 50-60 Hz, with an insulation reference voltage of 0.72 kV and a test voltage of 3 kV for 1 minute at 50 Hz. The protection degree is IP 00, which can be increased to IP 20 with terminal covers. CTs have a continuous overcurrent capacity of 1.2 times the nominal current (In), a rated short-time thermal current (Ith) of 40 In, and a rated dynamic current (Idyn) of 2.5 times Ith. The safety factor is N ≤ 5, with an operating temperature range of -25°C to +50°C and a storage range of -40°C to +80°C.
Product Types and Codes
Various busbar passing measuring CTs with different dimensions and ratios are available, such as TAT125, TAT126, TAT127, TAT128, TAT129, and TAT165 series. Each type has specific codes for different current ratios, e.g., 400/5A, 500/5A, up to 8000/5A, with codes provided for both Class 0.5 and Class 1 accuracy levels.
Accessories and Options
Supplied accessories include built-in busbar fixing systems and clamping terminals. Optional accessories include protective caps for CT fixing and sealable terminal covers. CTs with 1A secondary current are available with the same performance as 5A CTs, with ordering codes adjusted accordingly.
Additional Notes
The document provides examples of ordering codes and highlights the availability of CTs with secondary terminals on the front side upon request. It also mentions compliance with UKRMETR standards in Kazakhstan.
See more

Catalog excerpts

Current & voltage transformers, shunts & voltage dividers-1

TRASFORMATORI DI CORRENTE E TENSIONE, SHUNT E DIVISORI Current & voltage transformers, shunts & voltage dividers

 Open the catalog to page 1
Current & voltage transformers, shunts & voltage dividers-2

INDICE Index INFORMAZIONI GENERALI General informations T.A. DI MISURA Measuring CTs T.A. DI PRECISIONE High accuracy CTs T.A. COMPLETAMENTE PERSONALIZZABILI Fully customizable CTs T.A. SOMMATORI e T.A. DI CORREZIONE RAPPORTO Summing CTs and CT ratio correcting transformers T.A. SATURABILI PER RELE’ TERMICI Saturable CTs for thermal relays T.A. PER ELETTRONICA CTs for electronic applications T.V. DI PRECISIONE High accuracy VTs SOVRAPPREZZI PER ESECUZIONI SPECIALI Special executions extraprices DERIVATORI PER CORRENTE CONTINUA Shunts DIVISORI DI TENSIONE Voltage dividers

 Open the catalog to page 2
Current & voltage transformers, shunts & voltage dividers-3

INFORMAZIONI GENERALI General informations I trasformatori di corrente e tensione sono adatti all’utilizzo con strumenti di misura o dispositivi di protezione degli impianti. Hanno una tensione operativa standard di 0,72kV ed una frequenza di lavoro compresa tra 50 e 60Hz. Le correnti primarie dei TA sono comprese tra 1A e 8.000A ed i secondari standard sono1A o 5A. Le tensioni primarie dei TV sono comprese tra 100:√3V e 1200V ed i secondari standard 100V o 100:√3V (altri valori a richiesta). I trasformatori di corrente e tensione sono progettati per installazioni all’interno di edifici e sono...

 Open the catalog to page 3
Current & voltage transformers, shunts & voltage dividers-4

Modifies rapporto TA - CTratio modification Effettuando alcune spire attraverso il passaggio barra del TA si ottiene una riduzione della eorrente primaria mantenendo invariate: eorrente seeondaria, prestazioni e precisione. In questo modo si ottiene una corrente primaria ridotta, pari al rapporto tra la corrente primaria nominale e il numero di spire all' interno del passaggio barra. Corrente primaria ridotta = corrente primaria nominale : numero spire. To obtain a reduction of the primary current keeping the same secondary current, performance and precision, it is necessary to make some windings...

 Open the catalog to page 4
Current & voltage transformers, shunts & voltage dividers-5

* con accessorio with accessory Fissaggio su barra DIN EN 50022. Non è necessario l’utilizzo di attrezzi e deve essere effettuato, come evidenziato dalle frecce, inserendo prima il lato con l’aggancio elastico e poi ruotando il trasformatore fino a bloccaggio avvenuto. Procedere inversamente per lo smontaggio. Fixing on DIN bar EN50022. It is not necessary to use tools. It has to be carried out, as shown by the drawn arrows, firstly insert the side with the elastic coupling and then turn the CT until it locks. Proceed inversely for disassembly. Collegamento secondario per i modelli con terminali...

 Open the catalog to page 5
Current & voltage transformers, shunts & voltage dividers-6

FISSAGGIO COPRIMORSETTI - Terminals cover fixing SIGILLATURA COPRIMORSETTI - Terminals cover sealing Fissaggio del coprimorsetti a scatto, che si blocca sul trasformatore con una leggera pressione, e non necessita di viti di fissaggio. The snap-on terminals cover is fixed on the CT with a light pressure and does not require fixing screws. Sigillatura del coprimorsetti per la certificabilità ad uso fiscale del trasformatore. Per tutti i modelli indicati non sono necessarie viti a testa forata. Sealing of terminal covers Fissaggio del coprimorsetti a scatto, che si blocca sul trasformatore con...

 Open the catalog to page 6
Current & voltage transformers, shunts & voltage dividers-7

LIMIT! DI ERRORE PER I TRASFORMATORI DI CORRENTE DI MISURA - Error limits for measuring current transformers Tabella di consumo dei 2 cavi tra TA e strumento - Cables burdens between meter and CTs

 Open the catalog to page 7
Current & voltage transformers, shunts & voltage dividers-8

LIMIT! DI ERRORE PER I TRASFORMATORI DI TENSIONE DI MISURA - Error limits for measuring voltage transformers

 Open the catalog to page 8
Current & voltage transformers, shunts & voltage dividers-9

TABELLA RIASSUNTIVA T.A. DI MISURA Measuring CTs selection table Pagina - Page TA DI MISURA Measuring CTs Codice - Code cavo - cable barra - busbar larghezza - width Cl. TAC017 Ø 17 mm primario avvolto - primary wound 15 x 5 mm 56 mm 70 mm 85 mm 85 mm 56 mm PRESTAZIONI VA - BURDENS VA Pagina - Page TA DI MISURA Measuring CTs Codice - Code cavo - cable barra - busbar larghezza - width Cl.

 Open the catalog to page 9
Current & voltage transformers, shunts & voltage dividers-10

Pagina - Page Codice - Code cavo - cable barra - busbar larghezza - width Pagina - Page Id Id TA DI MISURA Measuring CTs Codice - Code cavo - cable barra - busbar

 Open the catalog to page 10
Current & voltage transformers, shunts & voltage dividers-11

TAA... DATI TECNICI - Technical data Sistema di chiusura a scatto! Snap closing system! custodia in materiale termoplastico autoestinguente frequenza funzionamento tensione di riferimento per l'isolamento tensione di prova isolamento grado di protezione sovracorrente permanente corrente termica di breve durata nominale (I th) corrente dinamica nominale (I dyn) fattore di sicurezza temperatura di funzionamento temperatura di magazzinaggio costruzione a norme terminali secondari integrati coprimorsetti sigillabili selfestinguishing thermoplastic material UL94-V0 insulation reference voltage 0,72...

 Open the catalog to page 11
Current & voltage transformers, shunts & voltage dividers-12

lUKRMETRTEST ' STANDARD DATI TECNICI - Technical data custodia in materiale termoplastico autoestinguente frequenza funzionamento tensione di riferimento per l'isolamento tensione di prova isolamento grado di protezione sovracorrente permanente corrente termica di breve durata nominale (I th) corrente dinamica nominale (I dyn) fattore di sicurezza max. potenza dissipata (portata max.) temperatura di funzionamento temperatura di magazzinaggio costruzione a norme terminali secondari integrati selfestinguishing thermoplastic material UL94-V0 insulation reference voltage 0,72 kV rated short-time...

 Open the catalog to page 12
Current & voltage transformers, shunts & voltage dividers-13

T.A. DI MISURA A PRIMARIO AVVOLTO Primary wound measuring CTs EH[ « Kz - Kazakhstan r 5A... i L 100A i Ed EAf UKRMETR TEST STANDARD custodia in materiale termoplastico autoestinguente frequenza funzionamento tensione di riferimento per l'isolamento tensione di prova isolamento grado di protezione sovracorrente permanente corrente termica di breve durata nominale (I th) corrente dinamica nominale (I dyn) fattore di sicurezza max. potenza dissipata (portata max.) temperatura di funzionamento temperatura di magazzinaggio costruzione a norme terminali secondari integrati TIPO - Type Rapporto Ratio...

 Open the catalog to page 13
Current & voltage transformers, shunts & voltage dividers-14

T.A. DI MISURA A PRIMARIO AVVOLTO Primary wound measuring CTs TAC008 EH[ «Kz - Kazakhstan UKRMETR TEST STANDARD DATI TECNICI - Technical data INPUT: E Cl custodia in materiale termoplastico autoestinguente frequenza funzionamento tensione di riferimento per l'isolamento tensione di prova isolamento grado di protezione sovracorrente permanente corrente termica di breve durata nominale (I th) corrente dinamica nominale (I dyn) fattore di sicurezza max. potenza dissipata (portata max.) temperatura di funzionamento temperatura di magazzinaggio costruzione a norme terminali secondari integrati selfestinguishing...

 Open the catalog to page 14