Introduction
The 627 Series direct-operated pressure reducing regulators are versatile devices suitable for both low and high-pressure systems, compatible with natural gas, air, and other gases. Their performance is contingent on their construction.
Features
  • Internal Relief Valve: Types 627R, 627LR, and 627MR feature an internal relief valve, often negating the need for an external one, thus reducing costs.
  • Travel Stop: Ensures functionality of the internal relief valve even if the disk or linkage fails.
  • Relief Operation Indicator: A rubber cap on the vent assembly signals when the relief valve is activated.
  • Maintenance: Trim parts can be replaced without detaching the regulator body from the pipeline.
  • Installation Adaptability: The diaphragm case and/or regulator body can be rotated for installation in confined spaces.
  • Application Versatility: Suitable for various applications, including farm tap and high-pressure industrial regulators.
  • Tamper-Resistant: Features an adjusting screw locknut and protective cap.
  • Flow Capabilities: Available in various body and orifice sizes to meet different flow requirements.
  • Tight Shutoff Capability: Utilizes materials like Nitrile, Nylon, or Fluorocarbon for effective shut-off.
Specifications
  • Maximum Pressures: Varies by material and construction, with specific limits for steel, ductile iron, and stainless steel.
  • Orifice Sizes: Detailed in Table 2.
  • Internal Relief Performance: Specific to each type, with details in Tables 4 and 5.
  • Construction Materials: Includes ductile iron, WCC steel, stainless steel, and aluminum for various components.
Principle of Operation
The regulator adjusts gas flow based on downstream demand, using a diaphragm and spring mechanism to maintain pressure settings.
Product Description
  • Types 627 and 627H: Provide economical pressure control for various applications.
  • Type 627 Long Body: Can replace Type 630 installations without piping modifications.
  • Internal Relief: Provides overpressure protection by allowing excess pressure to bleed out.
  • Downstream Control Line: Used for monitoring applications, separating body outlet pressure from the diaphragm case.
Installation and Maintenance
Regulators should be inspected periodically for damage and to ensure temperature capabilities are not exceeded. Internal relief may provide adequate overpressure protection in many cases.
Overpressure Protection
Types 627R and 627LR provide internal relief to limit outlet pressure build-up. Users must ensure additional protection if inlet pressure can exceed outlet pressure ratings.
Figures and Tables
Figures 2-5 illustrate operational schematics for different types, while Tables 1-2 provide detailed specifications on maximum pressures and orifice sizes.
Contact Information
Contact details for TESCOM regional offices in Singapore, Italy, France, USA, Germany, and China are provided, including telephone numbers for inquiries.
Specification Worksheet
This section outlines the necessary information for specifying a gas regulator application, including application type, line size, gas type and specific gravity, gas temperature, and overpressure protection needs. Options for overpressure protection include a relief valve, monitor regulator, or shutoff device, with assistance available for selecting equipment.
Pressure Specifications
The worksheet requires details on maximum and minimum inlet pressures, downstream pressure settings, and maximum flow requirements, as well as performance requirements such as accuracy and response speed.
Regulators Quick Order Guide
Products are categorized based on their availability for shipment. Some are readily available, others require additional time, and special orders are constructed from non-stocked parts, requiring consultation with a local sales office. The availability of a product is determined by the component with the longest shipping time.
See more

Catalog excerpts

627 Series Pressure Reducing Regulators-1

627 Series Pressure Reducing Regulators Introduction The 627 Series direct-operated pressure reducing regulators (Figure 1) are for low and high-pressure systems. These regulators can be used with natural gas, air, or a variety of other gases. Performance characteristics vary according to construction (see the Specifications section). Features • Internal Relief Valve—Types 627R, 627LR, and 627MR regulators have an internal relief valve, which in many cases eliminates the usual requirement for an external relief valve, thereby reducing equipment and maintenance costs. Refer to the Specifications section for performance data. • Types 627R, 627LR, and 627MR Travel Stop— The internal relief valve still works if the disk or linkage fails. The pusher post (Figure 6) contacts the travel stop of the lever retainer and, as the diaphragm continues to rise, it opens the relief valve. • Relief Operation Indicator—A rubber cap (Figure 7) slipped on the vent assembly pops off when the relief valve opens, indicating the relief valve has opened since the last inspection. • Easy to Maintain—Trim parts can be replaced without removing the regulator body from the pipeline. A two-bolt connection between the body and diaphragm casing simplifies disassembly for maintenance. • Installation Adaptability—The diaphragm case and/ or regulator body can be rotated in any of four positions to allow regulator installation in locations with limited space (Figure 8). The regulator may be installed in any position without affecting operation as long as the spring case vent is protected from the elements. Figure 1.  Typical 627 Direct-Operated Pressure Reducing Regulator • Extended Body Option—The Type 627 Long Body is available with same face-to-face dimensions as the Type 630 with threaded NPT end connections. • Tamper-Resistant—An adjusting screw locknut and protective cap (Figure 2) is standard on all 627 Series regulators to discourage tampering with the pressure setting. • Wide Range of Flow Capabilities—A selection of body sizes and orifice sizes is available to satisfy various flow requirements. • Tight Shutoff Capability—A flat-faced disk of Nitrile (NBR), Nylon (PA), or Fluorocarbon (FKM) provides excellent shut-off capability. • Application Versatility—The different 627 Series constructions can be used as farm tap regulators, regulator-relief valves, monitoring regulators, or high-pressure industrial regulators.

 Open the catalog to page 1
627 Series Pressure Reducing Regulators-2

Bulletin 71.1:627 Specifications The Specifications section gives some general specifications for the 627 Series regulators. The nameplates give detailed information for a particular regulator as it comes from the factory. Available Constructions Type 627: Direct-operated pressure reducing regulator equipped with a pitot tube for greater regulated capacities (Figure 2). Type 627R: Type 627 with internal relief and open throat (Figure 3). Type 627LR: Type 627R with light rate relief spring (Figure 3). Type 627M: Type 627 with a stem seal between the body outlet pressure and diaphragm case. Pressure...

 Open the catalog to page 2
627 Series Pressure Reducing Regulators-3

Bulletin 71.1:627 Specifications (continued) Relief Indicator For Types 627R, 627LR, and 627MR (see Figure 7) Elastomer Temperature Capabilities(1)(3) MATERIAL Nitrile (NBR) Fluorocarbon (FKM) DISK/ DIAPHRAGM Disk Dipahragm Disk Diaphragm Neoprene (CR) for Types 627H and 627HM only Pressure Registration Type 627, 627H, 627R, or 627LR: Internal Type 627M, 627HM, or 627MR: External through 1/4 NPT internal control line connection in the diaphragm casing De-Icer System See Figure 10 and Type 627M De-Icer System Application section Spring Case Orientation and Vent Location See Figure 8 Spring Case...

 Open the catalog to page 3
627 Series Pressure Reducing Regulators-4

Bulletin 71.1:627 ADJUSTING SCREW CAP LOCKNUT ADJUSTING SCREW 1/4 NPT CONTROL LINE CONNECTION SPRING CASE CONTROL SPRING PITOT TUBE SCREENED VENT ASSEMBLY INLET PRESSURE OUTLET PRESSURE ATMOSPHERIC PRESSURE BLOCKING THROAT STEM SEAL ORIFICE PUSHER POST DIAPHRAGM CASING DISK ASSEMBLY Figure 2.  Types 627 and 627M Operational Schematics Month Year Type 627R Schematic Closed RELIEF VALVE SPRING LARGE OPENING FOR RELIEF INTERNAL RELIEF VALVE PUSHER POST LEVER RETAINER INLET PRESSURE W4681-2 OUTLET PRESSURE ATMOSPHERIC PRESSURE LET PRESSURE W4679-2 TLET PRESSURE MOSPHERIC PRESSURE INTERNAL RELIEF...

 Open the catalog to page 4
627 Series Pressure Reducing Regulators-5

Month Year Month Year 1/4 NPT CONTROL LINE CONNECTION W4682-2 INLET PRESSURE OUTLET PRESSURE ATMOSPHERIC PRESSURE RESSURE T PRESSURE PHERIC PRESSURE INTERNAL RELIEF VALVE INTERNAL RELIEF FLOW PATH BLOCKING THROAT STEM SEAL Figure 4.  Type 627MR Operational Schematics Type XXXX Month Year BLOCKING THROAT STEM SEAL ADJUSTING SCREW CAP ADJUSTING SCREW SPRING CASE 1/4 NPT CONTROL LINE CONNECTION CONTROL SPRING SCREENED VENT ASSEMBLY DIAPHRAGM LIMITER DIAPHRAGM HEAD INLET PRESSURE OUTLET PRESSURE ATMOSPHERIC PRESSURE DIAPHRAGM LIMITER O-RING PUSHER POST O-RINGS PITOT TUBE INLET PRESSURE CASING OUTLET...

 Open the catalog to page 5
627 Series Pressure Reducing Regulators-6

LEVER RETAINER PUSHER POST TRAVEL STOP Figure 6.  Internal Relief Construction Feature Figure 7.  Relief Indicator Table 1.  Maximum Cold Working Pressure of Body Inlet (Body Rating)(1)(2) NPS BODY SIZE BODY MATERIAL Ductile iron Steel Stainless Steel Ductile iron Stainless Steel 1. The pressure/temperature limits in this Bulletin, and any applicable standard or code should not be exceeded. 2. Temperature may decrease these maximum pressures. Note If the regulator is shipped mounted on another unit, install that unit according to the appropriate Instruction manual. Overpressure Protection 627...

 Open the catalog to page 6
627 Series Pressure Reducing Regulators-7

Bulletin 71.1:627 Table 2.  Maximum Inlet Pressures and Outlet Pressure Ranges TYPE OUTLET PRESSURE RANGE, SPRING PART NUMBER, AND COLOR CODE 5(2) to 20 psig / 0.34 to 1.4 bar 10B3076X012 Yellow 15 to 40 psig / 1.0 to 2.8 bar 10B3077X012 Green 35 to 80 psig / 2.4 to 5.5 bar 10B3078X012 Blue 70 to 150 psig / 4.8 to 10.3 bar 10B3079X012 Red 5(2) to 20 psig / 0.34 to 1.4 bar 10B3076X012 Yellow 15 to 40 psig / 1.0 to 2.8 bar 10B3077X012 Green 35 to 80 psig / 2.4 to 5.5 bar 10B3078X012 Blue 70 to 150 psig / 4.8 to 10.3 bar 10B3079X012 Red 15 to 40 psig / 1.0 to 2.8 bar 10B3077X012 Green 140 to 250...

 Open the catalog to page 7

All FISHER REGULATORS catalogs and technical brochures

  1. R Series

    2  Pages

  2. LP-31

    96  Pages

  3. CS 200 series

    2  Pages

  4. 1301F, 1301G

    12  Pages

  5. MR95 and MR98

    2  Pages

  6. 630 Regulator

    16  Pages

  7. S200 series

    32  Pages

  8. R622 series

    8  Pages

  9. cs200 series

    40  Pages

  10. CS400 Series

    60  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.