data sheet flox[on] B new

data sheet flox[on] B new

data sheet flox[on] B new

Product catalog summary
Overview: The flox[on] B is a mass flow controller designed by FCTechnik, primarily used for gas flow regulation. It operates on the principle of thermal anemometry and is equipped with a high-performance microcontroller.
Specifications:
  • Available in three versions: Economy, Extended, and Stainless Steel.
  • Maximum flow rate: 200-250 Nl/min.
  • Minimum flow rate: 0.5 Nl/min.
  • Maximum operating pressure: 16 bar.
  • Regulation ratio: 1:30 to 1:50.
  • Device accuracy: 1% Full Scale.
  • Step response time: 1.5 seconds or less.
  • Operating temperature: -10 to +60°C.
Materials:
  • Economy and Extended versions use Aluminium and Brass.
  • Stainless Steel version uses steel X2CrNi18-9 and X2CrNiMo17-12-2.
  • Sealing materials include NBR and FPM.
Connections:
  • M8 Power Supply: 24 VDC, 0 V, PE Ground.
  • M12 Analog Connector: Set and Real Value 4-20 mA, Digital Input 24 VDC.
  • Micro USB port for PC connection.
Calibration:
  • Calibrated with atmospheric air; correction factors available for other gases.
  • Recalibration generally not required unless specified by the client.
Important Notices:
  • Device should be installed horizontally to avoid faulty measurements.
  • Not suitable for liquids; gas condensation can damage the measuring cell.
  • Incorrect wiring can destroy electronics.
Guarantee: The flox[on] B comes with a 2-year guarantee.
Contact Information: FC Technik AG, St. Gallerstrasse 340, CH-8409 Winterthur, Tel. +41 (0) 52 238 01 75, [email protected]
See more

Catalog excerpts

data sheet flox[on] B new-1

FCTechnik M ass f low contr o ller Data sheet flox[on] B | October 2016 | Page 1 7 1 Proportional valve 2 Outlet flange with thread connection 3 Inlet flange with thread connection 4 M8 Power supply 5 M12 Connector signal interface 6 Micro USB port 7 3 LEDs operating mode backsight of flox[on] B economy and extended frontsight of flox[on] B stainless steel connection assignment The USB Port connects the flox]on] B with a PC. LED and operating modus Real value 4-20 mA > AIP Real value All information is provided in best conscience. Some clients may desire certain modifications which lead to results other than those found in this manual.

 Open the catalog to page 1
data sheet flox[on] B new-2

FCTechnik M ass f low contro ller Data sheet flox[on] B | October 2016 | Page 2 Data sh eet flox[on] B | October 2016 | Page 3 ava i la ble m o d ificatio ns o f flox[ o n] B The measurement of all flox[on] B mass flow controller is based on the principle of thermal anemometry. The measuring cell is located in a bypass. The measurement of the gas flow is temperature and pressure compensated. The regulation of the flow will be made by a pressure compensated proportional valve which is insensitive to incoming pressure (0-16 bar) as well as outflow pressure. The valve is controlled by a solenoid...

 Open the catalog to page 2
data sheet flox[on] B new-3

Data sheet flox[on] B | October 2016 | Page 4 T o ensure trouble-free operation, the flox[on] B should be installed in a horizontal position. If installed vertically, the device could produce faulty measurements under certain conditions. Before delivery, the measuring cell in every flox[on] B is calibrated with atmospheric air. There are correction factors for applications using other gases. In individual cases, if desired by the client, the calibration can be made directly with the specific gas intended for use. The flox[on] B is maintenance-free even under harsh conditions. In case of a fault...

 Open the catalog to page 3
*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.