1. Catalogs
  2. Fr. Sauter AG
  3. DSA: Pressure switch

DSA: Pressure switch

DSA: Pressure switch

DSA: Pressure switch

Product catalog summary
Overview: The DSA pressure switch is designed for regulating and monitoring pressure in liquids, gases, and vapors without the need for auxiliary energy. It is particularly suitable for compact installations and features an adjustable upper switching point with a fixed switching difference, eliminating the need for hysteresis settings. The pressure sensor is made of brass, suitable for non-aggressive media.
Technical Specifications:
  • Power Supply: Maximum load with gold-plated contacts is 400 mA, 24 V, 10 VA; minimum load is 4 mA, 5 V. For silver-plated contacts, the maximum load is 10(4) A, 250 V~, 50 W, 250 V=; minimum load is 100 mA, 24 V.
  • Pressure Connection: G½" male.
  • Temperature Range: Sensor temperature up to 70 °C; ambient temperature from -20 to 70 °C.
  • Construction: Pipe and wall mounting with a transparent cover made of impact-proof thermoplastic.
  • Protection: IP 65 (EN 60529), Protection class I (IEC 60730), CE conformity according to various directives.
Types and Parameters:
  • DSA140F002: Setting range 0.5...2.5 bar, switching difference 0.25 bar, maximum pressure 12 bar, vacuum loading -0.7 bar, weight 0.5 kg.
  • DSA143F002: Setting range 0.5...6 bar, switching difference 0.3 bar, maximum pressure 16 bar, vacuum loading -0.7 bar, weight 0.5 kg.
  • DSA146F002: Setting range 1...10 bar, switching difference 0.4 bar, maximum pressure 20 bar, vacuum loading -1.0 bar, weight 0.4 kg.
Operation: The pressure switch operates by switching contacts when the pressure exceeds or falls below the setpoint by the fixed switching difference. It is intended for use as described and should not be altered.
Service Life: Electrical elements are tested for 250,000 to 1,000,000 switchings depending on the load and conditions. Mechanical service life exceeds 2 million switch strokes.
Materials: The pressure sensor is made of brass, stainless steel, and nitrile rubber. Disposal should comply with local laws.
Accessories: Various accessories are available, including throttle screws, cap nuts, capillary tubes, setpoint adjusters, damping screws, and fixing brackets.
See more

Catalog excerpts

DSA: Pressure switch-1

Product data sheet DSA: Pressure switch How energy efficiency is improved Control and monitoring according to needs and with no auxiliary energy. For regulating and monitoring pressure in liquids, gases and vapours Especially suitable for applications in compact installations Upper switching point can be set Fixed switching difference, no hysteresis setting is necessary Sealable Pressure sensor made of brass for non-aggressive media Technical data Power supply 400 mA, 24 V, 10 VA Minimum load with gold-plated contacts Maximum load with silver-plated con- 10(4) A, 250 V~, 50 W, 250 V= tacts Maximum load with gold-plated contacts1) Minimum load with silver-plated con- 100 mA, 24 V tacts 3 2 Pressure connection Admissible sensor temperature Admissible ambient temperature Pipe and wall mounting Transparent cover Ambient conditions Housing material Impact-proof thermoplastic Housing-mounted plug Standard plug with female cable connector for cable of Ø 6...10 mm Standards and directives Protection class Machine directive 2006/42/EC (according to appendix IIB) Overview of types Type Setting range Switching difference Maximum pressure Admissible vacuum loading DSA: Pressure sensor made of brass for non-aggressive media; Xs = upper switching point If the contacts are subjected to a load greater than specified, the gold plating will be destroyed. They are then classed merely as silver contacts and lose the properties of gold-plated contacts Depending on the fitting position, see the fitting instructions. The devices are not suitable for outdoor applications. Excluded from the directive on pressure equipment 97/23/EC (as per Art. 1.3.6) Right of amendment reserved © 2014 Fr. Sau

 Open the catalog to page 1
DSA: Pressure switch-2

Product data sheet Accessories Type Throttle screw for absorbing pressure surges, brass Cap nut with solder connector 1 m capillary tube for absorbing pressure surges, copper Throttle screw for absorbing pressure surges, stainless steel Reduction piece G½" on 7/16" 20-UNF-2A for copper tubes of Ø 6 mm, brass Setpoint adjuster according to customer's wishes (setting accuracy: ±3% of the setting range, but a minimum of ±0.2 bar) Setpoint adjuster sealed (with accessory 0292001 only) Damping screw for absorbing pressure surges in low viscosity media Fixing bracket for wall mounting Fixing brackets...

 Open the catalog to page 2
DSA: Pressure switch-3

Product data sheet Materials Materials that come into contact with the medium: Pressure sensor made of brass (DSA): brass, stainless steel, nitrile rubber. Disposal When disposing of the product, observe the currently applicable local laws. More information on materials can be found in the Declaration on materials and the environment for this product. Dimension drawing Right of amendment reserved © 2014 Fr. Sauter AG Connection diagram

 Open the catalog to page 3
DSA: Pressure switch-4

Product data sheet Fr. Sauter AG Im Surinam 55 CH-4016 Basel Tel. +41 61 - 695 55 55 www.sauter-controls.com Right of amendment reserved © 2014 Fr. Saute

 Open the catalog to page 4

All Fr. Sauter AG catalogs and technical brochures

  1. SAUTER Catalogue