Overview: The EGT 311 and 411 are clamp-on temperature sensors designed for precise room temperature measurement, enhancing energy efficiency in HVAC systems. They are suitable for monitoring energy consumption and controlling HVAC installations.
Features:
  • Available with passive or active measuring elements.
  • IP65 protection against dust and humidity.
  • Designed for temperature measurement on pipes with diameters ranging from 10 to 50 mm.
  • Includes a retaining strap and silicone-free heat-conducting paste.
Technical Data:
  • Recommended measurement current is typically less than 1 mA.
  • Time constant with heat-conducting paste is 16 seconds.
  • Storage and transport temperature range: -35 to 70 °C.
  • Humidity tolerance: 85% relative humidity, non-condensing.
  • Housing made of polyamide, available in yellow/black.
  • Connection terminals support 0.35 - 1.5 mm² wires.
Standards and Directives:
  • IP65 protection as per EN 60529.
  • CE conformity according to RoHS Directive 2011/65/EU and EMC Directive 2004/108/EC.
Resistance Values:
  • Ni1000: 1000 Ω at 0 °C, ±0.4 K tolerance.
  • Ni200: 200 Ω at 0 °C, ±0.4 K tolerance.
  • Pt100: 100 Ω at 0 °C, ±0.3 K tolerance.
Product Types:
  • EGT311F022: Passive, Ni200, -35 to 90 °C, 80 g.
  • EGT311F102: Passive, Ni1000, -35 to 90 °C, 80 g.
  • EGT411F102: Passive, Pt1000, -35 to 90 °C, 80 g.
  • EGT311F031: Active, adjustable range -50 to 160 °C, 0...10 V output, 120 g.
Operation: The sensor's resistance changes with temperature, with a positive temperature coefficient. It is designed for use on pipes and curved surfaces, connecting to control and display systems.
Installation Notes:
  • Requires safety extra low voltage (SELV/PELV) for operation.
  • Must be installed by a qualified electrician.
  • Use retaining strap for fitting, ensuring the tube diameter does not exceed 50 mm.
  • Apply heat-conducting paste to the brass sleeve before fastening.
Disposal: Follow local laws for product disposal. Additional material information is available in the product's environmental declaration.
See more

Catalog excerpts

EGT 311, 411: Clamp-on temperature sensor-1

Product data sheet EGT 311, 411: Clamp-on temperature sensor How energy efficiency is improved Precise measurement of room temperature for energy-efficient control of HVAC installations and monitoring energy consumption Features • Passive or active measuring element • Extra protection against dust and humidity (IP65) • Temperature measurement on pipes • Including retaining strap for pipes of 0 10...50 mm • Heat-conducting paste (silicone-free) is included in the scope of delivery Technical data Parameters Time characteristic with heatconducting paste Recommended measurement current Typ.< 1 mA Time constant 16 s Ambient conditions Storage and transport temperature -35...70 °C Humidity (non-condensing) 85% rh Housing Yellow/black Housing material Polyamide Connection terminals Screw terminals 0.35 - 1.5 mm2, for number of poles see connection diagram Cable inlet M16 for cable RoHS Directive 2011/65/EU EN 50581 EN 60730-1. Mode of operation 1. Residential premises Resistance values / characteristics i The tolerance listed below applies only to the corresponding measuring element. The accuracy of the sensor depends on the cable length and the measuring element used. Measuring element Overview of types Type ^ SAUTER Right of amendment reserved © 2015 Fr. Sauter AG

 Open the catalog to page 1
EGT 311, 411: Clamp-on temperature sensor-2

Product data sheet Accessories Type Description 0300360002 Retaining strap 900 mm and heat-conducting paste 0300360004 Heat-conducting paste incl. gun with 2 g content Description of operation The resistance of the measuring element changes according to the temperature. The temperature coefficient is positive, which means the resistance increases along with the temperature. The elements can be exchanged within the specified tolerance ranges. Areas of use Clamp-on sensor for temperature measurement on pipes and curved surfaces. Designed for connection to control and display systems. Intended...

 Open the catalog to page 2
EGT 311, 411: Clamp-on temperature sensor-3

Product data sheet 31.130 IQ O O O O Q| lOODOOOl Q 16 6 6 6 o o| lo o o oinsi lo o o q o ol Offset adjustment 0 K-3 K +3 K Dimension drawing Fr. Sauter AG Im Surinam 55 CH-4016 Basel Tel. +41 61 - 695 55 55 www.sauter-controls.com ^ SAUTER Right of amendment reserved © 2015 Fr. Sauter AG

 Open the catalog to page 3

All Fr. Sauter AG catalogs and technical brochures

  1. SAUTER Catalogue

    551  Pages

  2. EQJW 24

    8  Pages

  3. NRT 101

    8  Pages

  4. Thermowells

    6  Pages

  5. SAUTER EGQ

    4  Pages

  6. TFL 201

    3  Pages

  7. TLC

    2  Pages

  8. TSHK 670...67

    3  Pages

  9. SAUTER FACTS

    28  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.