Product catalog summary
Prime and Standby Ratings: The document outlines two types of ratings for the generator set: Prime Rating and Standby Rating. Prime Rating is for continuous power supply at variable loads without annual hour limitations, allowing a 10% overload for 1 hour in 12 hours. Standby Rating is for power supply during utility failures, with no overload permitted, and the alternator is peak continuous rated as per ISO 8528-3.
Standard Reference Conditions: The generator's performance is based on standard conditions of 25°C air inlet temperature, 100m altitude, and 30% relative humidity. Fuel consumption is measured using diesel fuel with specific gravity of 0.85, conforming to BS2869: 1998, Class A2.
Output Ratings and Performance Data: The generator set is equipped with a Leroy Somer alternator, a Perkins®1104C-44TAG2 engine, and various control and circuit breaker options. It operates at different voltages and frequencies, with specific fuel consumption rates at various loads.
Dimensions and Weights: The document provides detailed dimensions and weights for both dry and wet conditions, indicating the inclusion of lube oil and coolant.
Available Options: FG Wilson offers optional features such as CE Certification upgrades, sound attenuated enclosures, control panels, additional alarms, and exhaust silencer noise levels.
Exhaust and Lubrication Systems: Details on the exhaust system include silencer types, noise reduction levels, and exhaust gas flow. The lubrication system specifies oil filter types, capacities, and cooling methods.
Cooling System: The cooling system is designed for ambient conditions up to 50°C, with specifications on water pump types, heat rejection, and radiator fan load.
Engine Technical Data: The engine is a 4-cylinder, in-line, 4-stroke, turbocharged model with specific bore/stroke measurements and performance metrics like gross engine power and BMEP.
Fuel System: The generator uses Class A2 Diesel or BSEN590 fuel, with detailed fuel consumption rates at different loads and frequencies.
Alternator Physical and Performance Data: The alternator is manufactured by Leroy Somer, with specifications on bearings, insulation class, excitation system, and voltage regulation. Performance data includes motor starting capability and short circuit capacity.
Standards and Warranty: The generator set complies with standards such as BS5000, ISO 8528, ISO 3046, IEC 60034, and NEMA MG-1.22. FG Wilson provides a one-year warranty for prime equipment and a two-year warranty for standby equipment, limited to 500 running hours per year.
See more

Catalog excerpts

P80-3S (80 kVA Single Phase Open Generator Set)-1

P80-3S Image for illustration purposes only. Output Ratings Ratings and Performance Data Prime Ratings at 1.0 power factor. Please refer to the output ratings technical data section for specific generator set outputs per voltage. Prime Rating These ratings are applicable for supplying continuous electrical power (at variable load) in lieu of commercially purchased power. There is no limitation to the annual hours of operation and this model can supply 10% overload power for 1 hour in 12 hours. Standby Rating These ratings are applicable for supplying continuous electrical power (at variable load) in the event of a utility power failure. No overload is permitted on these ratings. The alternator on this model is peak continuous rated (as defined in ISO 8528-3). Standard Reference Conditions Note: Standard reference conditions 25°C (77°F) Air Inlet Temp, 100m (328 ft) A.S.L. 30% relative humidity. Fuel consumption data at full load with diesel fuel with specific gravity of 0.85 and conforming to BS2869: 1998, Class A2. Engine Make & Model: Alternator manufactured for FG Wilson by: Leroy Somer Alternator Model: Control Panel: Base Frame: Heavy Duty Fabricated Steel Circuit Breaker Type: Voltage, Frequency Fuel Tank Capacity: Fuel Consumption: l/hr (US gal/hr) - Prime Available Options FG Wilson offer a range of optional features to tailor our generator sets to meet your power needs. Options include: Upgrade to CE Certification A wide range of Sound Attenuated Enclosures A variety of generator set control and synchronising panels Additional alarms and shutdowns A selection of exhaust silencer noise levels For further information on all of the standard and optional features accompanying this product please contact your local Dealer or visit: www.FGWilson.com Dimensions and Weights Length (L) Wet = With Lube Oil and Coolant Ratings in accordance with ISO 8528, ISO 3046, IEC 60034, BS5000 and NEMA MG-1.22. Generator set pictured may include optional accessories.

 Open the catalog to page 1
P80-3S (80 kVA Single Phase Open Generator Set)-2

Engine Technical Data Replaceable Element Combustion Air Flow: m³/min (cfm) Bore / Stroke: mm (in) Induction: Turbocharged Air To Air Charge Cooled Cooling Method: Governing Type: Governing Class: Max. Combustion Air Intake Restriction: kPa (in H2O) Compression Ratio: Cooling System Moment of Inertia: kg m² (lb/in²) Cooling System Capacity: l (US gal) Water Pump Type: Engine Electrical System: - Voltage / Ground - Battery Charger Amps Weight: kg (lb) Heat Rejected to Water & Lube Oil: Heat Radiation to Room: Heat radiated from engine and alternator kW (Btu/min) Radiator Fan Load: kW (hp) Performance...

 Open the catalog to page 2
P80-3S (80 kVA Single Phase Open Generator Set)-3

Alternator Physical Data Alternator Operating Data Insulation Class: Winding Pitch Code: Ingress Protection Rating: Excitation System: Leroy Somer Voltage Regulation: (Steady state) Wave Form NEMA = TIF: Total Harmonic content LL/LN: Radio Interference: Radiant Heat: kW(Btu/min) Suppression is in line with European Performance Data: Data Item Motor Starting Short Circuit Reactances shown are applicable to prime ratings. *Based on 30% voltage dip at 0.6 power factor . **With optional permanent magnet generator.

 Open the catalog to page 3
P80-3S (80 kVA Single Phase Open Generator Set)-4

General Information Documentation A full set of operation and maintenance manuals and circuit wiring diagrams. Generator Set Standards The equipment meets the following standards: BS5000, ISO 8528, ISO 3046, IEC 60034, NEMA MG-1.22. FG Wilson is a fully accredited ISO 9001 company. EU stage II emissions compliant. Warranty All prime equipment carries a one year manufacturer's warranty. Standby equipment, limited to 500 running hours per year, has a two year manufacturer's warranty. For details on warranty cover please contact your local Dealer, or visit our website: FGWilson.com. Dealer contact...

 Open the catalog to page 4

All FG WILSON catalogs and technical brochures

  1. P2250-3M

    6  Pages

  2. P7.5-4S

    6  Pages

Archived catalogs

  1. Rental Range

    7  Pages

  2. PG345B3

    4  Pages

  3. PG375B3

    4  Pages

  4. PG1250B2

    4  Pages

  5. PG450B1

    4  Pages

  6. PG525B1

    4  Pages

  7. P7.5-4S

    4  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.