flox[on] S

flox[on] S

flox[on] S

Product catalog summary
Overview: The flox[on] S is a mass flow controller designed for precise gas flow regulation. It is manufactured by FC Technik and is intended for use with gases only.
Specifications:
  • Maximum Flow: 1650 Nl/min
  • Minimum Flow: 70 Nl/min
  • Maximum Operating Pressure: 16 bar
  • Regulation Ratio: 1:40
  • Accuracy: ±3%
  • Step Response: 1 to 5 seconds
  • Operating Temperature: -10°C to +60°C
Materials:
  • Housing and Flange Connector: Aluminium
  • Valve and Sinter Filter: Brass
  • Sealing: NBR
Electrical Equipment:
  • Connection Voltage: 24 V DC ± 15%
  • Capacity: Max 20 W
  • Signal Set/Real: 4-20 mA
Installation and Maintenance:
  • Install horizontally to avoid faulty measurements.
  • Maintenance-free under harsh conditions.
  • Store in dry conditions for up to two years before installation.
Calibration: The measuring cell is pre-calibrated with atmospheric air. Calibration with specific gases is available upon request. No recalibration is needed for the device's lifetime.
Important Notices:
  • Use only with gases; liquids will damage the measuring cell.
  • Incorrect wiring can destroy electronics.
  • Particulate matter may clog filters and reduce performance.
Guarantee: The flox[on] S comes with a 2-year guarantee.
Contact Information: FC Technik AG, St. Gallerstrasse 340, CH-8409 Winterthur, Tel. +41 (0) 52 238 01 75, Fax +41 (0) 52 238 01 77, www.fc-technik.ch, [email protected]
See more

Catalog excerpts

flox[on] S-1

FCTechnik M ass f low contro ller Data sheet flox[on] S | October 2013 | Page 1 3 Outlet flange with thread connection 5 4 Inlet flange with thread connection 5 Micro-processor board Data o p e rat i o n Maximum flow Minimum flow Maximum operating pressure Regualtion ratio Operating temperature Flange connector Sinter filter E le ct ri ca l e q u i p m e n t Connection voltage Capacity max. Connection analog Signal Set/Real Bypass Signal All information is provided in best conscience. Some clients may desire certain modifications which lead to results other than those found in this manual.

 Open the catalog to page 1
flox[on] S-2

Data sheet flox[on] S | October 2013 | Page 2 connection assignment Ready In operation Fully open Fault Before delivery, the measuring cell in every flox[on] S is calibrated with atmospheric air. There are correction factors for applications using other gases. In individual cases, if desired by the client, the calibration can be made directly with the specific gas intended for use. The measuring cell does not require a recalibration for the rest of its operating life. If a mixed gas such as air or natural gas is used, it should be noted that a change in the composition of the gas can occur during...

 Open the catalog to page 2
*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.