TSO, TSH: Room thermostat
4Pages

{{requestButtons}}

Catalog excerpts

TSO, TSH: Room thermostat - 1

Product data sheet TSO, TSH: Room thermostat How energy efficiency is improved Enables controlling of HVAC components according to needs. Features • Room temperature can be set as the setpoint using the printed temperature scale • Variants of the standard devices are available, such as thermal feedback, night set-back mode, fan switches and switches for heating/cooling • Setpoint adjuster with mechanical min. and max. limitation of the setting range TSO67*F001 Technical data Power supply 230 V~ 10(2,5) A, 24 V= max. 1 A, 24 V~ min. 0.2 A Parameters Setting range Time constant in still air Time constant in moving air (0.2 m/s) 13 min Thermal feedback Proportional band Shortest switching interval Admissible ambient temperature Ambient conditions Housing material Fire-retardant thermoplastic Wall/recessed Black thermoplastic with membrane sensor and contact system Screw terminals Fitting Cable inlet Standards and directives Protection class Energy class / Power supply: 10% more voltage means P-band approx. 4 K, switching period = 15 min, actualvalue reduction = approx. 0.5 K / H/C = heating or cooling, depending on connection; H//C = heating or cooling, selectable Type Operating mode switch Power supply Right of amendment reserved © 2015 Fr. Sauter AG

Open the catalog to page 1
TSO, TSH: Room thermostat - 2

Product data sheet TSO670F001, TSO672F001: switching difference 1.3 K without thermal feedback2) TSH670F002, TSH676F002: dynamic switching difference 0.5 K with thermal feedback3) TSH676F002: additional feature N/R (normal/reduced) for external clock Accessories Type Intermediate plate, pure white, for wall mounting on recessed junction box 0303124000: only in combination with intermediate cover plate 0362225001 Description of operation A membrane sensor expands depending on the temperature and activates an electrical switch. The operating points of the controller are determined by the...

Open the catalog to page 2
TSO, TSH: Room thermostat - 3

Product data sheet Operating time Proportional band Switching difference Room temperature Control factor (tE/SP) Upper change-over point Transient response of therm. feedback Lower change-over point Temperature at membrane sensor Engineering and fitting notes The specified voltage tolerances are necessary because the output of the feedback heating resistor is significantly dependent on it. 10% excess voltage results in: 20% more power, P-band 4 K, switching period 15 min instead of 19 min, reduction in room temperature 0.5 K. Disposal When disposing of the product, observe the currently...

Open the catalog to page 3
TSO, TSH: Room thermostat - 4

Product data sheet Thermal feedback Normal/Reduced (night set-back mode) Fr. Sauter AG Im Surinam 55 CH-4016 Basel Tel. +41 61 - 695 55 55 www.sauter-controls.com Right of amendment reserved © 2015 Fr. Sauter A

Open the catalog to page 4