1. Catalogs
  2. Fr. Sauter AG
  3. flexotron ® 2000

flexotron ® 2000

flexotron ®  2000

flexotron ® 2000

Product catalog summary
Overview: The Flexotron® 2000 by Sauter Components includes the EXR 101 and EXR 102 switching units designed to enhance energy efficiency by enabling two-stage fan control. These units can be used for switching and alarm functions across various applications.
Key Features:
  • Analogue user interface for easy operation.
  • LED display indicating switching status.
  • Setpoint and switching difference settings available.
Technical Description:
  • Standard housing compliant with DIN 43880, made from flame-retardant thermoplastic.
  • Analogue input options: 0 - 10 V or 4 - 20 mA.
  • Potential-free relay contact per switch position.
  • Mountable on top-hat rail as per EN 60715.
  • Electrical connections via screw terminals for wires up to 2.5 mm².
Operation: The input signal is compared with setpoints XS1 (XS2). If exceeded, contacts 5-4 (8-7) close, indicated by an LED. If the input signal falls below XS1-XSd1 (XS2-XSd2), contacts 5-3 (8-6) close.
Compliance and Standards:
  • Complies with Directive 2006/95/EC and EMC directive 2004/108/EC.
  • Meets standards EN 60730-1, EN 60730-2-9, EN 61000-6-1, EN 61000-6-3, and EN 61000-6-4.
Technical Data:
  • EXR 101: 1-stage switching unit, 24 V~, 0.13 kg.
  • EXR 102: 2-stage switching unit, 24 V~, 0.22 kg.
  • Input: 0(2)...10 V, Ri = 30 kΩ or 0(4)...20 mA, Ri = 50 Ω.
  • Output relay: 4(1)A, 250 V~.
  • Power supply: 24 V~ ± 20%, 50...60 Hz.
  • Power consumption: approx. 3 VA.
  • Permissible ambient temperature: 0...40 °C.
  • Degree of protection: IP 20 (EN 60529), frontal IP 40.
Accessories:
  • Terminal covers for EXR 101 and EXR 102 to attain protection class II as per IEC 60730.
Additional Notes: The units are protected against excess voltage up to 20 V and excess current up to 40 mA. Wiring diagrams and dimension drawings are available for both EXR 101 and EXR 102.
See more

Catalog excerpts

flexotron ®  2000-1

flexotron 2000 EXR 101, 102: Switching units How energy efficiency is improved Switching outputs for the activation of a two-stage fan control. With this you can, for example, retrofit a system with a ventilation control if needed. Areas of application Switching and alarm function in various applications. Features • Easy to operate thanks to analogue user interface • LED display for indication of switching status • Setting options for setpoint and switching difference Technical description • Standard housing as per DIN 43880 made of flame-retardant thermoplastic • Analogue input 0 - 10 V or 4 - 20 mA • 1 potential-free relay contact per switch position • Suitable for mounting on top-hat rail as per EN 60715 • Electrical connection with screw terminals for wires up to 2.5 mm² 1-stage switching unit 2-stage switching unit Setting ranges Setpoint XS1, XS2 Switching difference Power supply 24 V~ Power consumption Permissible ambient temp. Degree of protection frontal Wiring diagram Dimension drawing Fitting instructions Input or Output relay Terminal cover for EXR 101; attains protection class II as per IEC 60730 Terminal cover for EXR 102; attains protection class II as per IEC 60730 Protected against excess voltage up to 20 V– Protected against excess current up to 40 mA Operation The input signal is compared with the setpoint XS1 (XS2) If this is exceeded, contacts 5-4 (8-7) are closed, which is indicated by an LED. If the input signal undercuts the value XS1-XSd1 (XS2-XSd2), contacts 5-3 (8-6) are closed. N.B.: The figures in brackets also apply to EXR 102. Engineering note The contacts are equipped with RC circuitry. Additional technical data EXR 101 F001 EXR 102 F001 Complies with:Complies with:Directive 2006/95/EC EN 60730-1/ EN 60730-2-9 Directive 2006/95/EC EN 60730-1/ EN 60730-2-9 EMC directive 2004/108/EC EN 61000-6-1/ EN 61000-6-3 EMC directive 2004/108/EC EN 61000-6-1/ EN 61000-6-2 EN 61000-6-4 EN 61000-6-3/ EN 61000-6-4 Sauter Components

 Open the catalog to page 1
flexotron ®  2000-2

Wiring diagrams Dimension drawings Right of amendment reserved N.B.: A comma between cardinal numbers denotes a decimal point

 Open the catalog to page 2

All Fr. Sauter AG catalogs and technical brochures

  1. SAUTER Catalogue

    551  Pages

  2. EQJW 24

    8  Pages

  3. NRT 101

    8  Pages

  4. Thermowells

    6  Pages

  5. SAUTER EGQ

    4  Pages

  6. TFL 201

    3  Pages

  7. TLC

    2  Pages

  8. TSHK 670...67

    3  Pages

  9. SAUTER FACTS

    28  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.