1. Catalogs
  2. F.E.A.M. s.r.l.
  3. Lighting fixtures
video corpo

Lighting fixtures

Lighting fixtures
1 / 94 PagesView full catalog

Lighting fixtures

Product catalog summary
Overview: This document is a comprehensive technical catalogue for explosion-proof and weatherproof lighting fixtures, detailing specifications, mechanical and electrical characteristics, compliance standards, and installation options for various lighting products, including floodlights and street lighting fixtures.
Specifications: The luminaires are designed for hazardous areas with explosion-proof features, constructed from marine-grade copper-free aluminum and high-temperature resistant borosilicate glass. They comply with IP66 protection standards and are suitable for ambient temperatures ranging from -60°C to +60°C. Electrical characteristics include power supply options of 120, 230, or 277 Vac at 700mA, with LED configurations offering high efficiency.
Mechanical Characteristics: The equipment features robust construction with marine-grade aluminum bodies, tempered glass diffusers, and stainless steel components. External painting is done with epoxy powders in grey RAL-9006 color, ensuring durability and resistance to environmental conditions.
Electrical Characteristics: The lighting fixtures operate on a 230V - 50Hz power supply with options for conventional or electronic ballasts. They include high-temperature resistant silicon rubber insulation cables and porcelain lampholders.
Compliance and Standards: The products comply with Directive 94/9/EC and Directive 2014/34/EU, with certifications such as INERIS, IECEx, and others. They meet EN/IEC standards, ensuring safety and reliability in hazardous environments.
Installation and Mounting: Suitable for hazardous areas in Zone 1/2 for gases and Zone 21/22 for dusts, with various mounting options including ceiling, wall, and pole installations. Accessories for mounting include stainless steel and aluminum hardware.
Photometric Data: The document provides detailed photometric data, including luminaire flux, power, efficacy, and efficiency for various models. Polar diagrams illustrate light intensity distribution.
Performance Data: The efficacy and efficiency of the luminaires are highlighted, with models showing high performance metrics. The document includes performance data such as maximum value in cd/klm and gamma angles.
Accessories: Optional accessories include different external painting colors, cable entry options, and mounting kits. Protection guards and electronic devices for auxiliary lamps are also available.
Remarks: The document notes that technical characteristics are subject to change based on national and international specifications and technological advancements.
See more

Catalog excerpts

Lighting fixtures-1

EVF Lighting fixtures for fluorescent tube lamps and LED Explosion Proof Electrical Equipment Installation: hazardous areas - Zone 1 / 2 (Gases) - Zone 21 / 22 (Dusts) Classification: Group II - Category 2G 2D REFERENCE STANDARDS Directive 94/9/EC (until April 19th, 2016) and Directive 2014/34/EU (from April 20th, 2016) II 2G Ex d IIC T6 Gb II 2D Ex tb IIIC T85°C Db EXECUTION RULES OF COMPLIANCE EN/IEC 60079-0; EN/IEC 60079-1; EN/IEC 60079-31; PROTECTION DEGREE AMBIENT TEMPERATURE OTHER AVAILABLE CERTIFICATES IECEx: IECEX INE 13.0055X INMETRO: CEPEL 13.2291X RUSSIAN MARINE CERTIFICATE (RMRS): 13.03516.315 (-60°C ÷ +60°C) Mechanical characteristics Body marine grade copper free aluminium (control gear & emergency unit ) high-temperature resistant borosylicate glass tube external epoxy powders grey RAL-9006 colour external stainless steel silicon rubber O-Ring white stove enamelled sheet steel Cable entry Electrical characteristics for fluorescent lamps Power supply elettronic ballast 110÷260V AC/DC 50/60 Hz (p.f.corrected - cos ρ ≥ 0,98) Emergency unit emergency unit composed of inverter charger and Ni-Cd battery pack 4A/h 4.8v. autonomy 120min. LED power-on indicating lamp provided - (inverter) 220÷240V 50/60Hz Bartec Feam Catalog

 Open the catalog to page 1
Lighting fixtures-2

Explosion Proof Electrical Equipment Electrical characteristics for LED lamps Power supply • Pole mounting kit complete with stainless steel hardware • Ceiling mounting kit complete with stainless steel hardware • Pendant mounting kit complete with stainless steel hardware • Wall/Structure mounting kit complete with stainless steel hardware • Galvanized steel wire protection guard • Stainless steel wire protection guard • Stainless steel reflectors • External painting colour on request • Electronic ballast with voltage supply different than standard EVF Technical data CODE TEMPERATURE CLASS (DUSTS)...

 Open the catalog to page 2
Lighting fixtures-3

Explosion Proof Electrical Equipment CABLE ENTRY EVF Installation and mounting details Ceiling mounting Pendant mounting Pole mounting Assemblig detail with pole (typical) Wall/structure mounting Bartec Feam Catalogue 04 I

 Open the catalog to page 3
Lighting fixtures-4

Explosion Proof Electrical Equipment EVF Polar diagrams – photometric data EVF118EL chio AppArepareicchio a p cch o Apparecchio Rilievo RilieRilievo vo Rilievo ApLampadao parecchi ApLaAecaarao chio pamLp mpc da r p a d ea p chi ApLampadao parecchi Rilievo Rilievolievo Ri Rilievo Apparecchio Lampada ApLmrLiamipe da La umada ria pa p cch o e na Apparecchio Lampada Rilievo Rileasurem. Rilievo Lampada Lampada Lampada Mievo Lamp EVFF-18 CodiCe dicEVFE-1FF-18 Codice EVFF-18 Codice FEA22 c o e FV 8 CodiCe dFEAF2 A22 c o ice 2E Codice FEA22 oCiodiceEVFF-36 CoCioCodiEe FF-36 F-18/C0CiodiceEVFF-36 /20...

 Open the catalog to page 4
Lighting fixtures-5

EVFG Lighting fixtures for fluorescent tube lamps and LED Explosion Proof Electrical Equipment Installation: hazardous areas - Zone 1 / 2 (Gases) - Zone 21 / 22 (Dusts) Classification: Group II - Category 2G 2D REFERENCE STANDARDS Directive 94/9/EC (until April 19th, 2016) and Directive 2014/34/EU (from April 20th, 2016) II 2 G Ex d IIC T6 Gb II 2 G Ex de IIC T6 Gb II 2 D Ex tb IIIC T85°C Db EXECUTION RULES OF COMPLIANCE EN/IEC 60079-0; EN/IEC 60079-1; EN/IEC 60079-7; EN/IEC 60079-31; EC Type-Examination Certificate PROTECTION DEGREE AMBIENT TEMPERATURE OTHER AVAILABLE CERTIFICATES IECEx: IECEx...

 Open the catalog to page 5
Lighting fixtures-6

Explosion Proof Electrical Equipment EVFG Technical data CODE TEMPERATURE CLASS (DUSTS) EMERGENCY UNIT FLUORESCENT LIGHTING FIXTURES FOR SINGLE AND TWIN LAMPS - POWER SUPPLY 110÷260Vac/dc T6 *d: for Exd version (Ex. EVFGd120LED) - Without “d” for Exde version (Ex. EVFG120LED) EMERGENCY FLUORESCENT LIGHTING FIXTURES FOR SINGLE AND TWIN LAMPS - POWER SUPPLY (inverter) 220÷240V 50/60Hz EVFG*E18 *d: for Exd version (Ex. EVFGdE236) - Without “d” for Exde version (Ex. EVFGE236) EMERGENCY OPERATING WITH ONE TUBE LAMP ONLY AS STANDARD LED LIGHTING FIXTURES FOR SINGLE AND TWIN LAMPS - POWER SUPPLY 100÷240Vac...

 Open the catalog to page 6
Lighting fixtures-7

Explosion Proof Electrical Equipment EVFG Technical features Reference details EVFG EVFG CABLE ENTRY *= 1 or 2: 1= single lamp - 2= twin lamp EVFG Installation and mounting details type 2 Pendant mounting Ceiling mounting

 Open the catalog to page 7
Lighting fixtures-8

Explosion Proof Electrical Equipment EVFG Installation and mounting details Wall/structure mounting Pole mounting Assemblig detail with pole (typical) EVFG Polar diagrams – photometric data EVFG218 Gamma Angle Gamma Angle Gamma Angle DESCRIPTION PROTECTION GUARD FOR 18W FL and 9W LED LIGHTING FIXTURES PROTECTION GUARD FOR 36W FL and 20W LED LIGHTING FIXTURES PROTECTION GUARD FOR 58W FL and 27W LED LIGHTING FIXTURES PROTECTION GUARD FOR 18W FL and 9W LED LIGHTING FIXTURES PROTECTION GUARD FOR 36W FL and 20W LED LIGHTING FIXTURES PROTECTION GUARD FOR 58W FL and 27W LED LIGHTING FIXTURES CEILING...

 Open the catalog to page 8
Lighting fixtures-9

EVAC Lighting fixtures for incandescent and discharge lamps Explosion Proof Electrical Equipment Installation: hazardous areas - Zone 1 / 2 (Gases) - Zone 21 / 22 (Dusts) Classification: Group II - Category 2G 2D REFERENCE STANDARDS Directive 94/9/EC (until April 19th, 2016) - Directive 2014/34/EU (from April 20th, 2016) II 2 G Ex d IIC T6÷T2 Gb II 2 D Ex tb IIIC T85°C-T225°C Db EXECUTION RULES OF COMPLIANCE EN/IEC 60079-0; EN/IEC 60079-1; EN/IEC 60079-31 PROTECTION DEGREE AMBIENT TEMPERATURE OTHER AVAILABLE CERTIFICATES IECEx: IECEx INE 13.0075X INMETRO: CEPEL 14.2311X EAC: TC RU C-IT.ГБ08.В.01342...

 Open the catalog to page 9
Lighting fixtures-10

Explosion Proof Electrical Equipment EVAC Technical data CODE TEMPERATURE CLASS ( DUSTS ) LAMPHOLDER SIZE CABLE ENTRY SIZE LIGHTING FIXTURE FOR INCANDESCENT LAMPS - POWER SUPPLY 230V-50Hz T4 LIGHTING FIXTURE FOR HALOGEN LAMP - POWER SUPPLY 230V-50Hz LIGHTING FIXTURE FOR HIGH PRESSURE MERCURY VAPOUR LAMP - POWER SUPPLY 230V 50Hz EVAC101-80HG LIGHTING FIXTURE FOR HIGH PRESSURE SODIUM LAMP - POWER SUPPLY 230V 50Hz T4 LIGHTING FIXTURE FOR METAL HALIDE LAMP - POWER SUPPLY 230V 50Hz EVAC101-100MH LIGHTING FIXTURE FOR BLENDED LIGHT LAMP - POWER SUPPLY 230V 50Hz EVAC201-160MLL 10 I Bartec Feam Catalogue...

 Open the catalog to page 10

All F.E.A.M. s.r.l. catalogs and technical brochures

  1. Miscellaneous

    12  Pages

  2. Enclosures

    50  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.