Prime Rating: This rating is for continuous electrical power supply at variable load, replacing commercially purchased power. It allows for 10% overload for 1 hour in every 12 hours without annual operation limits.
Standby Rating: This rating is for continuous power supply during utility power failures, with no overload permitted. The alternator is peak continuous rated as per ISO 8528-3.
Standard Reference Conditions: Conditions include 25°C air inlet temperature, 100m above sea level, and 30% relative humidity. Fuel consumption is based on diesel fuel with specific gravity of 0.85, conforming to BS2869: 1998, Class A2.
Output Ratings and Performance Data: The generator set is manufactured by FG Wilson with a Leroy Somer alternator. It includes various specifications such as voltage, frequency, engine model, and control panel details. The generator is designed to operate in ambient conditions up to 50°C.
Available Options: FG Wilson offers options like CE Certification upgrades, sound attenuated enclosures, control panels, additional alarms, and exhaust silencer noise levels.
Exhaust System: Details include maximum allowable back pressure, exhaust gas flow, and temperature.
Lubrication and Cooling Systems: Specifications cover oil filter type, total oil capacity, cooling system capacity, and heat rejection data.
Engine Technical Data: Includes number of cylinders, cycle, bore/stroke, induction, engine speed, and performance metrics.
Fuel System: Uses Class A2 Diesel or BSEN590 with specific fuel consumption rates at various loads.
Alternator Physical and Performance Data: Manufactured by Leroy Somer, it includes details on bearings, insulation class, excitation system, and voltage regulation.
Generator Set Standards: Complies with BS5000, ISO 8528, ISO 3046, IEC 60034, and NEMA MG-1.22 standards. FG Wilson is ISO 9001 accredited.
Warranty: Prime equipment has a one-year unlimited hours warranty or a two-year warranty limited to 6,000 hours. Standby equipment has a three-year warranty limited to 500 hours per year.
See more

Catalog excerpts

P1825-P2000E (1825-2000 kVA) Open Generator Set-1

P1825/P2000E Image for illustration purposes only. Output Ratings Ratings and Performance Data Voltage, Frequency Engine Make & Model: Alternator manufactured for FG Wilson by: Leroy Somer Alternator Model: Ratings at 0.8 power factor. Control Panel: Please refer to the output ratings technical data section for specific generator set outputs per voltage. Base Frame: Heavy Duty Fabricated Steel Circuit Breaker Type: Frequency: Prime Rating These ratings are applicable for supplying continuous electrical power (at variable load) in lieu of commercially purchased power. There is no limitation to the annual hours of operation and this model can supply 10% overload power for 1 hour in 12 hours. Standby Rating These ratings are applicable for supplying continuous electrical power (at variable load) in the event of a utility power failure. No overload is permitted on these ratings. The alternator on this model is peak continuous rated (as defined in ISO 8528-3). Standard Reference Conditions Note: Standard reference conditions 25°C (77°F) Air Inlet Temp, 100m (328 ft) A.S.L. 30% relative humidity. Fuel consumption data at full load with diesel fuel with specific gravity of 0.85 and conforming to BS2869: 1998, Class A2. Fuel Tank Capacity: Fuel Consumption: l/hr (US gal/hr) - Prime 378.2 (99.9) Available Options FG Wilson offer a range of optional features to tailor our generator sets to meet your power needs. Options include: Upgrade to CE Certification A wide range of Sound Attenuated Enclosures A variety of generator set control and synchronising panels Additional alarms and shutdowns A selection of exhaust silencer noise levels For further information on all of the standard and optional features accompanying this product please contact your local Dealer or visit: www.FGWilson.com Dimensions and Weights Length (L) Wet = With Lube Oil and Coolant Ratings in accordance with ISO 8528, ISO 3046, IEC 60034, BS5000 and NEMA MG-1.22. Generator set pictured may include optional accessories.

 Open the catalog to page 1
P1825-P2000E (1825-2000 kVA) Open Generator Set-2

Engine Technical Data Combustion Air Flow: m³/min (cfm) Turbocharged Air To Air Charge Cooled Replaceable Element Cooling Method: Governing Type: Governing Class: Max. Combustion Air Intake Restriction: kPa (in H2O) Compression Ratio: Cooling System Moment of Inertia: kg m² (lb/in²) Cooling System Capacity: l (US gal) Water Pump Type: Engine Electrical System: - Voltage / Ground - Battery Charger Amps Weight: kg (lb) Heat Rejected to Water & Lube Oil: - Prime 586.0 (33325) Heat Radiation to Room: Heat radiated from engine and alternator - Prime 171.2 (9736) - Standby 185.0 (10521) Radiator Fan...

 Open the catalog to page 2
P1825-P2000E (1825-2000 kVA) Open Generator Set-3

Alternator Physical Data Alternator Operating Data Insulation Class: Winding Pitch Code: Ingress Protection Rating: Excitation System: Leroy Somer Voltage Regulation: (Steady state) Wave Form NEMA = TIF: Total Harmonic content LL/LN: Radio Interference: Radiant Heat: kW (Btu/min) Suppression is in line with European Performance Data: Motor Starting Short Circuit Reactances shown are applicable to prime ratings. *Based on 30% voltage dip at 0.4 power factor. **With optional permanent magnet generator.

 Open the catalog to page 3
P1825-P2000E (1825-2000 kVA) Open Generator Set-4

General Information A full set of operation and maintenance manuals and circuit wiring diagrams. The equipment meets the following standards: BS5000, ISO 8528, ISO 3046, IEC 60034, NEMA MG-1.22. FG Wilson is a fully accredited ISO 9001 company. All prime equipment carries a one year manufacturer's warranty with unlimited hours or two year manufacturer's warranty limited to 6,000 running hours. Standby equipment, limited to 500 running hours per year, has a three year manufacturer's warranty. Dealer contact details: FG Wilson manufactures product in the following locations: Northern Ireland •...

 Open the catalog to page 4

All FG WILSON catalogs and technical brochures

  1. P2250-3M

    6  Pages

  2. P7.5-4S

    6  Pages

Archived catalogs

  1. Rental Range

    7  Pages

  2. PG345B3

    4  Pages

  3. PG375B3

    4  Pages

  4. PG1250B2

    4  Pages

  5. PG450B1

    4  Pages

  6. PG525B1

    4  Pages

  7. P7.5-4S

    4  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.