Prime and Standby Ratings: The document outlines two types of ratings for the generating sets: Prime Rating and Standby Rating. Prime Rating is for continuous power supply at variable loads without annual hour limitations, allowing a 10% overload for 1 hour in 12 hours. Standby Rating is for power supply during utility failures, with no overload permitted, and the alternator is peak continuous rated as per ISO 8528-3.
Standard Reference Conditions: The standard conditions are set at 25°C air inlet temperature, 100m above sea level, and 30% relative humidity. Fuel consumption data is based on diesel fuel with specific gravity of 0.85, conforming to BS2869: 1998, Class A2.
Manufacturing and Contact Information: FG Wilson has manufacturing facilities in Northern Ireland, Brazil, China, India, and the USA, with headquarters in Northern Ireland. A global dealer network is available for contact through their website.
Output Ratings and Performance Data: The document provides detailed specifications for the generating set model, including engine make and model, alternator details, control panel, circuit breaker type, engine speed, and dimensions. It also includes fuel tank capacity and weight details.
Available Options: FG Wilson offers optional features such as CE Certification upgrades, sound attenuated enclosures, control and synchronizing panels, additional alarms, and various exhaust silencer noise levels.
Technical Specifications: Detailed technical data is provided for the exhaust system, lubrication system, cooling system, engine performance, fuel system, and alternator physical data. This includes information on oil capacity, cooling methods, engine power, fuel consumption, and alternator performance.
Standards and Warranty: The generating sets comply with standards such as BS5000, ISO 8528, ISO 3046, IEC 60034, and NEMA MG-1.22. FG Wilson is ISO 9001 accredited. Prime equipment has a one-year warranty, while standby equipment has a two-year warranty limited to 500 running hours per year.
See more

Catalog excerpts

P2000- P2200E Open Generator Set-1

www.FGWilson.com P2000/P2200E Image for illustration purposes only. Output Ratings Ratings and Performance Data Generating Set Model Standby* - / - - / - Ratings at 0.8 power factor. Prime Rating These ratings are applicable for supplying continuous electrical power (at variable load) in lieu of commercially purchased power. There is no limitation to the annual hours of operation and this model can supply 10% overload power for 1 hour in 12 hours. Standby Rating These ratings are applicable for supplying continuous electrical power (at variable load) in the event of a utility power failure. No overload is permitted on these ratings. The alternator on this model is peak continuous rated (as defined in ISO 8528-3). Standard Reference Conditions Note: Standard reference conditions 25°C (77°F) Air Inlet Temp, 100m (328 ft) A.S.L. 30% relative humidity. Fuel consumption data at full load with diesel fuel with specific gravity of 0.85 and conforming to BS2869: 1998, Class A2. Perkins 4016TAG2A Alternator manufactured for FG Wilson by: Leroy Somer Alternator Model: LL9124H Control Panel: PowerWizard 1.1+ Heavy Duty Fabricated Steel Circuit Breaker Type: 2000.0 kVA / 1600.0 kW 2200.0 kVA / 1760.0 kW Engine Make & Model: Base Frame: 380-415V,50Hz Prime* 3 Pole ACB Frequency: 50 Hz 60 Hz Engine Speed: RPM 1500 - Fuel Tank Capacity: - litres (US gal) Fuel Consumption: l/hr (US gal/hr) - Prime 423.5 (111.9) - - Standby 474.1 (125.2) - (100% Load) Available Options FG Wilson offer a range of optional features to tailor our generating sets to meet your power needs. Options include: Upgrade to CE Certification A wide range of Sound Attenuated Enclosures A variety of generating set control and synchronising panels Additional alarms and shutdowns A selection of exhaust silencer noise levels For further information on all of the standard and optional features accompanying this product please contact your local Dealer or visit: www.FGWilson.com Dimensions and Weights Length (L) Width (W) Height (H) Dry Wet mm (in) mm (in) mm (in) kg (lb) kg (lb) 5749 (226.3) 2300 (90.6) 3020 (118.9) 15495 (3416115695 (34602 Dry = With Lube Oil Wet = With Lube Oil and Coolant Ratings in accordance with ISO 8528, ISO 3046, IEC 60034, BS5000 and NEMA MG-1/22. Generating set pictured may include optional accessories. FG Wilson has manufacturing facilities in the following locations: Northern Ireland • Brazil • China • India • USA With headquarters in Northern Ireland, FG Wilson operates through a Global Dealer Network. To contact your local Sales Office please visit the FG Wilson website at www.FGWilson.com

 Open the catalog to page 1
P2000- P2200E Open Generator Set-2

Engine Technical Data 50 Hz Air Systems No. of Cylinders / Alignment: 16 / Vee 4 Stroke Cycle: Air Filter Type: 60 Hz Combustion Air Flow: m³/min (cfm) Bore / Stroke: mm (in) Turbocharged Air To Air Charge Cooled - Prime 137.0 (4838) - - Standby 145.0 (5121) - 160.0 (6.3)/190.0 (7.5) Induction: Replaceable Element Cooling Method: Water Governing Type: 3.7 (14.9) - 50 Hz 60 Hz 355.0 (93.8) - Electronic Governing Class: Max. Combustion Air Intate Restriction: kPa (in H2O) ISO 8528 G2 Compression Ratio: 13.6:1 Cooling System Displacement: l (cu. in) 61.1 (3730.0) Moment of Inertia: kg m² (lb/in²)...

 Open the catalog to page 2
P2000- P2200E Open Generator Set-3

Alternator Physical Data Alternator Operating Data Insulation Class: Winding Pitch Code: Ingress Protection Rating: Excitation System: Leroy Somer Voltage Reguation: (Steady state) Wave Form NEMA = TIF: Total Harmonic content LL/LN: Radio Interference: Radiant Heat: kW(Btu/min) Suppression is in line with European Reactances shown are applicable to prime ratings. *Based on 30% voltage dip at 0.6 power factor. **With optional permanent magnet generator or AREP excitation.

 Open the catalog to page 3
P2000- P2200E Open Generator Set-4

General Information Documentation A full set of operation and maintenance manuals and circuit wiring diagrams. Generating Set Standards The equipment meets the following standards: BS5000, ISO 8528, ISO 3046, IEC 60034, NEMA MG-1.22. FG Wilson is a fully accredited ISO 9001 company. Warranty All prime equipment carries a one year manufacturer's warranty. Standby equipment, limited to 500 running hours per year, has a two year manufacturer's warranty. For details on warranty cover please contact your local Dealer, or visit our website: FGWilson.com. Dealer contact details: FG Wilson has manufacturing...

 Open the catalog to page 4

All FG WILSON catalogs and technical brochures

  1. P2250-3M

    6  Pages

  2. P7.5-4S

    6  Pages

Archived catalogs

  1. Rental Range

    7  Pages

  2. PG345B3

    4  Pages

  3. PG375B3

    4  Pages

  4. PG1250B2

    4  Pages

  5. PG450B1

    4  Pages

  6. PG525B1

    4  Pages

  7. P7.5-4S

    4  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.