1. Catalogs
  2. FG WILSON
  3. P200-4 (200 kVA) EU II Compliant Open Generator Set
video corpo

P200-4 (200 kVA) EU II Compliant Open Generator Set

P200-4 (200 kVA) EU II Compliant Open Generator Set

P200-4 (200 kVA) EU II Compliant Open Generator Set

Product catalog summary
Prime Rating: This rating is for continuous electrical power supply at variable load, replacing commercially purchased power. It allows for 10% overload for 1 hour in every 12 hours with no annual operation limit.
Standby Rating: Used for continuous power supply during utility failures, with no overload permitted. The alternator is peak continuous rated as per ISO 8528-3.
Standard Reference Conditions: Conditions include 25°C air inlet temperature, 100m altitude, and 30% relative humidity. Fuel consumption is based on diesel fuel with specific gravity of 0.85, conforming to BS2869: 1998, Class A2.
Output Ratings and Performance Data: The generator set is available in various voltage and frequency configurations, with specific ratings for prime and standby power. The engine is a Perkins® 1106C-E66TAG4, and the alternator is manufactured by Marelli.
Dimensions and Weights: The generator set has specific dimensions and weights for dry and wet conditions, with detailed measurements provided.
Fuel Consumption: Detailed fuel consumption data is provided for different load levels at both 50 Hz and 60 Hz frequencies.
Available Options: FG Wilson offers various optional features, including CE certification upgrades, sound attenuated enclosures, control panels, additional alarms, and exhaust silencers.
Exhaust System: Specifications include maximum allowable back pressure, exhaust gas flow, and temperature for both prime and standby modes.
Lubrication and Cooling Systems: Details on oil filter type, oil capacity, cooling system capacity, and heat rejection are provided.
Engine Technical Data: Includes information on the number of cylinders, cycle, bore/stroke, induction, engine speed, and performance metrics.
Alternator Physical Data: Specifications include the number of bearings, insulation class, winding pitch code, and excitation system.
Generator Set Standards: The equipment complies with standards such as BS5000, ISO 8528, ISO 3046, IEC 60034, and NEMA MG-1.22. FG Wilson is ISO 9001 accredited and EU stage II emissions compliant.
Warranty: Prime equipment has a one-year warranty, while standby equipment has a two-year warranty limited to 500 running hours per year.
See more

Catalog excerpts

P200-4 (200 kVA) EU II Compliant Open Generator Set-1

P200-4 Image for illustration purposes only. Output Ratings Ratings and Performance Data Voltage, Frequency Engine Make & Model: Alternator manufactured for FG Wilson by: Alternator Model: Ratings at 0.8 power factor. Control Panel: Please refer to the output ratings technical data section for specific generator set outputs per voltage. Base Frame: Heavy Duty Fabricated Steel Circuit Breaker Type: Frequency: Prime Rating These ratings are applicable for supplying continuous electrical power (at variable load) in lieu of commercially purchased power. There is no limitation to the annual hours of operation and this model can supply 10% overload power for 1 hour in 12 hours. Standby Rating These ratings are applicable for supplying continuous electrical power (at variable load) in the event of a utility power failure. No overload is permitted on these ratings. The alternator on this model is peak continuous rated (as defined in ISO 8528-3). Standard Reference Conditions Note: Standard reference conditions 25°C (77°F) Air Inlet Temp, 100m (328 ft) A.S.L. 30% relative humidity. Fuel consumption data at full load with diesel fuel with specific gravity of 0.85 and conforming to BS2869: 1998, Class A2. Fuel Tank Capacity: Fuel Consumption: l/hr (US gal/hr) - Prime Available Options FG Wilson offer a range of optional features to tailor our generator sets to meet your power needs. Options include: Upgrade to CE Certification A wide range of Sound Attenuated Enclosures A variety of generator set control and synchronising panels Additional alarms and shutdowns A selection of exhaust silencer noise levels For further information on all of the standard and optional features accompanying this product please contact your local Dealer or visit: www.FGWilson.com Dimensions and Weights Length (L) Wet = With Lube Oil and Coolant Ratings in accordance with ISO 8528, ISO 3046, IEC 60034, BS5000 and NEMA MG-1.22. Generator set pictured may include optional accessories.

 Open the catalog to page 1
P200-4 (200 kVA) EU II Compliant Open Generator Set-2

Engine Technical Data Paper Element Combustion Air Flow: m³/min (cfm) Bore / Stroke: mm (in) Induction: Turbocharged Air To Air Charge Cooled Cooling Method: Governing Type: Governing Class: Max. Combustion Air Intake Restriction: kPa (in H2O) Compression Ratio: Cooling System Moment of Inertia: kg m² (lb/in²) Cooling System Capacity: l (US gal) Water Pump Type: Engine Electrical System: - Voltage / Ground - Battery Charger Amps Weight: kg (lb) Heat Rejected to Water & Lube Oil: Heat Radiation to Room: Heat radiated from engine and alternator - Prime Radiator Fan Load: kW (hp) Performance Radiator...

 Open the catalog to page 2
P200-4 (200 kVA) EU II Compliant Open Generator Set-3

Alternator Physical Data Alternator Operating Data Voltage Regulation: (Steady state) Wave Form NEMA = TIF: No. of Bearings: Insulation Class: Winding Pitch Code: Total Harmonic content LL/LN: Ingress Protection Rating: Radio Interference: Suppression is in line with European Standard EN55011 Radiant Heat: kW (Btu/min) Excitation System: Alternator Performance Data: Data Item Motor Starting Capability* kVA Short Circuit Capacity % Reactances: Per Unit Reactances shown are applicable to prime ratings. *Based on 30% voltage dip at 0 power factor. Output Ratings Technical Data 50 Hz Voltage Output...

 Open the catalog to page 3
P200-4 (200 kVA) EU II Compliant Open Generator Set-4

General Information Documentation A full set of operation and maintenance manuals and circuit wiring diagrams. Generator Set Standards The equipment meets the following standards: BS5000, ISO 8528, ISO 3046, IEC 60034, NEMA MG-1.22. FG Wilson is a fully accredited ISO 9001 company. EU stage II emissions compliant. Warranty All prime equipment carries a one year manufacturer's warranty. Standby equipment, limited to 500 running hours per year, has a two year manufacturer's warranty. For details on warranty cover please contact your local Dealer, or visit our website: FGWilson.com. Dealer contact...

 Open the catalog to page 4

All FG WILSON catalogs and technical brochures

  1. P2250-3M

    6  Pages

  2. P7.5-4S

    6  Pages

Archived catalogs

  1. Rental Range

    7  Pages

  2. PG345B3

    4  Pages

  3. PG375B3

    4  Pages

  4. PG1250B2

    4  Pages

  5. PG450B1

    4  Pages

  6. PG525B1

    4  Pages

  7. P7.5-4S

    4  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.