1. Catalogs
  2. Fr. Sauter AG
  3. ASV115CF152, ASV115BF152: VAV compact controller for laboratory and pharmaceutical applications

ASV115CF152, ASV115BF152: VAV compact controller for laboratory and pharmaceutical applications

ASV115CF152, ASV115BF152: VAV compact controller for laboratory and pharmaceutical applications
1 / 17 PagesView full catalog

ASV115CF152, ASV115BF152: VAV compact controller for laboratory and pharmaceutical applications

Product catalog summary
Overview: The ASV115CF152 and ASV115BF152 are VAV compact controllers designed for laboratory and pharmaceutical applications, enhancing energy efficiency through demand-based volume flow control.
Key Features:
  • Controls air in fume cupboards, laboratories, clean rooms, hospital wards, and operating theatres.
  • Uses static differential pressure measurement with a capacitive method.
  • Equipped with a brushless DC motor for minimal energy consumption and long service life.
  • Includes electromechanical torque limitation and a self-centering shaft adapter for easy installation.
  • Supports RS-485 bus interface and BACnet MSTP communication.
  • Programmable via SAUTER CASE VAV software.
Technical Specifications:
  • Power supply: 24 V~, ±20%, 50-60 Hz or 24 V=, ±20%.
  • Power consumption: Approx. 15 VA during operation, 4.5 VA when idle.
  • Torque: 10 Nm with a holding torque of 2 Nm.
  • Operating temperature: 0-55 °C; storage temperature: -20-55 °C.
  • Humidity: < 85% rh, no condensation.
  • Interfaces: RS-485, supporting SAUTER Local Communication (SLC) and BACnet MSTP.
Applications:
  • Volume flow control, room pressure control, duct pressure control, and flow control for fume cupboards.
  • Priority control via digital inputs and analogue outputs for volume flow and temperature control.
Installation and Configuration:
  • Self-centering spindle adapter for fitting.
  • Preconfigured inputs and outputs for ease of use.
  • Configurable via SAUTER CASE VAV software for specific applications.
Standards and Compliance:
  • Type of protection: IP30 (EN 60529).
  • Conforms to Machine Directive 2006/42/EC and EMC Directive 2004/108/EC.
Specifications and Initialisation: The controller determines the angle of rotation through initialisation, which can be disabled via software. It operates differently in 24 V= mode compared to AC mode.
Connection and Functionality: Features an RS-485 interface with a fixed baud rate of 115.2 kbit/s, supporting up to 31 devices. Operates in SLC or BACnet MSTP mode.
BACnet MSTP Protocol: Supports various BACnet BIBBs and standard objects, with specific configurations for data sharing and device management.
Configuration with CASE VAV: Facilitates easy configuration, saving presets, and monitoring parameters. Includes a BACnet browser.
Installation and Wiring: Can be installed in any position with specific wiring recommendations for the 24 V power supply.
Standards and Safety: Compliance with local installation and safety standards is necessary. Outdoor installations should be weather-protected.
Technical Details: Includes a brushless DC motor and maintenance-free transmission. Supports twisted-pair wiring for bus connections.
Example Applications: Used for VAV with cascade control for CO2, temperature, and differential pressure. Supports a second control loop for various sensor inputs.
Specifications and Procedures: Outlines VAV systems with reheaters and recoolers, emphasizing continuous valve actuator use.
Room Pressure Control: Includes a second control loop for room pressure management, crucial for maintaining air-tightness in clean rooms.
Fume Cupboard Control: Complies with EN 14175, adjusting volume flow based on sash opening or air inflow speed.
Duct Section Pressure Control: Regulates differential pressure in duct sections to maintain constant upstream pressure.
System Diagrams: Provides diagrams illustrating configurations and components involved in each application.
See more

Catalog excerpts

ASV115CF152, ASV115BF152: VAV compact controller for laboratory and pharmaceutical applications-1

Product data sheet ASV115CF152, ASV115BF152: VAV compact controller for laboratory and pharmaceutical applications How energy efficiency is improved Allows demand-based volume flow control in order to optimise energy consumption in ventilation systems. Differential pressures of as little as 1 Pa can be controlled to allow minimal volume flows for the lowest possible duct pressure and energy consumption. Features • Controlling the return air in fume cupboards and controlling the supply and return air in laboratories, clean rooms, hospital wards and operating theatres using a VAV box or a damper and flow probe. • Static measurement of differential pressure based on the capacitive method of measurement • Can be used in areas with dirty or contaminated return air • Brushless DC motor guarantees minimum energy consumption and a long service life • Electromechanical torque limitation for safe operation • Extremely simple installation due to self-centring shaft adapter • Disengageable transmission for manual adjustment and positioning of damper • Power cable 0.5 m long, 10 × 0.32 mm2, fixed to housing • Integrated second control loop for the following applications:1): • Room-pressure control: can be ideally combined with EGP 100 with symmetrical measuring range • Room temperature control: can be ideally combined with SAUTER Ni1000 sensor and AXS 215S continuous valve actuator • RS-485 bus interface • Up to 31 subscribers in a segment with SLC (SAUTER Local Communication) protocol • Communication within network via BACnet MSTP2) • Very easy programming of the following applications using the SAUTER CASE VAV software:3): • Volume flow control • Room pressure control • Duct pressure control • Flow control for fume cupboards • Adjustable end values of the differential pressure measuring range4) • 50...150 Pa • 100...300 Pa • Efficient control algorithm for fast control loops • Analogue input and output signals to connect the setpoints and actual values for: • Volume flow • Room pressure control • Room temperature control • Duct section pressure control • Control of fume cupboards • Priority control via switching contacts • Zero point can be calibrated Technical data Power supply Power supply5) Power consumption during operation Approx. 15 VA (10 Nm) Power consumption when idle6) Application support depending on hardware and software version in CASE VAV manual 7010022001 Support of BACnet MSTP interface depending on hardware/type Application support depending on hardware and software version in CASE VAV manual 7010022001 Available measuring ranges depending on hardware/type 24 V=: Analogue inputs that are not connected are rated 0 V. The nominal torque is achieved within the specified tolerances. Terminal 02 cannot be used with 24 V= power supply. Holding torque approx. 5 N

 Open the catalog to page 1
ASV115CF152, ASV115BF152: VAV compact controller for laboratory and pharmaceutical applications-2

Product data sheet Parameters Torque Integrated damper actuator Admissible dimensions of damper shaft Admissible damper shaft (hardness) Operating noise ∆p sensor Surge-voltage resistance Measuring range ∆p (gain = 1) 0...150/300 Pa Pressure range, types D & I/E & K10) Linearity error Time constant Zero point stability Admissible positive pressure Admissible operating pressure pstat12) ±3 kPa Low-pressure connections13) Ambient conditions Operating temperature Storage and transport temperature Admissible humidity Interfaces and communication RS-485 not electrically isolated SAUTER Local Communication...

 Open the catalog to page 2
ASV115CF152, ASV115BF152: VAV compact controller for laboratory and pharmaceutical applications-3

Product data sheet Construction Weight Self-centring spindle adapter Power cable Standards and directives Protection class Machine directive 2006/42/EC, appendix II 1.B Overview of types Type ASV115CF152D, ASV115CF152E, ASV115BF152D: Version with PVC cable ASV115CF152I, ASV115CF152K: Version with halogen-free cable Accessories Type CERTIFICAT001 Manufacturer’s test certificate type M 0372300001 Torsion protection, long (230 mm) Spindle adaptor for squared end hollow profile (x 15 mm), pack of 10 pcs. Flow sensor to measure the air volume in ventilation ducts Reference pressure container Description...

 Open the catalog to page 3
ASV115CF152, ASV115BF152: VAV compact controller for laboratory and pharmaceutical applications-4

Product data sheet Colour coding Actual value Priority control rqV 0…10 V Ξ 0…100% mnom mmin (actuated condition) Priority control mmax (actuated condition) Volume flow characteristics To configure the device, the design data of the VAV box must be loaded to the actuator using the SAUTER CASE VAV software. At least the following data is required for this: Box DN Unit Setting the operating volume flows The following functions are available for operating the VAV controller: Volume flow control setting ranges Function Volume flow / damper posi- Maximum tion setting ranges Recommended setting ranges...

 Open the catalog to page 4
ASV115CF152, ASV115BF152: VAV compact controller for laboratory and pharmaceutical applications-5

Product data sheet tion of these applications and their functions using the CASE VAV software is described in the document 7010022001. Functions of the ASV115 (existing functions depending on application or selected type) Digital inputs (DI04 and DI05) Priority control can be implemented using the available digital inputs. Individual functions can be selected easily using the software. The digital inputs can be operated with normally-closed contacts or normally-open contacts. A mixture of NC and NO contacts can be used. Minimum and maximum volume flow (mmin and mmax) of the VAV controller command...

 Open the catalog to page 5
ASV115CF152, ASV115BF152: VAV compact controller for laboratory and pharmaceutical applications-6

Product data sheet Temperature actual value (Ni1000) The temperature is measured by an Ni1000 sensor connected to terminal 04. The measuring range of the temperature input is 0…50 °C. Actuator positioning signal (AO02) A continuous valve actuator can be activated via analogue output 02. The output signal relates to the corresponding sequence of the temperature controller and can be configured freely or as a 0…10 V, 2…10 V signal. Note This function is only available with a power supply of 24 V~. Sensor technology The measuring element in the VAV compact controller is a static twin-membrane sensor...

 Open the catalog to page 6

All Fr. Sauter AG catalogs and technical brochures

  1. SAUTER Catalogue

    551  Pages

  2. EQJW 24

    8  Pages

  3. NRT 101

    8  Pages

  4. Thermowells

    6  Pages

  5. SAUTER EGQ

    4  Pages

  6. TFL 201

    3  Pages

  7. TLC

    2  Pages

  8. TSHK 670...67

    3  Pages

  9. SAUTER FACTS

    28  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.