1. Catalogs
  2. FG WILSON
  3. P501-1 Generator Set (501 kVA)
video corpo

P501-1 Generator Set (501 kVA)

P501-1 Generator Set (501 kVA)

P501-1 Generator Set (501 kVA)

Product catalog summary
Prime Rating: This rating is for continuous electrical power supply at variable load, replacing commercially purchased power. It allows for 10% overload for 1 hour in every 12 hours without annual operation limits.
Standby Rating: Used for continuous power supply during utility failures, with no overload permitted. The alternator is peak continuous rated as per ISO 8528-3.
Standard Reference Conditions: Conditions include 25°C air inlet temperature, 100m altitude, and 30% relative humidity. Fuel consumption is based on diesel fuel with specific gravity of 0.85, conforming to BS2869: 1998, Class A2.
Output Ratings and Performance Data: The generator set is manufactured by FG Wilson with a Leroy Somer alternator. It operates at 480V, 60 Hz, with a power factor of 0.8. The engine model is Perkins® 2206A-E13TAG6, with a control panel model P501-1 and a 3 Pole MCCB circuit breaker.
Dimensions and Weights: The generator set measures 3800mm in length, 1131mm in width, and 2156mm in height. Dry weight is 3183 kg, and wet weight is 3241 kg.
Fuel Consumption: At 100% load, fuel consumption is specified for both prime and standby ratings.
Available Options: Options include CE certification, sound attenuated enclosures, control and synchronizing panels, additional alarms, and various exhaust silencer noise levels.
Exhaust System: Details include silencer type, model, pressure drop, noise reduction level, and exhaust gas flow and temperature.
Lubrication and Cooling Systems: The lubrication system includes an oil filter and total oil capacity, while the cooling system details include capacity, water pump type, and heat rejection data.
Engine Technical Data: The engine is a 6-cylinder, in-line, 4-stroke with turbocharged air to air charge cooling. It operates at 1800 rpm with a compression ratio of 16.3:1.
Alternator Physical Data: Manufactured by Leroy Somer, the alternator has an insulation class H, IP23 ingress protection, and operates with a SHUNT excitation system.
Generating Set Standards: The equipment complies with BS5000, ISO 8528, ISO 3046, IEC 60034, and NEMA MG-1.22 standards. FG Wilson is ISO 9001 accredited.
Warranty: Prime equipment has a one-year warranty, while standby equipment has a two-year warranty limited to 500 running hours per year.
General Information: FG Wilson manufactures in multiple locations globally and operates through a global dealer network. Specifications are subject to change without notice.
See more

Catalog excerpts

P501-1 Generator Set (501 kVA)-1

P501-1 Image for illustration purposes only. Output Ratings Ratings and Performance Data Ratings at 0.8 power factor. Please refer to the output ratings technical data section for specific generator set outputs per voltage. Prime Rating These ratings are applicable for supplying continuous electrical power (at variable load) in lieu of commercially purchased power. There is no limitation to the annual hours of operation and this model can supply 10% overload power for 1 hour in 12 hours. Standby Rating These ratings are applicable for supplying continuous electrical power (at variable load) in the event of a utility power failure. No overload is permitted on these ratings. The alternator on this model is peak continuous rated (as defined in ISO 8528-3). Standard Reference Conditions Note: Standard reference conditions 25°C (77°F) Air Inlet Temp, 100m (328 ft) A.S.L. 30% relative humidity. Fuel consumption data at full load with diesel fuel with specific gravity of 0.85 and conforming to BS2869: 1998, Class A2. Engine Make & Model: Alternator manufactured for FG Wilson by: Leroy Somer Alternator Model: Control Panel: Base Frame: Heavy Duty Fabricated Steel Circuit Breaker Type: Voltage, Frequency Engine Speed: RPM Fuel Tank Capacity: Fuel Consumption: l/hr (US gal/hr) - Prime Available Options FG Wilson offer a range of optional features to tailor our generating sets to meet your power needs. Options include: Upgrade to CE Certification A wide range of Sound Attenuated Enclosures A variety of generating set control and synchronising panels Additional alarms and shutdowns A selection of exhaust silencer noise levels For further information on all of the standard and optional features accompanying this product please contact your local Dealer or visit: www.FGWilson.com Dimensions and Weights Length (L) Wet = With Lube Oil and Coolant Ratings in accordance with ISO 8528, ISO 3046, IEC 60034, BS5000 and NEMA MG-1.22. Generating set pictured may include optional accessories.

 Open the catalog to page 1
P501-1 Generator Set (501 kVA)-2

Engine Technical Data Combustion Air Flow: m³/min (cfm) Bore / Stroke: mm (in) Induction: Turbocharged Air To Air Charge Cooled Cooling Method: Governing Type: Governing Class: Max. Combustion Air Intake Restriction: kPa (in H2O) Compression Ratio: Cooling System Moment of Inertia: kg m² (lb/in²) Cooling System Capacity: l (US gal) Water Pump Type: Engine Electrical System: - Voltage / Ground - Battery Charger Amps Weight: kg (lb) Heat Rejected to Water & Lube Oil: - Prime Heat Radiation to Room: Heat radiated from engine and alternator - Prime Radiator Cooling Airflow: m³/min (cfm) External...

 Open the catalog to page 2
P501-1 Generator Set (501 kVA)-3

Alternator Physical Data Alternator Operating Data Leroy Somer Voltage Reguation: (Steady state) Wave Form NEMA = TIF: No. of Bearings: Insulation Class: Winding Pitch Code: Total Harmonic content LL/LN: Ingress Protection Rating: Radio Interference: Suppression is in line with European Standard EN61000-6 Radiant Heat: kW (Btu/min) Excitation System: Alternator Performance Data: Data Item Motor Starting Capability* kVA Short Circuit Capacity** % Reactances: Per Unit Reactances shown are applicable to prime ratings. *Based on 30% voltage dip at 0.6 power factor and SHUNT excitation. **With optional...

 Open the catalog to page 3
P501-1 Generator Set (501 kVA)-4

General Information A full set of operation and maintenance manuals and circuit wiring diagrams. The equipment meets the following standards: BS5000, ISO 8528, ISO 3046, IEC 60034, NEMA MG-1.22. FG Wilson is a fully accredited ISO 9001 company. All prime equipment carries a one year manufacturer's warranty. Standby equipment, limited to 500 running hours per year, has a two year manufacturer's warranty. For details on warranty cover please contact your local Dealer, or visit our website: FGWilson.com. Dealer contact details: FG Wilson manufactures product in the following locations: Northern...

 Open the catalog to page 4

All FG WILSON catalogs and technical brochures

  1. P2250-3M

    6  Pages

  2. P7.5-4S

    6  Pages

Archived catalogs

  1. Rental Range

    7  Pages

  2. PG345B3

    4  Pages

  3. PG375B3

    4  Pages

  4. PG1250B2

    4  Pages

  5. PG450B1

    4  Pages

  6. PG525B1

    4  Pages

  7. P7.5-4S

    4  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.