1. Catalogs
  2. Fr. Sauter AG
  3. HSC 120: Room humidistat

HSC 120: Room humidistat

HSC 120: Room humidistat

HSC 120: Room humidistat

Product catalog summary
Product Overview: The HSC 120 Room Humidistat is designed to improve energy efficiency by enabling humidity control devices to operate based on need. It monitors and regulates relative air humidity in rooms by controlling fans, drying units, and air humidifiers.
Key Specifications:
  • Power Supply: Max load of 5(3) A, 250 V~; Min load of 100 mA, 24 V.
  • Setting Range: 30...90% relative humidity (rh).
  • Setting Accuracy: ±5% rh at 55% rh and 23 °C.
  • Switching Difference: Typically 6% rh.
  • Long-term Stability: Approx. -1.5% rh per annum.
  • Temperature Influence: 0.5% rh per Kelvin.
Environmental Conditions:
  • Operational Humidity: 30...90% rh (non-condensing).
  • Operational Temperature: 0...50 °C.
  • Storage and Transport Humidity: 10...95% rh (non-condensing).
  • Storage and Transport Temperature: -20...70 °C.
Design and Construction:
  • Weight: 0.09 kg.
  • Housing: Pure white (RAL 9010), made of fire-retardant thermoplastic.
  • Screw Terminals: Suitable for wire up to 1.5 mm².
Standards and Compliance:
  • Ingress Protection: IP 20 (EN 60529).
  • Protection Class: II (IEC 60730).
  • CE Conformity: Complies with EMC directive 2004/108/EC and Low-voltage directive 2006/95/EC.
Product Variants:
  • HSC120F001: External setpoint adjuster.
  • HSC120F010: Internal setpoint adjuster.
Accessories: Intermediate plate for wall mounting on recessed junction box.
Operation Description: The humidistat operates by opening and closing contacts based on humidity levels. Recalibration may be necessary due to the ageing effect of the measuring element.
Installation Notes: The housing allows for cable insertion from behind and can be mounted on recessed junction boxes. Openings for surface mounting can be made as needed.
Disposal: Disposal must comply with local laws, and further information on materials is available in the product's material declaration.
See more

Catalog excerpts

HSC 120: Room humidistat-1

Product data sheet HSC 120: Room humidistat Improving energy efficiency Enables humidity control devices to be switched on according to needs Properties • Monitoring and regulation of relative air humidity in rooms by controlling fans, drying units and air humidifiers • Variable relative humidity as setpoint based on printed scale in % rh • Measurement taken via a measuring element of stabilised synthetic textile tape. • Micro-switch with fixed switching difference XSd Technical data Setting accuracy Power supply Switching difference Typ. 6% rh Long-term stability Approx. -1.5% rh/a Time constant in moving air (0.2 Approx. 5 min Ambient conditions Operation Humidity (non-condensing) 30...90 %rh Storage and transport Humidity (non-condensing) 10...95 %rh Structural design Housing Pure white (RAL 9010) Housing material Fire-retardant thermoplastic Screw terminals For wire of up to 1.5 mm2 Ingress protection IP 20 (EN 60529) Protection class II (IEC 60730) Overview of types Type Features HSC120F001 External setpoint adjuster HSC120F010 Internal setpoint adjuster The setting accuracy of the humidistat is valid for the calibration point ±5% rh at 55% rh and 23 °C following initial calibration at the factory. See diagram “Setting accuracyIn general, humidity sensors (humidistats) are subject to increased ageing if they are used and/or stored in very contaminated air or aggressive gases. The humidistat may start to drift and its linearity may change under these conditions. If the humidistats are used in very contaminated air, the warranty does not cover a premature re-calibration or the replacement of the complete humidistat WSAUTER Right of amendment reserved © 2014 Fr. Sauter AG

 Open the catalog to page 1
HSC 120: Room humidistat-2

Product data sheet Accessories Type Description 0362225001 Intermediate plate, pure white, for wall mounting on recessed junction box Additional information Fitting instructions WSAUTER Right of amendment reserved © 2014 Fr. Sauter AG

 Open the catalog to page 2
HSC 120: Room humidistat-3

Product data sheet Dimension drawing Right of amendment r es er ved © 2014 Fr. Sauter AG Fr. Sauter AG Im Surinam 55 CH-4016 Basel Tel. +41 61 - 695 55 55 www.sauter-controls.com Right of amendment reserved © 2014 Fr. Sauter AG

 Open the catalog to page 3

All Fr. Sauter AG catalogs and technical brochures

  1. SAUTER Catalogue

    551  Pages

  2. EQJW 24

    8  Pages

  3. NRT 101

    8  Pages

  4. Thermowells

    6  Pages

  5. SAUTER EGQ

    4  Pages

  6. TFL 201

    3  Pages

  7. TLC

    2  Pages

  8. TSHK 670...67

    3  Pages

  9. SAUTER FACTS

    28  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.