1. Catalogs
  2. FG WILSON
  3. P688-1 (625-688 kVA) Open Generator Set
video corpo

P688-1 (625-688 kVA) Open Generator Set

P688-1 (625-688 kVA) Open Generator Set

P688-1 (625-688 kVA) Open Generator Set

Product catalog summary
Prime Rating: This rating is for continuous electrical power supply at variable load, replacing commercially purchased power. It allows for 10% overload for 1 hour in every 12 hours without annual operation limits.
Standby Rating: Used for continuous power supply during utility failures, with no overload permitted. The alternator is peak continuous rated as per ISO 8528-3.
Standard Reference Conditions: Conditions include 25°C air inlet temperature, 100m above sea level, and 30% relative humidity.
Output Ratings and Performance Data: The generating set model includes specifications for prime and standby power, engine make and model, alternator details, control panel, circuit breaker type, engine speed, and base frame. Dimensions and weights are provided for both dry and wet conditions.
Fuel Consumption: Data is provided for 100% load at prime and standby ratings.
Available Options: FG Wilson offers various optional features such as sound attenuated enclosures, control panels, alarms, shutdowns, and exhaust silencers.
Engine Specifications: Details include the engine model, speed, power, bore/stroke, induction type, and fuel system. Lubrication and cooling systems are also described.
Alternator Specifications: Information on the alternator model, insulation class, winding pitch, excitation system, and voltage regulation is provided.
General Information: FG Wilson manufactures in multiple locations and operates through a global dealer network. Specifications are subject to change without notice.
See more

Catalog excerpts

P688-1 (625-688 kVA) Open Generator Set-1

Output Ratings Ratings at 0.8 power factor. Prime Rating These ratings are applicable for supplying continuous electrical power (at variable load) in lieu of commercially purchased power. There is no limitation to the annual hours of operation and this model can supply 10% overload power for 1 hour in 12 hours. Standby Rating These ratings are applicable for supplying continuous electrical power (at variable load) in the event of a utility power failure. No overload is permitted on these ratings. The alternator on this model is peak, continuous rated (as defined in ISO 8528-3). Standard Reference Conditions Note: Standard reference conditions 25°C (77°F) Air Inlet Temp, 100m Fuel consumption data at full load with diesel fuel with specific gravity of Ratings and Performance Data Engine Make & Model: Alternator Model: Control Panel: Base Frame: Circuit Breaker Type: Fuel Tank Capacity: Fuel Consumption: l/hr (US gal/hr) Image for illustration purposes only. Leroy Somer Heavy Duty Fabricated Steel Available Options FG Wilson offer a range of optional features to tailor our generating sets to meet your power needs. Options include: • A wide range of Sound Attenuated Enclosures • A variety of generating set control and synchronising panels • Additional alarms and shutdowns • A selection of exhaust silencer noise levels For further information on all of the standard and optional features accompanying this product please contact your local Dealer or visit: Dry = With Lube Oil Wet = With Lube Oil and Coolant Ratings in accordance with ISO 8528, ISO 3046, IEC 60034, BS5000 and NEMA MG-122. Generating set pictured may include optional accessories.

 Open the catalog to page 1
P688-1 (625-688 kVA) Open Generator Set-2

Engine Technical Data Cooling Method: Governing Type: Governing Class: Compression Ratio: Engine Electrical System: - Voltage / Ground - Battery Charger Amps Gross Engine Power: kW(hp) Fuel System Fuel Filter Type: Recommended Fuel: Fuel Consumption: l/hr (US gal/hr) Charge Cooled (Based on diesel fuel with a specific gravity of 0.85 and conforming to BS2869, Cooling System Cooling System Capacity: I (US gal) Water Pump Type: Heat Rejected to Water & Lube Oil: Heat Radiation to Room: Heat radiated from engine and alternator Radiator Fan Load: kW(hp) Radiator Cooling Airflow: m3/min (dm) Designed...

 Open the catalog to page 2
P688-1 (625-688 kVA) Open Generator Set-3

Alternator Physical Data Alternator Operating Data Insulation Class: Winding Pitch Code: Ingress Protection Rating: Excitation System: Leroy Somer Voltage Reguation: (Steady state) Wave Form NEMA = TIF: Total Harmonic content LL/LN: Radio Interference: Radiant Heat: kW(Btu/min) Suppression is in line with European Performance Data: Data Item Motor Starting Short Circuit Reactances shown are applicable to prime ratings. *Based on 30% voltage dip at 0.6 power factor and AREP excitation system. **With optional permanent magnet generator or AREP excitation.

 Open the catalog to page 3
P688-1 (625-688 kVA) Open Generator Set-4

General Information A full set of operation and maintenance manuals and circuit wiring diagrams. The equipment meets the following standards: BS5000, ISO 8528, ISO 3046, IEC 60034, NEMA MG-1.22. FG Wilson is a fully accredited ISO 9001 company. All prime equipment carries a one year manufacturer's warranty. Standby equipment, limited to 500 running hours per year, has a two year manufacturer's warranty. For details on warranty cover please contact your local Dealer, or visit our website: FGWilson.com. Dealer contact details: FG Wilson manufactures product in the following locations: Northern...

 Open the catalog to page 4

All FG WILSON catalogs and technical brochures

  1. P2250-3M

    6  Pages

  2. P7.5-4S

    6  Pages

Archived catalogs

  1. Rental Range

    7  Pages

  2. PG345B3

    4  Pages

  3. PG375B3

    4  Pages

  4. PG1250B2

    4  Pages

  5. PG450B1

    4  Pages

  6. PG525B1

    4  Pages

  7. P7.5-4S

    4  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.