1. Catalogs
  2. FIVES PILLARD
  3. Pillard NocostopTM
video corpo

Pillard NocostopTM

Pillard NocostopTM

Pillard NocostopTM

Product catalog summary
Overview
Pillard NocostopTM is a state-of-the-art toxic gas detector designed for continuous monitoring of air quality in tunnels and car parks. It ensures user safety by measuring concentrations of carbon monoxide (CO), nitrogen monoxide (NO), and nitrogen dioxide (NO2) using electrochemical cells specific to each gas.
Key Features
  • Continuous Detection: Provides real-time monitoring with a 4/20mA output for electronic microprocessor display.
  • Easy Maintenance: Features a communication console management system and an LCD screen that requires no adjustments.
  • Increased Resistance: Constructed with stainless steel (316L) for durability in extreme environments.
Technical Specifications
  • Material: Stainless Steel 316L
  • Protection: IP65
  • Dimensions/Weight: 210 x 175 x 110mm / 2kg
  • Resolution: CO and NO: 0.1ppm; NO2: 0.05 ppm
  • Accuracy: CO: 2ppm; NO: 0.2ppm; NO2: 0.1ppm
  • Response Time: Less than 30 seconds
  • Lifetime: Over 3 years
  • Temperature Range: -40°C to +65°C
  • Power Supply: 24VDC +10/-15%
  • Power Consumption: 0.7W without heating / 12W with heating
Compliance and Standards
  • Compliant with EN 61000-6-1, EN 61000-6-3, EN60947-1
Additional Features
  • Integrated particle filter and anti-splashing devices
  • Extractive measurement with an adapter for gas circulation
  • Fault alert signal included between 1 and 3mA
  • Compatible with communication console RC3 for analogue output signal
  • Detection inferior limits: CO: 1ppm; NO: 0.5ppm; NO2: 0.2ppm
  • Measuring range: CO: 0-100 to 300ppm; NO: 0-10 to 100ppm; NO2: 0-1 to 10ppm
  • Humidity conditions: 0 to 100% humidity; 700 to 1,300hPa
See more

Catalog excerpts

Pillard NocostopTM-1

Ultimate toxic gas detector for your security • Continuous detection • Easy operation, easy maintenance • Increased resistance • Stainless steel (316L)

 Open the catalog to page 1
Pillard NocostopTM-2

Monitoring air quality in tunnels and car parks is essential to ensure users' safety. Regulations impose limited values and maximum exposure time to toxic gas. Mechanical features CONTINUOUS DETECTION Pillard NocostopTMdetector has been designed to measure continuously the concentration of carbon monoxide (CO), nitrogen monoxide (NO), nitrogen dioxide (NO2). Measure is evaluated by means of electrochemical cell specific to each gas (CO, NO or NO2). Using the 4/20mA output, electronic microprocessor cell displays the measure. Integrated filter system protects the cell from fog and water spray. EASY...