1. Catalogs
  2. Fr. Sauter AG
  3. Dew-point monitor and transducer

Dew-point monitor and transducer

Dew-point monitor and transducer

Dew-point monitor and transducer

Product catalog summary
Overview: The EGH 102 is a dew-point monitor and transducer designed by Sauter Components to enhance energy efficiency by providing effective protection against humidity damage and excessive cooling. It is primarily used to prevent dew formation on chilled beams and to control a regulating unit via a holding relay.
Features:
  • Spring-loaded dew-point sensor for measurement.
  • Active measured value acquisition.
  • Available versions with external sensors.
Technical Description:
  • Housing made of flame-retardant thermoplastic (RAL 9010).
  • Includes a holding relay with change-over contact.
  • Screw terminals accommodate wires up to 1.5 mm².
  • Includes cable inlet for Pg 11 and strap retainer for pipes 10 to 100 mm in diameter.
Operation: The dew-point sensor's resistance increases with relative humidity. This resistance is evaluated by the electronics unit, which controls the change-over contacts via a holding relay. Contacts 4-6 close when the switching point is reached or exceeded, while contacts 4-5 open. If the switching point is undercut, contacts 4-6 open and contacts 4-5 close. An analogue output signal is available at Pin 3.
Engineering and Fitting Notes: The monitor should be installed at the coldest point of the supply pipe. The pipe surface must be clean and bare, with heat-conducting paste applied sparingly. The sensor is secured using a strap with a snap-shut mechanism.
Specifications:
  • Switching point: 95 ± 4 %rh.
  • Sensor measuring range: 70…85 %rh.
  • Power supply: 24 V~/= ± 20%.
  • Power consumption: max. 1 VA.
  • Degree of protection: IP 40 (EN 60529).
  • Change-over contacts: 1A, 24 V~/=.
  • Output signal: 0...10 V, load > 10 kΩ.
  • Response time in still air: max. 3 min for 80 to 99 %rh and 99 to 80 %rh.
Recommendations: When driving relays or contactors with cos ϕ < 0.3, it is recommended to use an RC section in parallel to the coil to reduce contact pitting and prevent high-frequency interference impulses.
See more

Catalog excerpts

Dew-point monitor and transducer-1

34.042 Sauter Components EGH 102: Dew-point monitor and transducer How energy efficiency is improved Effective protection against humidity damage and excessive cooling. Areas of application Protection against dew formation on chilled beams. Control system for a regulating unit using a holding relay, which interrupts the flow of cold water or raises the temperature of the cooling water. Features • Measurement is effected by a spring-loaded dew-point sensor • Active measured value acquisition • Versions with external sensor Technical description • Housing made of pure-white, flame-retardant thermoplastic (RAL 9010) • Holding relay with change-over contact • Screw terminals for wire of up to 1,5 mm² • Cable inlet for Pg 11 • Strap retainer for 10 to 100 mm ø pipe and heat-conducting paste are included in supply Operation The resistance of the dew-point sensor rises in accordance with the relative humidity. The resistance value is evaluated with the aid of the electronics unit and then (via a holding relay) used to control the change-over contacts. When power is applied, contacts 4-6 close as soon as the switching point is reached or exceeded. At the same time, contacts 4-5 open. If the switching point is undercut by the amount of the switching difference, contacts 4-6 open and contacts 4-5 close. In addition, there is an analogue output signal (Pin 3) available. If no power is applied, contacts 4-6 are closed and contacts 4- 5 are open. Engineering and fitting notes The monitor should be fitted to the supply pipe at its coldest place: the surface of the pipe should be rendered clean and bare, the heat-conducting paste applied sparingly, and the sensor fixed by tightening the strap (snap-shut mechanism). Y02859 H % Type Switching point %rh Sensor Measuring range %rh Power supply Weight kg EGH 102 F001 95 ± 4 on housing 70…85 24 V~/= 0,1 EGH 102 F101 95 ± 4 with cable 70…85 24 V~/= 0,1 Power supply 24 V~/= ± 20% Exposure to dew max. 30 min Switching difference fixed, approx. 5 %rh Ambient temperature 5...60 °C Power consumption max. 1 VA Degree of protection IP 40 (EN 60529) Change-over contacts 1) 1A, 24 V~/= Output signal Wiring diagram A09353 approx. 70...85 %rh 0...10 V, load > 10 kÙ Dimension drawing F001 M07664 Response time in still air:- F101 M10454 80 to 99 %rh max. 3 min Fitting instructions F001 MV 505732 99 to 80 %rh max. 3 min F101 MV 506037 1) When driving relays, contactors etc. with cos < 0,3, the use of an RC section in parallel to the coil is recommended. This reduces pitting of the contacts and prevents high-frequency interference impulses. XSd 6 B09444 5 4 95 %rh 10 V- Output signal 0 70 % r.h. 85 B06506 7134042003 04

 Open the catalog to page 1

All Fr. Sauter AG catalogs and technical brochures

  1. SAUTER Catalogue

    551  Pages

  2. EQJW 24

    8  Pages

  3. NRT 101

    8  Pages

  4. Thermowells

    6  Pages

  5. SAUTER EGQ

    4  Pages

  6. TFL 201

    3  Pages

  7. TLC

    2  Pages

  8. TSHK 670...67

    3  Pages

  9. SAUTER FACTS

    28  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.