1. Catalogs
  2. Flowair
  3. CATALOGUE CARD LEO S | L | XL / BMS

CATALOGUE CARD LEO S | L | XL / BMS

CATALOGUE CARD LEO S | L | XL / BMS

CATALOGUE CARD LEO S | L | XL / BMS

Product catalog summary
General Information
Fan heaters LEO are designed for heating large volume buildings such as industrial and public buildings. They are intended for indoor use where air dustiness does not exceed 0.3 g/m3. The devices feature an EPP housing in grey color (similar to RAL 9007) and come with a standard 3-speed, energy-saving fan. They are easy to mount due to their small size and weight.
Heating Capacity Range
The heaters operate with a maximum temperature of 120/90/0°C at III-speed and a minimum of 40/30/20°C at I-speed.
Control System
The T-box control system offers 3-speed auto fan regulation with modes for heating and ventilation, antifreeze, and integration with the FLOWAIR SYSTEM. The TS control system provides manual fan regulation with similar modes.
Installation
Various models (S1, S2, S3, L1, L2, L3, XL2, XL3) have specific installation parameters, including airflow and pressure requirements.
Technical Data
  • LEO S Series: Max airflow ranges from 1000 to 2300 m3/h, heating power ranges from 0.7 to 32.7 kW, and the devices have a max operating pressure of 1.6 MPa.
  • LEO L Series: Max airflow ranges from 1200 to 4250 m3/h, heating power ranges from 1.3 to 65.2 kW.
  • LEO XL Series: Max airflow ranges from 2500 to 5800 m3/h, heating power ranges from 6.6 to 121.0 kW.
All models have a max heating water temperature of 120°C, a max working temperature of 60°C, and are designed for indoor use.
Acoustic Levels
Acoustic pressure levels range from 42.1 to 67.5 dB(A) depending on the model and speed, measured 5m from the unit in a 1500m3 space.
Heating Capacity Tables
Detailed tables provide specific heating capacities, water flow rates, and pressure drops for various inlet and outlet water temperatures across different models and speeds.
See more

Catalog excerpts

CATALOGUE CARD LEO S | L | XL / BMS-1

FLOWAIR GŁOGOWSKI I BRZEZIŃSKI SP.J. ul. Chwaszczyńska 135, 81-571 Gdynia tel. (058) 669 82 20 www.flowair.com CATALOGUE CARD LEO S | L | XL / BMS KARTA KATALOGOWA LEO S | L | XL / BMS GENERAL INFORMATION | INFORMACJE OGÓLNE EN • Fan heaters LEO are used for heating large volume buildings: general, industrial and public buildings etc. The devices are designed for indoor use where maximum air dustiness does not exceed 0,3 g/m3. EPP housing, colour grey (near to RAL 9007) 3-speed, energy saving fan in standard. Easy to mount thanks to small size and weight. Wodne nagrzewnice powietrza LEO służą do ogrzewania obiektów o dużych kubaturach budownictwa ogólnego i przemysłowego, budynków użyteczności publicznej itp. Przeznaczone są do pracy wewnątrz pomieszczeń o maksymalnym zapyleniu powietrza 0,3g/m3. Obudowa wykonana z EPP, kolor szary (zbliżony do RAL 9007) W standardzie z energooszczędnym wentylatorem z silnikiem 3 biegowym. Łatwy montaż dzięki niewielkim gabarytom oraz masie. HEATING CAPACITY RANGE | ZAKRES MOCY GRZEWCZYCH max. 120/90/0oC III-speed, min. 40/30/20oC I-speed | max. 120/90/0oC III-bieg, min. 40/30/20oC I-bieg CONTROL SYSTEM I STEROWANIE T-box LEO S BMS | L BMS | XL BMS - 3-speed, auto fan regulation - 3-stopniowa, automatyczna regulacja wentylatora working modes: heating/ventilation tryby pracy: grzanie/wentylacja antifreeze BMS integration with FLOWAIR SYSTEM integracja urządzeń do SYSTEMU FLOWAIR TS LEO S | L | XL - 3-speed, manual fan regulation 3-stopniowa, manualna regulacja wentylatora - working modes: heating/ventil

 Open the catalog to page 1
CATALOGUE CARD LEO S | L | XL / BMS-2

INSTALATION I MOŻLIWOŚĆ MONTAŻU A TECHNICAL DATA I DANE TECHNICZNE LEO S1 I S2 I S3 Max airflow [m /h ] | Max. strumień przepływu powietrza [m /h ] Heating power range | Zakres mocy grzewczej [kW]* Nominal heating power (70/50/16oC, III-speed) | Nominalna moc grzewcza (70/50/16oC, III-bieg) Power supply [V/Hz] | Zasilanie [V/Hz] | Max current consumption [A] | Max. pobór prądu [A] Max power consumption [W] | Mak. pobór mocy [W] IP/ Insulation class | IP/Klasa izolacji Acoustic pressure level [dB(A)]** Poziom ciśnienia akustycznego [dB(A)]** Acoustic power level [dB(A)]*** Poziom mocy akustycznej...

 Open the catalog to page 2
CATALOGUE CARD LEO S | L | XL / BMS-3

TECHNICAL DATA I DANE TECHNICZNE LEO L1 I L2 I L3 Max airflow [m /h ] | Max. strumień przepływu powietrza [m /h ] Heating power range | Zakres mocy grzewczej [kW]* Nominal heating power (70/50/16oC, III-speed) | Nominalna moc grzewcza (70/50/16oC, III-bieg) Power supply [V/Hz] | Zasilanie [V/Hz] | Max current consumption [A] | Max. pobór prądu [A] Max power consumption [W] | Mak. pobór mocy [W] IP/ Insulation class | IP/Klasa izolacji Acoustic pressure level [dB(A)] | Poziom ciśnienia akustycznego [dB(A)]** Acoustic power level [dB(A)] | Poziom mocy akustycznej [dB(A)]*** Horizontal range [m]...

 Open the catalog to page 3
CATALOGUE CARD LEO S | L | XL / BMS-4

HEATING CAPACITY I TABELE MOCY GRZEWCZYCH LEO S1 Tp1 V - airflow / przepływ powietrza PT - heat capacity / moc grzewcza Tp1 - inlet air temp. / temperatura powietrza na wlocie do aparatu Tp2 - outlet air temp. / temperatura powietrza na wylocie z aparatu Tw1 - inlet water temp. / temperatura wody na zasilaniu wymiennika Tw2 - outlet water temp. / temperatura wody na powrocie z wymiennika Qw - water flow rate / strumień przepływu wody grzewcz

 Open the catalog to page 4
CATALOGUE CARD LEO S | L | XL / BMS-5

HEATING CAPACITY I TABELE MOCY GRZEWCZYCH LEO L2 Tp1 V - airflow / przepływ powietrza PT - heat capacity / moc grzewcza Tp1 - inlet air temp. / temperatura powietrza na wlocie do aparatu Tp2 - outlet air temp. / temperatura powietrza na wylocie z aparatu Tw1 - inlet water temp. / temperatura wody na zasilaniu wymiennika Tw2 - outlet water temp. / temperatura wody na powrocie z wymiennika Qw - water flow rate / strumień przepływu wody grzewczej Δpw - pressure drop of water / spadek ciśnienia wody w wymienniku For different parameters of the device please use our calculator, scan QR code. Dobierz...

 Open the catalog to page 5
*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.