Y600A Series Pressure Reducing Regulators Figure 1. Type Y600A Pressure Reducing Regulator Y600A Series direct-operated, spring-loaded regulators provide economical pressure-reducing control for a variety of residential, commercial, and industrial applications.   •  Precision Control at Low-Pressure Settings— The large diaphragm area provides more accurate control at low-pressure settings. The pitot tube of Types Y600A and Y600AR (Figure 2) regulators also creates a dynamic boost that helps provide greater capacity. The large diaphragm area provides more accurate control at low-pressure settings, and the pitot tube of the Type Y600A or Y600AR regulator also creates a dynamic boost that helps provide greater capacity.   •  Tamper-Resistant Adjustment—The closing cap and spring case (Figure 2) allow the installation of sealing wire to discourage or detect unauthorized adjustment of the pressure setting.   •  Easy to Maintain—Trim parts can be replaced without removing the regulator body from the pipeline. A two-bolt connection between the body and diaphragm casing simplifies disassembly for maintenance. D102575X012 The Type Y600A features internal registration. The Type Y600AR has internal registration and relief. The Type Y600AM uses external registration with a 1/2 NPT downstream control line connection and an O-ring stem seal.   •  Easy Conversion Between Types Y600A and Y600AM—The throat seal can be modified to either version. A new lower casing is not need

Open the catalog to page 1
Y600A Series Pressure Reducing Regulators - 2

Bulletin 71.1:Y600A Specifications Available Configurations See Table 1 Pressure Registration See Table 1 Body Sizes and End Connection Style 3/4 or 1 NPT Maximum Inlet Pressure (Body Rating)(1) 150 psig (10,3 bar) Spring Case Vent Connection 1/4 NPT Outlet Pressure Ranges(1) See Table 2 Diaphragm Case (Control Line) Connection 1/2 NPT Maximum Outlet (Casing) Pressure(1) 20 psig (1,4 bar) Construction Materials See Table 5 Maximum Operating Outlet Pressure to Avoid Internal Parts Damage(1) 2 psig (0,14 bar) above outlet pressure setting Pressure Setting Adjustment Adjusting screw...

Open the catalog to page 2
Y600A Series Pressure Reducing Regulators - 3

Bulletin 71.1:Y600A Table 2. Outlet Pressure Ranges control control spring wire spring free outlet pressure range with spring spring part diameter, length, spring case above color number inches (mm) inches (mm) diaphragm(1) approximate point above pressure setting at which type y600ar internal relief start-to-discharge Light blue   1.  Minimum outlet pressure setting may be approximately 1-inch w.c. (2 mbar) lower if spring case is below diaphragm. Table 3. Maximum Operating Inlet Pressures Maximum operating inlet pressure, psig (bar) Orifice size, inches (mm) 1/8 With 1.2 Psig (0,08 bar)...

Open the catalog to page 3
Y600A Series Pressure Reducing Regulators - 4

control spring umbrella vent pitot tube lever pipe plug Type Y600A with internal pressure registration control spring THROAT SEAL O-RING STEM SEAL UMBRELLA VENT CONTROL LINE CONNECTION Type Y600AM with external pressure registration W7325 inlet pressure outlet pressure atmospheric pressure Figure 2. Y600A Series Operational Schematic

Open the catalog to page 4
Y600A Series Pressure Reducing Regulators - 5

Bulletin 71.1:Y600A relief valve spring valve disk pusher post pipe plug Type Y600AR with internal relief/internal pressure registration inlet pressure outlet pressure atmospheric pressure Figure 2. Y600A Series Operational Schematic (continued) Principle of Operations Refer to Figure 2. When downstream demand decreases, the pressure under the diaphragm increases. This pressure overcomes the regulator setting (which is set by a spring). Through the action of the pusher post assembly, the valve disk moves closer to the orifice and reduces gas flow. If demand downstream increases, pressure...

Open the catalog to page 5
Y600A Series Pressure Reducing Regulators - 6

Bulletin 71.1:Y600A Capacity Information Tables 6 and 7 give the natural gas regulating capacities of Y600A Series regulators at selected inlet pressures and outlet pressure settings. Flows are in SCFH (60°F and 14.7 psia) of 0.6 specific gravity gas. To determine equivalent capacities for air, propane, butane, or nitrogen, multiply the Table 6 or 7 capacity by the following appropriate conversion factor: 0.775 for air, 0.628 for propane, 0.548 for butane, or 0.789 for nitrogen. For gases of other specific gravities, multiply the given capacity by 0.775, and divide by the square root of the...

Open the catalog to page 6
Y600A Series Pressure Reducing Regulators - 7

Bulletin 71.1:Y600A Table 6. Y600A Series Capacities for 3/4 NPT Body Size (continued) OUTLET PRESSURE RANGE, CONTROL SPRING PART NUMBER, AND COLOR 3/4 NPT BODY SIZE OFFSET FROM SETPOINT OUTLET PRESSURE SETTING INLET PRESSURE, PSIG (bar) Capacities in SCFH (Nm3/h) of 0.6 Specific Gravity Natural Gas Orifice Size, Inches (mm) 1/8 (3,2) 1.2 to 2.5 psig (83 to 172 mbar) 1B537127022 Green 0.7 psig (48 mbar) 7 psig (483 mbar) - Shaded areas indicate where maximum operating inlet pressure for a given orifice size is exceeded.

Open the catalog to page 7
Y600A Series Pressure Reducing Regulators - 8

Bulletin 71.1:Y600A Table 7. Y600A Series Capacities for 1 NPT Body Size OUTLET PRESSURE RANGE, CONTROL SPRING PART NUMBER, AND COLOR 1 NPT BODY SIZE OFFSET FROM SETPOINT OUTLET PRESSURE SETTING INLET PRESSURE, PSIG (bar) Capacities in SCFH (Nm3/h) of 0.6 Specific Gravity Natural Gas Orifice Size, Inches (mm) 1/8 (3,2) 15-inches w.c. (37 mbar) 15-inches w.c. to 1.2 psig (37 mbar to 83 mbar) 1B537027052 Yellow 1. Indicates capacity limited due to boost. - Shaded areas indicate where maximum operating inlet pressure for a given orifice size is exceeded.

Open the catalog to page 8
Y600A Series Pressure Reducing Regulators - 9

Bulletin 71.1:Y600A Table 7. Y600A Series Capacities for 1 NPT Body Size (continued) OUTLET PRESSURE RANGE, CONTROL SPRING PART NUMBER, AND COLOR 1 NPT BODY SIZE OFFSET FROM SETPOINT OUTLET PRESSURE SETTING INLET PRESSURE, PSIG (bar) Capacities in SCFH (Nm3/h) of 0.6 Specific Gravity Natural Gas Orifice Size, Inches (mm) 1/8 (3,2) 1.2 to 2.5 psig (83 to 172 mbar) 1B537127022 Green 2.5 to 4.5 psig (172 to 310 mbar) 1B537227022 Light blue 0.7 psig (48 mbar) 7 psig (483 mbar) - Shaded areas indicate where maximum operating inlet pressure for a given orifice size is exceeded.

Open the catalog to page 9
Y600A Series Pressure Reducing Regulators - 10

1/4 NPT VENT CONNECTION WITH REMOVABLE VENT 1/2 NPT CONTROL LINE CONNECTION ON TYPE Y600AM DIMENSION, INCHES (mm) BODY SIZE 3/4 and 1 APPROXIMATE SHIPPING WEIGHT, POUNDS (kg) Ordering Information When ordering, specify: Application   1.  Type of regulator   2.  Body, spring case, diaphragm case, and     trim materials   3.  Control spring range in psig (bar) Construction Refer to the Specifications section on page 2 and to each referenced table. Specify the desired selection whenever there is a choice to be made. Always be sure to specify the regulat

Open the catalog to page 10