FV20C

FV20C

Product catalog summary
Specifications:
1. Remote Control Contact: Available for models with 'S'.
2. AC Specifications: Voltage ≤250V, Current ≤0.5A, Single core wire max 1.5mm².
3. DC Specifications: Voltage ≤60V, Current ≤0.1A, Multi-core wire max 1.3mm².
4. Model Variants: FV20C/4-150(S), FV20C/4-275(S), FV20C/4-320(S), FV20C/4-385(S), FV20C/4-440(S).
5. Test Class: IEC/EN/VDE Class II/C.
6. Network Type: TT, TN.
7. Protection Mode: L1, L2, L3, N-PE.
8. Nominal Voltage: 110V/220V ac to 230V/400V ac.
9. Rated Voltage (UC): 150V ac to 440V ac.
10. Max Discharge Current (Imax): 40kA.
11. Nominal Discharge Current (In): 20kA.
12. Voltage Protective Level (Up): ≤0.7kV to ≤2.0kV.
13. Response Time (tA): ≤25ns.
14. Recommended Back-up Fuse: 125A.
15. Isolation Resistance: >10 MΩ.
16. I/O Connections: Multi-core wire: 4mm² ~ 25mm².
17. Mounting: 35mm Symmetrical rail (EN50022/DIN46277-3).
18. Operation Temperature Range: -40℃ to +80℃.
19. Humidity: 30% to 90%.
20. Altitude: Up to 3000m.
21. Degree of Protection: IP20.
22. Housing Material: UL94 V-0.
23. Disconnection Indicator: Mechanical indicator (Green: OK, Red: replace).
24. Remote Control Contact: Optional.

Procedures and Recommendations:
- The device consists of a base part and MOV pluggable protection modules.
- Designed for use in lightning protection zones at boundary 1-2.
- Core parts are metal oxide varistor components with high discharge capacity.
- Features low residual voltage and quick response.
- Reliable control with Thermo Dynamic Control disconnector.
- Fault indication via red mark in the inspection window.

Additional Information:
- For models without 'S', the remote control contact function is not available.
- For more details, visit www.fatech-surge-protection.com.
See more

Catalog excerpts

FV20C-1

Surge Protective Device for Low-voltage Power System ♦ Consisting of a base part and MOV pluggable protection modules. ♦ For using in the lightning protection zones concept at boundary 1-2. ♦ The core parts are metal oxide vristor components with high discharge capacity. ♦ Low residual voltage and quick response. ♦ Reliable control thanks to Thermo Dynamic Control disconnector. ♦ With remote signaling contact for control device. ♦ Fault indication via red mark in the inspection window. ♦ Protection mode: L1,L2,L3,N-PE. Remark: if the model number is without“S”, the model is without remote control contact function

 Open the catalog to page 1

All FATECH ELECTRONIC (FOSHAN) CO., LTD catalogs and technical brochures

  1. iSPD

    4  Pages

  2. iSPD-M

    4  Pages

  3. FLP03-320-S/G

    2  Pages

  4. FLP03-275-S/G

    2  Pages

  5. FLP03-275-P/G

    2  Pages

  6. FLP03-24-P/G

    2  Pages

  7. FV30B+C/4

    1  Page

  8. FV10D/2

    1  Page

  9. FV40C/3+NPE

    1  Page

  10. FLRC-S/II

    1  Page

  11. FLRC-D

    1  Page

  12. FV30B+C

    1  Page

  13. FLRC-L

    1  Page

  14. FLRC-S/D

    1  Page

  15. FV20C/3

    1  Page

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.