1. Catalogs
  2. FEAS GmbH
  3. LDR40MH12-HT

LDR40MH12-HT

LDR40MH12-HT

Product catalog summary
General Overview: The LDR40MH12-HT is a DC power supply with an integrated accupack, designed for uninterrupted power supply (DC-USV) applications. It is identified by the FEAS order number 589933.
Input Specifications: The device accepts an AC input voltage range of 85 - 270V (0-400Hz) and a DC input voltage range of 120 - 400V. The input current at nominal load is 1.3A at 115V and 0.65A at 230V, with a peak input current of less than 17A at 230VAC. It includes a transient voltage suppressor varistor for protection.
Output Specifications: The power supply provides an output voltage of 12VDC with a nominal output current of 8.0A. It has a power rating of 96 Watts and a residual ripple of less than 25mVPP. The buffered voltage ranges from 9.0 to 13.0 VDC, following the accu-voltage.
Control Data: The control deviation with load variation is less than 200 mV for 10-90% variation and less than 25 mV for ±10% variation. The control time is less than 10ms for load variation between 10-90%. The typical buffered time is 30 minutes with a capacity of 6.0 Ah at 20°C.
Operating Conditions: The device operates at 100% duty cycle within a temperature range of -40°C to +70°C. It features self-cooling and has an efficiency of approximately 86% in grid mode. The installation altitude is unlimited, and the MTBF is greater than 380,000 hours without the accupack.
Safety and Protection: The power supply includes a 2.5A slow blow fuse for 115V and a 1.25A slow blow fuse for 230V. It is short circuit proof and integrates overload protection. It meets various safety standards, including VDE0570, VDE0806, and EN62368.
Mechanical and Environmental Data: The dimensions are 83mm x 161mm x 160.5mm, and it weighs approximately 3.5kg. It can be mounted on a DIN-rail or wall. The device is IP65 rated for protection class and can withstand vibrations greater than 30g at 33Hz.
Compliance and Standards: The LDR40MH12-HT complies with multiple international standards, including CSA/UL, VDE, IEC, and EN regulations, ensuring its reliability and safety in various applications.
Additional Features: The device includes status indicators for input, charging, buffer mode, and temperature, as well as relay input and accu-protection signals.
See more

Catalog excerpts

LDR40MH12-HT-1

Technical data Withdrawable capacity in % of the nominal capacity at different temperatures General data Mechanical data Mounting On DIN-rail or on wall with screws E-Mail: [email protected] Internet: www.feas.com

 Open the catalog to page 1

All FEAS GmbH catalogs and technical brochures

  1. SNT9424-3

    1  Page

  2. GSLC2

    1  Page

  3. GSNT90

    1  Page

  4. PSW250

    1  Page

  5. PSW500T

    1  Page

  6. PSLC3

    1  Page

  7. LDR40MH12-HT

    1  Page

  8. SNT9112

    1  Page

  9. SNT12612

    1  Page

  10. PSW15012

    1  Page

  11. PS2W15012

    1  Page

  12. PSGK10

    1  Page

  13. MPS10024/05

    1  Page

  14. SNT8005

    1  Page

  15. SNT1405

    1  Page

  16. SNT1205

    1  Page

  17. PS2W15005

    1  Page

  18. PSLC1

    1  Page

  19. PSLC051

    1  Page

  20. PSGK05

    1  Page

  21. SNT12812

    1  Page

  22. LDR40MH12-HT

    1  Page

  23. PSW15005

    1  Page

Archived catalogs

  1. FEAS Catalogue

    24  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.